[NTT DATA] On-Premise Web system #30

Open YaSuenag opened 1 year ago

YaSuenag commented 1 year ago

On-Premise Web system

Overview

Architecture for the system under consideration

architecture

Technical details of the components in the architecture

Procedure

(What) Software boundary

Included

Excluded

(Scale) Functional unit

We define functional unit R as 1 [Web Interaction (WI)].

The result of TPC-W benchmark is Web Interactions Per Second (WIPS), which is the number of responses (throughput) from the web server per second. In this case study, we got 10564.65 [WIPS], which means 38032740 [Web Interaction per hour] (multiplied by 3600 [hour in seconds]).

We calculate ((E * I) + M) per 1 hour, then divide it by the number of web interactions per hour (="scale factor") to derive the SCI score for the functional unit.

[scale factor] = [WIPS] * [hour in seconds]
               = 10564.65 * 3600
               = 38032740 [WI per hour]

(How) Quantification method

L3 switch ((1) in figure of architecture)

Energy (E)

Estimates from data sheet of Cisco Catalyst 9300 Series and from 5 minute input rate/5 minute output rate on Cisco IOS.

From Table.22 of data sheet, our network switch consumes 92.5 [W] in full port 100% traffic. We use this value as base line.

5 minute input rate and 5 minute output rate from show interfaces command on Cisco IOS shows mean an approximation of traffic per second during a given 5-minute period. We collect these values several times, and calculate median of sum of them because they are connected with full duplex. Note that we should collect values from ports which we used only.

>show interfaces Gi1/0/13
GigabitEthernet1/0/13 is up, line protocol is up (connected)

 ~snip~

  Full-duplex, 1000Mb/s, media type is 10/100/1000BaseTX

 ~snip~

  5 minute input rate 0 bits/sec, 0 packets/sec
  5 minute output rate 2000 bits/sec, 2 packets/sec

 ~snip~

We can estimate energy consumption with following:

[Max power consumption per port] = [value from ATIS] / [kW] * [hour] / [number of ports]
                                 = 92.5 / 1000 * 1 / 24
                                 = 3.85e-3 [kWh/port]
[E per port] = [Max power consumption per port] * median([5 minute input rate] + [5 minute output rate]) / 2 (full duplex) / [link speed (Gbps)]
             = 3.85e-3 * median([5 minute input rate] + [5 minute output rate]) / 2 / 1000000000

E = sum([E per port]) * [PUE]
  = sum([E per port]) * 1.5
Carbon Intensity (I)
Embodied Carbon (M)

This was on-premise system, and it was occupied by this workload. So we can use PCF from manufacturers straightly.

However Cisco has not published PCF of Catalyst 9300 series (Nov, 2022 at least), so we use emission factor database from Ministry of the Environment in Japan (ver. 3.2, in Japanese).

According this database, network switch is categorized to “computer accessories”, and one switch's PCF is 0.251 [tCO2eq] in quantity-based emissions intensity (No.239, code 333103). Thus we can estimate embodied carbon in mesurement duration with following:

M = 0.251 [tCO2eq] / [4 years in hour]
  = 251000 [gCO2eq] / 35040 [hours]
  = 7.16 [gCO2eq/hour]

L2 switch ((2) in figure of architecture)

Energy (E)

As well as Catalyst 9300, estimates from data sheet of Cisco Catalyst 1000 Series and from 5 minute input rate/5 minute output rate on Cisco IOS.

From Table 2 of data sheet, our network switch consumes 22.8 [W] in 1Gbps 100% traffic. We will use this value as base line.

We can estimate energy consumption with following:

[Max power consumption per port] = [value from data sheet] / [kW] * [hour] / [number of ports]
                                 = 22.8 / 1000 * 1 / 24
                                 = 9.50e-4 [kWh/port]
[E per port] = [Max power consumption per port] * median([5 minute input rate] + [5 minute output rate]) / 2 (full duplex) / [link speed (Gbps)]
             = 9.50e-4 * median([5 minute input rate] + [5 minute output rate]) / 2 / 1000000000

E = sum([E per port]) * [PUE]
  = sum([E per port]) * 1.5
Carbon Intensity (I)

This network switches are located at same datacenter with L3 switch, so we use 457 [gCO2/kWh] as well as it.

Embodied Carbon (M)

As well as L3 switch, we use emission factor database from Ministry of the Environment in Japan. So M is 7.16 [gCO2eq/hour].

Physical severs ((3) - (5) in figure of architecture)

Energy (E)

These servers support IPMI (Intelligent Platform Management Interface), so we can use ipmitool.

$ ipmitool -I lanplus -H [host] -U [username] -P [passphrase] dcmi power reading

    Instantaneous power reading:                   176 Watts
    Minimum during sampling period:                  1 Watts
    Maximum during sampling period:               6560 Watts
    Average power reading over sample period:      113 Watts
    IPMI timestamp:                           Thu Dec  1 11:41:20 2022
    Sampling period:                          00000001 Seconds.
    Power reading state is:                   activated

The command is executed from remote host several times. We use average of Instantaneous power reading as power consumption.

We convert this value (Watt) to energy (kWh) with following formula:

E = [average of Instantaneous power reading] / [kW] * [hour] * [PUE]
  = [average of Instantaneous power reading] / 1000 * 1 * 1.5
Carbon Intensity (I)

These servers are located at same datacenter with network switches, so we use 457 [gCO2/kWh] as well as network switches.

