Baxi eco 4s + WeMos D1 sheld. [OT][WARN] Invalid response after setBoilerStatus: TIMEOUT #57

Closed MrDogYar closed 7 months ago

MrDogYar commented 7 months ago

Добрый день! Связка Baxi eco 4s + WeMos D1 sheld. Нет связи с котлом. [OT][WARN] Invalid response after setBoilerStatus: TIMEOUT Меняли местами OT PIN без результатно

Часть Log Основной в аттаче Log_BaxiEco4s+WenosD1 Shield .txt

00:00:00][NETWORK][TRACE] Set hostname 'zelenay19': success [00:00:05][SENSORS][OUTDOOR][INFO] Starting on gpio 12... [00:00:05][SENSORS][OUTDOOR][TRACE] Devices on bus: 1, DS18* devices: 1 [00:00:05][SENSORS][OUTDOOR][INFO] Started [00:00:06][PORTAL][WEBSERVER][TRACE] Started: AP up or STA connected [00:00:06][MQTT][INFO] Enabled [00:00:06][MQTT][INFO] Started [00:00:06][OT][INFO] Started. GPIO IN: 4, GPIO OUT: 5 [00:00:07][MAIN][VERB] Free heap size: 27440 of 81920 bytes (min: 27440, diff: 4294939856), max free block: 27144 (min: 27144, diff: 4294940152, frag: 1%) [00:00:07][NETWORK][INFO] Connected, downtime: 7 s., IP: 192.168.0.107, RSSI: -73 [00:00:08][OT][TRACE] ID: 0 Request: 2200 Response: 0 Attempt: 1 Status: TIMEOUT [00:00:09][OT][TRACE] ID: 0 Request: 2200 Response: 0 Attempt: 2 Status: TIMEOUT [00:00:10][REGULATOR][INFO] New target: 25.00 [00:00:10][REGULATOR][EQUITHERM][INFO] New result: 59 (59.38) [00:00:10][MAIN][VERB] Free heap size: 27216 of 81920 bytes (min: 27216, diff: 224), max free block: 27144 (min: 27144, diff: 0, frag: 0%) [00:00:10][SENSORS][OUTDOOR][TRACE] Raw temp: 27.437500 [00:00:10][SENSORS][OUTDOOR][INFO] New temp: 27.430000 [00:00:10][OT][TRACE] ID: 0 Request: 2200 Response: 0 Attempt: 3 Status: TIMEOUT [00:00:12][OT][TRACE] ID: 0 Request: 2200 Response: 0 Attempt: 4 Status: TIMEOUT [00:00:13][OT][TRACE] ID: 0 Request: 2200 Response: 0 Attempt: 5 Status: TIMEOUT [00:00:13][OT][WARN] Invalid response after setBoilerStatus: TIMEOUT [00:00:15][SENSORS][OUTDOOR][TRACE] Raw temp: 27.687500 [00:00:15][OT][TRACE] ID: 0 Request: 2200 Response: 0 Attempt: 1 Status: TIMEOUT [00:00:15][MQTT][INFO] Connecting to 91.203.125.214:1883... [00:00:15][MAIN][VERB] Free heap size: 26944 of 81920 bytes (min: 26944, diff: 272), max free block: 26752 (min: 26752, diff: 392, frag: 0%) [00:00:16][MQTT][INFO] Connected (downtime: 16 s.) [00:00:16][OT][TRACE] ID: 0 Request: 2200 Response: 0 Attempt: 2 Status: TIMEOUT [00:00:17][OT][TRACE] ID: 0 Request: 2200 Response: 0 Attempt: 3 Status: TIMEOUT [00:00:18][OT][TRACE] ID: 0 Request: 2200 Response: 0 Attempt: 4 Status: TIMEOUT [00:00:19][OT][TRACE] ID: 0 Request: 2200 Response: 0 Attempt: 5 Status: TIMEOUT [00:00:19][OT][WARN] Invalid response after setBoilerStatus: TIMEOUT [00:00:20][REGULATOR][EQUITHERM][INFO] New result: 40 (40.00) [00:00:20][SENSORS][OUTDOOR][TRACE] Raw temp: 27.437500 [00:00:21][OT][TRACE] ID: 0 Request: 2200 Response: 0 Attempt: 1 Status: TIMEOUT [00:00:22][OT][TRACE] ID: 0 Request: 2200 Response: 0 Attempt: 2 Status: TIMEOUT [00:00:24][OT][TRACE] ID: 0 Request: 2200 Response: 0 Attempt: 3 Status: TIMEOUT [00:00:25][SENSORS][OUTDOOR][TRACE] Raw temp: 27.500000 [00:00:25][OT][TRACE] ID: 0 Request: 2200 Response: 0 Attempt: 4 Status: TIMEOUT [00:00:26][OT][TRACE] ID: 0 Request: 2200 Response: 0 Attempt: 5 Status: TIMEOUT [00:00:26][OT][WARN] Invalid response after setBoilerStatus: TIMEOUT [00:00:28][OT][TRACE] ID: 0 Request: 2200 Response: 0 Attempt: 1 Status: TIMEOUT [00:00:29][OT][TRACE] ID: 0 Request: 2200 Response: 0 Attempt: 2 Status: TIMEOUT [00:00:30][SENSORS][OUTDOOR][TRACE] Raw temp: 27.562500 [00:00:30][OT][TRACE] ID: 0 Request: 2200 Response: 0 Attempt: 3 Status: TIMEOUT [00:00:31][MQTT][TRACE] Successfully publish 6 of 6 bytes to topic: zelenay19/status [00:00:31][MAIN][VERB] Free heap size: 26784 of 81920 bytes (min: 26784, diff: 160), max free block: 25368 (min: 25368, diff: 1384, frag: 5%) [00:00:31][MQTT][TRACE] Successfully publish 471 of 471 bytes to topic: zelenay19/state [00:00:31][MAIN][VERB] Free heap size: 26296 of 81920 bytes (min: 26296, diff: 488), max free block: 24864 (min: 24864, diff: 504, frag: 5%) [00:00:31][MQTT][TRACE] Successfully publish 553 of 553 bytes to topic: zelenay19/settings [00:00:31][OT][TRACE] ID: 0 Request: 2200 Response: 0 Attempt: 4 Status: TIMEOUT [00:00:32][MAIN][VERB] Free heap size: 26088 of 81920 bytes (min: 26088, diff: 208), max free block: 24704 (min: 24704, diff: 160, frag: 5%) [00:00:32][MQTT][TRACE] Successfully publish 633 of 633 bytes to topic: