Hi,
Have you activated Modbus in your S10X? You have to go to Main Menu > Functions > Function Modbus. The protocol requires E3DC.
Best regards Julian
Hi Julian,
You are right, it wasn't activated. I mixed it up with the RSCP interface (already activated for something else), sorry.
Thanks, Nils
And this issue can be closed, of course.
Hi, I've followed the configuration, but "connection refused" appears, because the password is missing.
How do I configure the password set in the E3DC (S 10 X) within the modbus.yaml? Or do I have to remove the password on the E3DC (set to empty) - wouldn't be my preference?
Thanks, Nils