Closed MikeMillerGIS closed 5 years ago
I had a conversation with Tom Brown this morning. In the Red Trolley database, he is modeling each of the fault indicators as a unique feature (device), one per phase, that is placed directly on the line and then an assembly feature used to contain them all. The features will require the Subnetwork Tap category to be assigned.
Which assembly feature? In the AG/AT list, I don't see any assembly feature for a fault indicator bank
It is in the Medium Voltage Line Monitor & Relay Asset Group
I still don't see an assembly feature for fault indicator banks, can you send the latest AG/AT list?
Anyway, here is a draft:
it's in the latest asset package. I will export to excel for you.
Completed
Current thoughts: The fault indicator will be a single device feature representing all the present devices and phases. (see picture below). This device would need to have the Subnetwork Tap property set and phases current should be set to null so that the phases propagated would populate the present phases. The only exception would be if a customer wants to account for each individual device. Need to examine Sempra database for examples