homeassistant/switch/zelenay19/emergency/config [00:00:32][MAIN][VERB] Free heap size: 24640 of 81920 bytes (min: 24640, diff: 1448), max free block: 24104 (min: 24104, diff: 600, frag: 2%) [00:00:32][MQTT][TRACE] Successfully publish 692 of 692 bytes to topic: homeassistant/number/zelenay19/emergency_target/config [00:00:32][MAIN][VERB] Free heap size: 24448 of 81920 bytes (min: 24448, diff: 192), max free block: 23848 (min: 23848, diff: 256, frag: 2%) [00:00:32][MQTT][TRACE] Successfully publish 820 of 820 bytes to topic: homeassistant/switch/zelenay19/emergency_use_equitherm/config [00:00:32][MAIN][VERB] Free heap size: 24376 of 81920 bytes (min: 24376, diff: 72), max free block: 24056 (min: 23848, diff: 0, frag: 1%) [00:00:33][MQTT][TRACE] Successfully publish 783 of 783 bytes to topic: homeassistant/switch/zelenay19/emergency_use_pid/config [00:00:33][OT][TRACE] ID: 0 Request: 2200 Response: 0 Attempt: 5 Status: TIMEOUT [00:00:33][OT][WARN] Invalid response after setBoilerStatus: TIMEOUT [00:00:33][MQTT][TRACE] Successfully publish 649 of 649 bytes to topic: homeassistant/switch/zelenay19/heating/config [00:00:33][MQTT][TRACE] Successfully publish 676 of 676 bytes to topic: homeassistant/switch/zelenay19/heating_turbo/config [00:00:34][MQTT][TRACE] Successfully publish 688 of 688 bytes to topic: homeassistant/number/zelenay19/heating_hysteresis/config [00:00:34][MQTT][TRACE] Successfully publish 615 of 615 bytes to topic: homeassistant/sensor/zelenay19/heating_setpoint/config [00:00:34][MQTT][TRACE] Successfully publish 774 of 774 bytes to topic: homeassistant/sensor/zelenay19/boiler_heating_min_temp/config [00:00:35][MQTT][TRACE] Successfully publish 772 of 772 bytes to topic: homeassistant/sensor/zelenay19/boiler_heating_max_temp/config [00:00:35][OT][TRACE] ID: 0 Request: 2200 Response: 0 Attempt: 1 Status: TIMEOUT [00:00:35][SENSORS][OUTDOOR][TRACE] Raw temp: 27.437500 [00:00:35][MQTT][TRACE] Successfully publish 691 of 691 bytes to topic: homeassistant/number/zelenay19/heating_min_temp/config [00:00:35][MQTT][TRACE] Successfully publish 690 of 690 bytes to topic: homeassistant/number/zelenay19/heating_max_temp/config [00:00:36][MQTT][TRACE] Successfully publish 689 of 689 bytes to topic: homeassistant/number/zelenay19/heating_max_modulation/config [00:00:36][OT][TRACE] ID: 0 Request: 2200 Response: 0 Attempt: 2 Status: TIMEOUT [00:00:36][MQTT][TRACE] Successfully publish 589 of 589 bytes to topic: homeassistant/switch/zelenay19/pid/config [00:00:37][MQTT][TRACE] Successfully publish 579 of 579 bytes to topic: homeassistant/number/zelenay19/pid_p_factor/config [00:00:37][MQTT][TRACE] Successfully publish 578 of 578 bytes to topic: homeassistant/number/zelenay19/pid_i_factor/config [00:00:37][OT][TRACE] ID: 0 Request: 2200 Response: 0 Attempt: 3 Status: TIMEOUT [00:00:37][MQTT][TRACE] Successfully publish 577 of 577 bytes to topic: homeassistant/number/zelenay19/pid_d_factor/config [00:00:38][MQTT][TRACE] Successfully publish 595 of 595 bytes to topic: homeassistant/number/zelenay19/pid_dt/config [00:00:38][MQTT][TRACE] Successfully publish 671 of 671 bytes to topic: homeassistant/number/zelenay19/pid_min_temp/config [00:00:38][MQTT][TRACE] Successfully publish 670 of 670 bytes to topic: homeassistant/number/zelenay19/pid_max_temp/config [00:00:38][OT][TRACE] ID: 0 Request: 2200 Response: 0 Attempt: 4 Status: TIMEOUT [00:00:39][MQTT][TRACE] Successfully publish 629 of 629 bytes to topic: homeassistant/switch/zelenay19/equitherm/config [00:00:39][MQTT][TRACE] Successfully publish 611 of 611 bytes to topic: homeassistant/number/zelenay19/equitherm_n_factor/config [00:00:39][MAIN][VERB] Free heap size: 24280 of 81920 bytes (min: 24280, diff: 96), max free block: 24104 (min: 23848, diff: 0, frag: 0%) [00:00:39][MQTT][TRACE] Successfully publish 606 of 606 bytes to topic: homeassistant/number/zelenay19/equitherm_k_factor/config [00:00:39][PORTAL][WEBSERVER][TRACE] Request /api/settings 216 bytes: {"opentherm":{"inPin":4,"outPin":5,"memberIdCode":0,"dhwPresent":true,"modulationSyncWithHeating":true,"summerWinterMode":false,"heatingCh2Enabled":false,"heatingCh1ToCh2":false,"dhwToCh2":false,"dhwBlocking":false}} [00:00:39][MAIN][VERB] Free heap size: 23296 of 81920 bytes (min: 23296, diff: 984), max free block: 22728 (min: 22728, diff: 1120, frag: 2%) [00:00:39][OT][TRACE] ID: 0 Request: 2200 Response: 0 Attempt: 5 Status: TIMEOUT [00:00:39][OT][WARN] Invalid response after setBoilerStatus: TIMEOUT

