Strange values for P1/P2/p3 #3

Closed elxsi closed 10 months ago

elxsi commented 10 months ago

Hi,

current setup:

I'm experiencing some strange values for P1/P2/P3. If I understand this correctly:

So I've constantly queried the SEC1000s for the corresponding values (one query per minute), and I found something strange. During the night, when all inverters are off ("waiting mode"), I always have negative values for P1 and P2 (power is consumed from mains) but positive values for P3 (power is delivered to mains):

{ "v1": 224.60000000000002, "v2": 224.60000000000002, "v3": 224.70000000000002, "i1": 2.82, "i2": 3.5300000000000002, "i3": 3.83, "p1": -0.308, "p2": -0.34400000000000003, "p3": 0.497, "meters_power": -0.155, "inverters_power": 0.001 }

Or with the test script:

` Total number of bytes received: 56

Bytes: b'\x04REVO\x001\x01\x01\x0b\x00\x00\x08\xbe\x00\x00\x08\xc9\x00\x00\x08\xd2\x00\x00\x00\xfb\x00\x00\x01B\x00\x00\x01i\xff\xff\xff(\xff\xff\xfe\xf2\x00\x00\x01\xc7\xff\xff\xff\xe1\x00\x00\x00\x03\x0f\xe2'

Fields: 045245564F00 Header: \x04REV0\x00 31 Data lenght: 49 01010B Unknown (request code?) 000008BE Voltage 1 (0.1V units): 2238 000008C9 Voltage 2 (0.1V units): 2249 000008D2 Voltage 3 (0.1V units): 2258 000000FB Current 1 (0.01A units): 251 00000142 Current 2 (0.01A units): 322 00000169 Current 3 (0.01A units): 361 FFFFFF28 Power 1 (1W units): -216 FFFFFEF2 Power 2 (1W units): -270 000001C7 Power 3 (1W units): 455 FFFFFFE1 Meter power (1W units): -31 00000003 Inverters power (1W units): 3 0FE2 Data checksum, calculated = FE2 `

The absolute values of P1/P2/P3 seem to be correct though. I've also checked the direction of the three CTs and all of them or correctly placed. Any ideas what is going on here?

Thank you :)

tombolano commented 10 months ago

It is strange, from the data that you show it looks like it might be some hardware problem, but unfortunately I don't know what could be wrong there. I actually have no experience with these kinds of electrical installations, the code in this repository was made for an already existing solar power system, and I only took care of making this code for retrieving the data, I don't know much more.

I would suggest asking on the goodwe community forum: https://community.goodwe.com/Forum There is also other forums devoted to solar power systems where could try asking such as https://diysolarforum.com/, https://powerforum.co.za, or https://forum.buildhub.org.uk/forum/121-photovoltaics-pv/