PowerSystem Measurement for Engene Feeder/BusbarSection (Scada) #49

Closed ThomasRanvikEriksen closed 1 year ago

ThomasRanvikEriksen commented 3 years ago

Add Measurement for Scada and Metering for settlement (Kamstrup?)

1 CurrentTransformer (Several cores) --> 2 Measurement

Joahimmehl commented 3 years ago

I added a CurrentTransformer which is pointing to the Terminal between a Breaker and the CN for the BusbarSection. Q: Should CT be placed here or on the secondary side of the breaker?

The measurement (Analog) has a refrence to both the Terminal, and the CurrentTransformer as shown i the drawing.

Q: should we also include Voltage as an own measurement?

<cim:Analog rdf:ID="_b64c1205-d433-425f-9861-17e67fd8dd92">
  <cim:IdentifiedObject.description>400 Volt Vestfoldstien 2 Analog 1 Current Transformer</cim:IdentifiedObject.description>
  <cim:IdentifiedObject.name>04 VESTFO 2 ANALOG1CURRTRA</cim:IdentifiedObject.name>
  <cim:Measurement.measurementType>Underground LV Cable Serving Current</cim:Measurement.measurementType>
  <cim:Measurement.phases></cim:Measurement.phases>
  <cim:Measurement.unitMultiplier>none</cim:Measurement.unitMultiplier>
  <cim:Measurement.unitSymbol>A</cim:Measurement.unitSymbol>
  <cim:Analog.maxValue>430</cim:Analog.maxValue>
  <cim:Analog.minValue>110</cim:Analog.minValue>
  <cim:Analog.normalValue>320</cim:Analog.normalValue>
  <cim:Analog.positiveFlowIn>false</cim:Analog.positiveFlowIn>
  <!--<cim:Measurement.Asset rdf:resource="#_"/>--><!--Can also be used related to an Asset like a tool-->
  <cim:Measurement.PowerSystemResources rdf:resource="#_26d2f8aa-b651-46c5-a54d-05948f35f3d2"/>
  <cim:Measurement.ACDCTerminal rdf:resource="#_"/>
</cim:Analog>

<cim:AnalogValue rdf:ID="_c284c4f3-db8d-42b0-b8f0-a9614ffd2fb6">
  <cim:IdentifiedObject.description>400 Volt Vestfoldstien 2 AnalogValue 1 Current</cim:IdentifiedObject.description>
  <cim:IdentifiedObject.name>04 VESTFO 2 ANALOGVALUE1CURR</cim:IdentifiedObject.name>
  <cim:MeasurementValue.sensorAccuracy>97.2</cim:MeasurementValue.sensorAccuracy>
  <cim:MeasurementValue.timeStamp>2021-08-11T11:45:39.393725Z</cim:MeasurementValue.timeStamp>
  <cim:AnalogValue.value>300</cim:AnalogValue.value>
  <cim:MeasurementValue.MeasurementValueSource rdf:resource="#_bb396abd-8537-409b-a983-ac1eb907ac30"/>
  <cim:MeasurementValue.RemoteSource rdf:resource="#_"/>
  <cim:AnalogValue.Analog rdf:resource="#_b64c1205-d433-425f-9861-17e67fd8dd92"/>
</cim:AnalogValue

<cim:CurrentTransformer rdf:ID="_26d2f8aa-b651-46c5-a54d-05948f35f3d2">
  <cim:IdentifiedObject.description>400 Volt Vestfoldstien 2 Current Transformer</cim:IdentifiedObject.description>
  <cim:IdentifiedObject.name>04 VESTFO 2 CURRTRA</cim:IdentifiedObject.name>
  <cim:IdentifiedObject.aliasName>04VFS2CURTRA</cim:IdentifiedObject.aliasName>
  <cim:Equipment.aggregate>false</cim:Equipment.aggregate>
  <cim:Equipment.inService>true</cim:Equipment.inService> <!--Will be placed in the SSH file-->
  <cim:Equipment.networkAnalysisEnabled>true</cim:Equipment.networkAnalysisEnabled>
  <cim:Equipment.normallyInService>true</cim:Equipment.normallyInService>
  <cim:CurrentTransformer.accuracyClass></cim:CurrentTransformer.accuracyClass>
  <cim:CurrentTransformer.accuracyLimit></cim:CurrentTransformer.accuracyLimit>
  <cim:CurrentTransformer.coreBurden></cim:CurrentTransformer.coreBurden>
  <cim:CurrentTransformer.ctClass></cim:CurrentTransformer.ctClass>
  <cim:CurrentTransformer.usage>metering</cim:CurrentTransformer.usage>
  <cim:AuxiliaryEquipment.Terminal rdf:resource="#_3d75146a-8de3-44f3-ad93-aec6c820eb9b"/>
</cim:CurrentTransformer>

