3.4.5 - Daylighting, Daylight Control Requirements #817

Open GoogleCodeExporter opened 9 years ago

GoogleCodeExporter commented 9 years ago
What 90.1 PRM Section(s) are relevant to this issue?

3.4.5 - Daylighting, Daylight Control Requirements

Explanation of issue:

Building descriptor 'Daylight Control Requirements'  identifies conditions 
under which daylighting controls are 'mandatory' and/or 'required'.  What is 
the desired software functionality if the mandatory/required controls are not 
present in the proposed design?

Original issue reported on code.google.com by lu...@360-analytics.com on 20 Oct 2014 at 9:22

GoogleCodeExporter commented 9 years ago
See attached- the proposed design either needs to meet the mandatory 
requirements or qualify for one of the exceptions (documented in the attachment)

A user shouldn't be able to generate a baseline/report if the mandatory 
requirements aren't met AND none of the exceptions are indicated as applicable 
by the user

This has been added to the PRM-RM as well

Original comment by supriya....@pnnl.gov on 20 Oct 2014 at 11:27

GoogleCodeExporter commented 9 years ago
I thought I attached the rule amendment, but I don't see it in the previous 
response. Attaching it again.

Original comment by supriya....@pnnl.gov on 21 Oct 2014 at 6:16