Update to EF values of NBC reference DHW Systems #78

Closed A-Wills closed 5 years ago

A-Wills commented 5 years ago

The EF values of the NBC DHW systems have been updated to reflect requirements in Table 9.36.4.2 All reference DHW are conventional tanks systems with volume V=189.3 L

Per the table for gas-fired systems: EF = 0.67-0.0005V = 0.575 for oil-fired: EF = 0.59-0.0005V = 0.495