<cim:MeasurementValueSource rdf:ID="_bb396abd-8537-409b-a983-ac1eb907ac30">
  <cim:IdentifiedObject.description>Telemetered values received from a local SCADA system</cim:IdentifiedObject.description>
  <cim:IdentifiedObject.name>SCADA</cim:IdentifiedObject.name>
</cim:MeasurementValueSource>

image

ThomasRanvikEriksen commented 3 years ago

We are modelling 1 CT pr core with its accuracyclass and functionallity

Questions:

  1. Measuring amps pr phase? Yes a. 1 CT pr phase and then 1 Asset pr phase
  2. What about Voltage? Use PotentialTransformer

Add:

What about measuring Voltage?

Joahimmehl commented 2 years ago
11 kilo Volt Vestfoldstien 2 Analog 2 Current Transformer 2 11 VESTFO 2 ANALOG2CURRTRA2 Phase 2 current 450 0 270 false 11 kilo Volt Vestfoldstien 2 Analog 3 Current Transformer 3 11 VESTFO 2 ANALOG3CURRTRA3 Phase 3 current 450 0 270 false 11 kilo Volt Vestfoldstien 2 Analog 4 Potential Transformer 1 11 VESTFO 2 ANALOG4POTTRA1 AB Voltage rdf:recource="http://iec.ch/TC57/2013/CIM-schema-cim16#UnitMultiplier.k"> 12 0 10.4 false 11 kilo Volt Vestfoldstien 2 Analog 5 Potential Transformer 2 11 VESTFO 2 ANALOG5POTTRA2 AC Voltage 12 0 10.4 false 11 kilo Volt Vestfoldstien 2 Analog 6 Potential Transformer 3 11 VESTFO 2 ANALOG6POTTRA3 BC Voltage 12 0 10.4 false 11 kilo Volt Vestfoldstien 2 AnalogValue 1 Current 11 VESTFO 2 ANALOGVALUE1CURR 97.2 2021-08-11T11:45:39.393725Z 265.8 11 kilo Volt Vestfoldstien 2 AnalogValue 2 Current 2 11 VESTFO 2 ANALOGVALUE2CURR2 97.2 2021-08-11T11:45:39.393725Z 270.3 11 kilo Volt Vestfoldstien 2 AnalogValue 3 Current 3 11 VESTFO 2 ANALOGVALUE3CURR3 97.2 2021-08-11T11:45:39.393725Z 268.9 11 kilo Volt Vestfoldstien 2 AnalogValue 4 Voltage AB 11 VESTFO 2 ANALOGVALUE4VOLTAB 97.2 2021-08-11T11:45:39.393725Z 11.2 11 kilo Volt Vestfoldstien 2 AnalogValue 5 Voltage AC 11 VESTFO 2 ANALOGVALUE5VOLTAC 97.2 2021-08-11T11:45:39.393725Z 10.6 11 kilo Volt Vestfoldstien 2 AnalogValue 6 Voltage BC 11 VESTFO 2 ANALOGVALUE6VOLTBC 97.2 2021-08-11T11:45:39.393725Z 10.3 11 kilo Volt Vestfoldstien 2 Current Transformer 1 11 VESTFO 2 CURRTRA1 11VFS2CURTRA1 false true true true metering 11 kilo Volt Vestfoldstien 2 Current Transformer 2 11 VESTFO 2 CURRTRA2 11VFS2CURTRA2 false true true true metering 11 kilo Volt Vestfoldstien 2 Current Transformer 11 VESTFO 2 CURRTRA 11VFS2CURTRA false true true true metering Telemetered values received from a local SCADA system SCADA 11 kilo Volt Vestfoldstien 2 Potential Transformer 1 11 VESTFO 2 POTTRA1 11VFS2POTTRA1 false true true true 11 kilo Volt Vestfoldstien 2 Potential Transformer 2 11 VESTFO 2 POTTRA2 11VFS2POTTRA2 false true true true 11 kilo Volt Vestfoldstien 2 Potential Transformer 3 11 VESTFO 2 POTTRA3 11VFS2POTTRA3 false true true true ``` ![image](https://user-images.githubusercontent.com/91242130/137153060-bfc7d814-ebfd-42a7-ab74-4452e17ee099.png)
ThomasRanvikEriksen commented 2 years ago

Connect measurement and CT and PT to the terminal below the Switch rather than the termnial above the Switch

PMU (Function?) --> Phasor (voltageAngle or currentAngle) --> Analog (Measurement). Awaiting to a later stage. Own issue: #79

Sveino commented 1 year ago

CIM100 is missing CurrentTransformerPhase: image