Laxilef commented 7 months ago

Какой адаптер используется?

MrDogYar commented 7 months ago

Собран самостоятельно по вашей схеме только без светодиодной индикации.  https://github.com/Laxilef/OTGateway/blob/master/assets/Schematic.pdf   Вчера вечером подключил к своему котлу Bocsh Gaz6000. Плата работает. :-(    

Вторник, 12 марта 2024, 10:28 +03:00 от Laxilef @.***>:     Какой адаптер используется? — Reply to this email directly, view it on GitHub , or unsubscribe . You are receiving this because you authored the thread. Message ID: <Laxilef/OTGateway/issues/57/1990943393 @ github . com>    

 

Laxilef commented 7 months ago

Значит аппаратную часть адаптера исключаем. На сайте зонта eco 4s заявлен как совместимый, значит opentherm там работает.

Подключали вместо перемычки? Настройки котла пробовали сбрасывать?

MrDogYar commented 7 months ago

Да. Перемычку удаляем и на ее место подключаем ОТ   Настройки не меняли и не сбрасывали.       Но что еще меня смутило. После удаления перемычки на контактах ОТ-котла 110 вольт. С подключенным  к ОТ контроллера падает до 1-2 вольт.   У меня на Bosch без подключения ОТ 30 вольт, с подключеным ОТ 6-8 вольт.

 

Вторник, 12 марта 2024, 12:12 +03:00 от Laxilef @.***>:     Значит аппаратную часть адаптера исключаем. На сайте зонта eco 4s заявлен как совместимый, значит opentherm там работает. Подключали вместо перемычки? Настройки котла пробовали сбрасывать? — Reply to this email directly, view it on GitHub , or unsubscribe . You are receiving this because you authored the thread. Message ID: <Laxilef/OTGateway/issues/57/1991113434 @ github . com>    

 

MrDogYar commented 7 months ago

А вот это интересно. Получаеться, что надо удалить перемычку, но подключаться не в нее как на всех котлах, а в разъем X6 

 

Вторник, 12 марта 2024, 12:22 +03:00 от Денис Титов < @.*** >:   Да. Перемычку удаляем и на ее место подключаем ОТ   Настройки не меняли и не сбрасывали.       Но что еще меня смутило. После удаления перемычки на контактах ОТ-котла 110 вольт. С подключенным  к ОТ контроллера падает до 1-2 вольт.   У меня на Bosch без подключения ОТ 30 вольт, с подключеным ОТ 6-8 вольт.

