Closed GoogleCodeExporter closed 9 years ago
Discussed this system with Kyle, and although some testing needs to be done, it
is likely that representing the two-pipe system per Concept #1 should be fine;
below is an updated description.
Before we make this any more of a priority, I reviewed the ACM and did not find
two-pipe systems listed in the ACM. I've added John to this issue, but since
it is not in the ACM, this suggests that this is not a Release 1 priority?
Roger/John, can you confirm before we add this to the SDD updates/instances?
Two-pipe systems
SDD description:
ZoneSystem:Type = TPFC (two-pipe fan coil)
FluidSystem:Type = TwoPipeWater. Would assign both chiller and boiler to the
Primary FluidSegs of this System
ZnSys has both CoilHtg and CoilClg children, connected to the same
FluidSegments of the two-pipe fluid system.
FluidSystem includes new properties: ChangeOverTemperature and
ChangeOverDeadband.
Clg/Htg availabilty schedules would also be added to FluidSystem to allow for
defining seasonal availability as well.
OS/E+ description:
- ZoneHVAC:FourPipeFanCoil would represent the air-side
- A single PlantLoop with both Chiller and Boiler objects to the Primary
FluidSegs of this System
- OA reset setpoint controller would be used to controller the change-over
behavior. The control inputs would be generated from the ChangeOverTemperature
and ChangeOverDeadband properties
Kyle - will add OA reset setpoint controller for two-pipe changeover control
and test configuration
Dave - Add necessary properties to FluidSystem and ZoneSystem and create SDD
instance file
Original comment by da...@360-analytics.com
on 6 May 2013 at 9:48
Changing priority to Low. This is not a baseline system and is not explicitly
required to be modeled by the current ACM. I don't think this should be
required in the Version 1 CBECC release.
Original comment by JohnJArent
on 6 May 2013 at 10:16
OA Reset has been added.
Original comment by kbe...@gmail.com
on 6 May 2013 at 10:18
Well, we needed OA reset anyways for hot/chilled water loops (see prototype
00400), so no lost time there. Roger, can you confirm with Martha that this
change is acceptable?
Original comment by da...@360-analytics.com
on 6 May 2013 at 10:23
I'll confirm with Martha.
Original comment by rhedr...@archenergy.com
on 6 May 2013 at 11:31
Original comment by rhedr...@archenergy.com
on 9 Dec 2014 at 9:19
Original issue reported on code.google.com by
da...@360-analytics.com
on 1 May 2013 at 6:22