Closed GoogleCodeExporter closed 8 years ago
What's happening with this issue? Isn't there a solution? Help please!
Original comment by jorgejua...@gmail.com
on 25 Jan 2010 at 5:07
there is a bug in Modrsim. I contacted the author on 8/24/06 but it looks like
he
still hasn't fixed it.
Conrad,
Thanks for the key. I think i may have found a "bug". The response for
writing a single holding register should echo the request. The
mod_RSsim response does not include the last two
bytes (the data).
For example -
TCP/IP request to set register 200 to value 350
000000000006 FF 06 00 C8 01 5E
the actual response
000000000004 FF 06 00 C8
should be
000000000004 FF 06 00 C8 01 5E
Original comment by sja...@gmail.com
on 26 Jan 2010 at 5:31
Original comment by sja...@gmail.com
on 26 Jan 2010 at 5:31
OK. Thanks for reporting.
Great job!
Original comment by jorgejua...@gmail.com
on 18 Feb 2010 at 3:09