 

Вторник, 12 марта 2024, 12:12 +03:00 от Laxilef < @.*** >:     Значит аппаратную часть адаптера исключаем. На сайте зонта eco 4s заявлен как совместимый, значит opentherm там работает. Подключали вместо перемычки? Настройки котла пробовали сбрасывать? — Reply to this email directly, view it on GitHub , or unsubscribe . You are receiving this because you authored the thread. Message ID: <Laxilef/OTGateway/issues/57/1991113434 @ github . com>    

 

MrDogYar commented 7 months ago

 

Вторник, 12 марта 2024, 12:28 +03:00 от Денис Титов @.***>:   А вот это интересно. Получаеться, что надо удалить перемычку, но подключаться не в нее как на всех котлах, а в разъем X6 

 

Вторник, 12 марта 2024, 12:22 +03:00 от Денис Титов < @.*** >:   Да. Перемычку удаляем и на ее место подключаем ОТ   Настройки не меняли и не сбрасывали.       Но что еще меня смутило. После удаления перемычки на контактах ОТ-котла 110 вольт. С подключенным  к ОТ контроллера падает до 1-2 вольт.   У меня на Bosch без подключения ОТ 30 вольт, с подключеным ОТ 6-8 вольт.

 

Вторник, 12 марта 2024, 12:12 +03:00 от Laxilef < @.*** >:     Значит аппаратную часть адаптера исключаем. На сайте зонта eco 4s заявлен как совместимый, значит opentherm там работает. Подключали вместо перемычки? Настройки котла пробовали сбрасывать? — Reply to this email directly, view it on GitHub , or unsubscribe . You are receiving this because you authored the thread. Message ID: <Laxilef/OTGateway/issues/57/1991113434 @ github . com>    

 

Laxilef commented 7 months ago

Это один и тот же разъем. Проверьте корректность подключения питания котла. Судя по документации, один из контактов этой колодки соединен с нулем питания. И если там не ноль, а фаза, то ничего хорошего не будет. 110в там не должно быть, по спецификации OT до 45в, если не ошибаюсь. Screenshot_20240312_123730_Drive

Upd: похоже этот контакт колодки соединён с фазой, а не с нулем. Но лучше прозвонить мультиметром и все же проверить подключение. Screenshot_20240312_125742_Drive

MrDogYar commented 7 months ago

Пообщался т техподдержкой БАКСИ.  

 

MrDogYar commented 7 months ago

Добрый вечер! Все заработало! Можно добавлять в копилку BAXI ECO 4S + WemosD1 Shield. Для подключения надо удалить перемычку, а ОТ контакты подсоединить к разъему X6 на плате.   Единственное. Почему-то постоянно показывает, что в ГВС есть проток sensor.opentherm_dhw_flow_rate.   Но на функционал ни как не влияет.   Спасибо за техподдержку.!!!  

 

Вторник, 12 марта 2024, 13:02 +03:00 от Денис Титов @.***>:   Пообщался т техподдержкой БАКСИ.  

  • Говорят, что ОТ разъем это как раз X6.
  • Перемычку надо удалить.
  • На ОТ должно быть 24 в.   Вечером пойдем с другом опять эксперементировать. По итогам отпишусь.  

    Вторник, 12 марта 2024, 12:42 +03:00 от Laxilef < @.*** >:     Это один и тот же разъем. Проверьте корректность подключения питания котла. Судя по документации, один из контактов этой колодки соединен с нулем питания. И если там не ноль, а фаза, то ничего хорошего не будет. 110в там не должно быть, по спецификации OT до 45в, если не ошибаюсь. Screenshot_20240312_123730_Drive.jpg (view on web) — Reply to this email directly, view it on GitHub , or unsubscribe . You are receiving this because you authored the thread. Message ID: <Laxilef/OTGateway/issues/57/1991188101 @ github . com>

 

Laxilef commented 7 months ago

В чем проблема была?

MrDogYar commented 7 months ago

В чем проблема была?

Перепутана L и N на котле. Плюс подключались к колодке термостата где была перемычка, а надо подключаться к разъему X6 на плате. (Он внизу платы)

MrDogYar commented 6 months ago

Добрый день! А возможно реализвать в прошивке локальный MQTT на примере https://github.com/martin-ger/uMQTTBroker что б контроллер заворачивал свои сообщения сам на себя?