Embodied Carbon (M)

In this system, we use HPE DL360 Gen10. According to data sheet from HPE, PCF is 6270 [kgCO2eq]. Thus we can estimate embodied carbon in mesurement duration with following:

M = 6270 [kgCO2eq] / [4 years in hour]
  = 6270000 [gCO2eq] / 35040 [hours]
  = 178.93 [gCO2eq/hour]

(Quantify) SCI Value Calculation

L3 switch ((1) in figure of architecture)

[Max power consumption per port] = [value from ATIS] / [kW] * [hour] / [number of ports]
                                 = 92.5 / 1000 * 1 / 24
                                 = 3.85e-3 [kWh/port]
[E per port] = [Max power consumption per port] * median([5 minute input rate] + [5 minute output rate]) / 2 (full duplex) / [link speed (Gbps)]
             = 3.85e-3 * median([5 minute input rate] + [5 minute output rate]) / 2 / 1000000000

E = sum([E per port]) * [PUE]
  = 3.31e-3 [kWh] * 1.5
  = 4.96e-3 [kWh]

SCI = ((E * I) + M) / [scale factor (WI)] per R
    = ((4.96e-3 [kWh] * 457 [gCO2/kWh]) + 7.16 [gCO2eq/hour]) / 38032740 [WI] per R
    = 2.47e-7 [gCO2eq] per R

L2 switch ((2) in figure of architecture)

[Max power consumption per port] = [value from data sheet] / [kW] * [hour] / [number of ports]
                                 = 22.8 / 1000 * 1 / 24
                                 = 9.50e-4 [kWh/port]
[E per port] = [Max power consumption per port] * median([5 minute input rate] + [5 minute output rate]) / 2 (full duplex) / [link speed (Gbps)]
             = 9.50e-4 * median([5 minute input rate] + [5 minute output rate]) / 2 / 1000000000

E = sum([E per port]) * [PUE]
  = sum([E per port]) * 1.5
L2 #1
E = sum([E per port]) * [PUE]
  = 5.41e-4 [kWh] * 1.5
  = 8.11e-4 [kWh]

SCI = ((E * I) + M) / [scale factor (WI)] per R
    = ((8.11e-4 [kWh] * 457 [gCO2/kWh]) + 7.16 [gCO2eq/hour]) / 38032740 per R
    = 1.98e-7 [gCO2eq] per R
L2 #2

No traffic because it was connected from backup interfaces, however we need to include it as a software boundary.

E = 0.00 [kWh]

SCI = ((E * I) + M) / [scale factor (WI)] per R
    = ((0.00 [kWh] * 457 [gCO2/kWh]) + 7.16 [gCO2eq/hour]) / 38032740 per R
    = 1.88e-7 [gCO2eq] per R
L2 #3
E = sum([E per port]) * [PUE]
  = 6.37e-4 [kWh] * 1.5
  = 9.55e-4 [kWh]

SCI = ((E * I) + M) / [scale factor (WI)] per R
    = ((9.55e-4 [kWh] * 457 [gCO2/kWh]) + 7.16 [gCO2eq/hour]) / 38032740 per R
    = 1.99e-7 [gCO2eq] per R
L2 #4
E = sum([E per port]) * [PUE]
  = 7.60e-9 [kWh] * 1.5
  = 1.14e-8 [kWh]

SCI = ((E * I) + M) / [scale factor (WI)] per R
    = ((1.14e-8 [kWh] * 457 [gCO2/kWh]) + 7.16 [gCO2eq/hour]) / 38032740 per R
    = 1.88e-7 [gCO2eq] per R

Physical severs ((3) - (5) in figure of architecture)

E = [average of Instantaneous power reading] / [kW] * [hour] * [PUE]
  = [average of Instantaneous power reading] / 1000 * 1 * 1.5
LB/Web server #1
SCI = ((E * I) + M) / [scale factor (WI)] per R
    = ((0.139 [kWh] * 457 [gCO2/kWh]) + 178.93 [gCO2eq/hour]) / 38032740 per R
    = 63.74e-7 [gCO2eq] per R
LB/Web server #2
SCI = ((E * I) + M) / [scale factor (WI)] per R
    = ((0.116 [kWh] * 457 [gCO2/kWh]) + 178.93 [gCO2eq/hour]) / 38032740 per R
    = 60.98e-7 [gCO2eq] per R
AP server #1
SCI = ((E * I) + M) / [scale factor (WI)] per R
    = ((0.149 [kWh] * 457 [gCO2/kWh]) + 178.93 [gCO2eq/hour]) / 38032740 per R
    = 64.95e-7 [gCO2eq] per R
AP server #2
SCI = ((E * I) + M) / [scale factor (WI)] per R
    = ((0.147 [kWh] * 457 [gCO2/kWh]) + 178.93 [gCO2eq/hour]) / 38032740 per R
    = 64.70e-7 [gCO2eq] per R
DB server #1
SCI = ((E * I) + M) / [scale factor (WI)] per R
    = ((0.258 [kWh] * 457 [gCO2/kWh]) + 178.93 [gCO2eq/hour]) / 38032740 per R
    = 78.04e-7 [gCO2eq] per R
DB server #2
SCI = ((E * I) + M) / [scale factor (WI)] per R
    = ((0.193 [kWh] * 457 [gCO2/kWh]) + 178.93 [gCO2eq/hour]) / 38032740 per R
    = 70.23e-7 [gCO2eq] per R

SCI Total

The total SCI for the whole system.

SCI = [SCI of L3 switch] + sum([SCI of L2 switches]) + sum([SCI of physical servers])
    = 2.47e-7 + 7.73e-7 + 402.64e-7
    = 4.12e-5 [gCO2eq per R (1 WI)]