Open yujiex opened 11 months ago
Zone VRF Air Terminal Total Heating Rate is relative to the zone. So Total Heating Rate = Heating Coil + Supp Heating Coil + Fan Heat - Outdoor Air Load.
Zone VRF Air Terminal Total Heating Rate is relative to the zone. So Total Heating Rate = Heating Coil + Supp Heating Coil + Fan Heat - Outdoor Air Load.
I'll add Fan Heat and outdoor air load to the system. The outdoor air mass flow rate is around 0.03kg/s
Issue overview
When one VRF serves one conditioned zone with one terminal unit, we would expect the "Zone VRF Air Terminal Total Heating Rate" to match the "Heating Coil Heating Rate"+ supplemental coil heating rate + Fan heating rate - outdoor air load. However, we observed some mismatches between these two quantities, as is shown in the following plot
Details
Some additional details for this issue (if relevant):
Defect file
idf: US+SF+CZ4A+hp+crawlspace+IECC_2006_VRF.idf.txt
epw: USA_NY_New.York-John.F.Kennedy.Intl.AP.744860_TMY3.epw.txt