Closed ThomasRanvikEriksen closed 1 year ago
I added a CurrentTransformer which is pointing to the Terminal between a Breaker and the CN for the BusbarSection. Q: Should CT be placed here or on the secondary side of the breaker?
The measurement (Analog) has a refrence to both the Terminal, and the CurrentTransformer as shown i the drawing.
Q: should we also include Voltage as an own measurement?
<cim:Analog rdf:ID="_b64c1205-d433-425f-9861-17e67fd8dd92">
<cim:IdentifiedObject.description>400 Volt Vestfoldstien 2 Analog 1 Current Transformer</cim:IdentifiedObject.description>
<cim:IdentifiedObject.name>04 VESTFO 2 ANALOG1CURRTRA</cim:IdentifiedObject.name>
<cim:Measurement.measurementType>Underground LV Cable Serving Current</cim:Measurement.measurementType>
<cim:Measurement.phases></cim:Measurement.phases>
<cim:Measurement.unitMultiplier>none</cim:Measurement.unitMultiplier>
<cim:Measurement.unitSymbol>A</cim:Measurement.unitSymbol>
<cim:Analog.maxValue>430</cim:Analog.maxValue>
<cim:Analog.minValue>110</cim:Analog.minValue>
<cim:Analog.normalValue>320</cim:Analog.normalValue>
<cim:Analog.positiveFlowIn>false</cim:Analog.positiveFlowIn>
<!--<cim:Measurement.Asset rdf:resource="#_"/>--><!--Can also be used related to an Asset like a tool-->
<cim:Measurement.PowerSystemResources rdf:resource="#_26d2f8aa-b651-46c5-a54d-05948f35f3d2"/>
<cim:Measurement.ACDCTerminal rdf:resource="#_"/>
</cim:Analog>
<cim:AnalogValue rdf:ID="_c284c4f3-db8d-42b0-b8f0-a9614ffd2fb6">
<cim:IdentifiedObject.description>400 Volt Vestfoldstien 2 AnalogValue 1 Current</cim:IdentifiedObject.description>
<cim:IdentifiedObject.name>04 VESTFO 2 ANALOGVALUE1CURR</cim:IdentifiedObject.name>
<cim:MeasurementValue.sensorAccuracy>97.2</cim:MeasurementValue.sensorAccuracy>
<cim:MeasurementValue.timeStamp>2021-08-11T11:45:39.393725Z</cim:MeasurementValue.timeStamp>
<cim:AnalogValue.value>300</cim:AnalogValue.value>
<cim:MeasurementValue.MeasurementValueSource rdf:resource="#_bb396abd-8537-409b-a983-ac1eb907ac30"/>
<cim:MeasurementValue.RemoteSource rdf:resource="#_"/>
<cim:AnalogValue.Analog rdf:resource="#_b64c1205-d433-425f-9861-17e67fd8dd92"/>
</cim:AnalogValue
<cim:CurrentTransformer rdf:ID="_26d2f8aa-b651-46c5-a54d-05948f35f3d2">
<cim:IdentifiedObject.description>400 Volt Vestfoldstien 2 Current Transformer</cim:IdentifiedObject.description>
<cim:IdentifiedObject.name>04 VESTFO 2 CURRTRA</cim:IdentifiedObject.name>
<cim:IdentifiedObject.aliasName>04VFS2CURTRA</cim:IdentifiedObject.aliasName>
<cim:Equipment.aggregate>false</cim:Equipment.aggregate>
<cim:Equipment.inService>true</cim:Equipment.inService> <!--Will be placed in the SSH file-->
<cim:Equipment.networkAnalysisEnabled>true</cim:Equipment.networkAnalysisEnabled>
<cim:Equipment.normallyInService>true</cim:Equipment.normallyInService>
<cim:CurrentTransformer.accuracyClass></cim:CurrentTransformer.accuracyClass>
<cim:CurrentTransformer.accuracyLimit></cim:CurrentTransformer.accuracyLimit>
<cim:CurrentTransformer.coreBurden></cim:CurrentTransformer.coreBurden>
<cim:CurrentTransformer.ctClass></cim:CurrentTransformer.ctClass>
<cim:CurrentTransformer.usage>metering</cim:CurrentTransformer.usage>
<cim:AuxiliaryEquipment.Terminal rdf:resource="#_3d75146a-8de3-44f3-ad93-aec6c820eb9b"/>
</cim:CurrentTransformer>
<cim:MeasurementValueSource rdf:ID="_bb396abd-8537-409b-a983-ac1eb907ac30">
<cim:IdentifiedObject.description>Telemetered values received from a local SCADA system</cim:IdentifiedObject.description>
<cim:IdentifiedObject.name>SCADA</cim:IdentifiedObject.name>
</cim:MeasurementValueSource>
We are modelling 1 CT pr core with its accuracyclass and functionallity
Questions:
Add:
What about measuring Voltage?
<cim:Analog rdf:ID="_b64c1205-d433-425f-9861-17e67fd8dd92">
<cim:IdentifiedObject.description>11 kilo Volt Vestfoldstien 2 Analog 1 Current Transformer 1</cim:IdentifiedObject.description>
<cim:IdentifiedObject.name>11 VESTFO 2 ANALOG1CURRTRA1</cim:IdentifiedObject.name>
<cim:Measurement.measurementType>Phase 1 current</cim:Measurement.measurementType>
<cim:Measurement.phases rdf:recource="http://iec.ch/TC57/2013/CIM-schema-cim16#PhaseCode.A">
<cim:Measurement.unitMultiplier rdf:recource="http://iec.ch/TC57/2013/CIM-schema-cim16#UnitMultiplier.none">
<cim:Measurement.unitSymbol rdf:recource="http://iec.ch/TC57/2013/CIM-schema-cim16#UnitSymbol.A">
<cim:Analog.maxValue>450</cim:Analog.maxValue>
<cim:Analog.minValue>0</cim:Analog.minValue>
<cim:Analog.normalValue>270</cim:Analog.normalValue>
<cim:Analog.positiveFlowIn>false</cim:Analog.positiveFlowIn>
<!--<cim:Measurement.Asset rdf:resource="#_"/>--><!--Can also be used related to an Asset like a tool-->
<cim:Measurement.PowerSystemResources rdf:resource="#_26d2f8aa-b651-46c5-a54d-05948f35f3d2"/>
<cim:Measurement.ACDCTerminal rdf:resource="#_83bf6035-97b6-4433-b5f9-bb455444a983"/> <!--A terminal from MV File-->
</cim:Analog>
Connect measurement and CT and PT to the terminal below the Switch rather than the termnial above the Switch
PMU (Function?) --> Phasor (voltageAngle or currentAngle) --> Analog (Measurement). Awaiting to a later stage. Own issue: #79
CIM100 is missing CurrentTransformerPhase:
Add Measurement for Scada and Metering for settlement (Kamstrup?)
1 CurrentTransformer (Several cores) --> 2 Measurement