Closed mjwitte closed 8 years ago
Also, in Chiller:Electric, Field: Design Heat Recovery Water Flow Rate, there is a typo "Enegineering Manual".
@mjwitte It should say "fan cycles with heating or cooling coil".
Engineering Reference for ASHRAE 55 says "If, using either method, To is less than 10°(C) or greater than 33.5°(C), the model is not applicable." where To is monthly mean outdoor air dry-bulb temperature (°C).
Engineering Reference for CEN 15251 is vague: "If Trm is not within the specified domain, the model is not applicable." where Trm = weighted running average of the previous 7 daily average outdoor air temperatures. The specified domain appears to be 15-30C based on the figure in that section, but this should be confirmed.
MJW 07 Dec 2015
In the source code ThermalComfort.cc these outputs are applicable when shown below, otherwise set to -1
For Zone Thermal Comfort ASHRAE 55 Adaptive Model . . . Acceptability Status
if ( runningAverageASH >= 10.0 && runningAverageASH <= 33.5 ) {
if ( numOccupants > 0 ) {
For Zone Thermal Comfort ASHRAE 55 Adaptive Model Temperature [C]
if ( runningAverageASH >= 10.0 && runningAverageASH <= 33.5 ) {
For Zone Thermal Comfort CEN 15251 Adaptive Model Category . . . Status
if ( runningAverageCEN >= 10.0 && runningAverageCEN <= 30.0 ) {
if ( numOccupants > 0 ) {
For Zone Thermal Comfort CEN 15251 Adaptive Model Temperature [C]
if ( runningAverageCEN >= 10.0 && runningAverageCEN <= 30.0 ) {
A2, \field Type of Load to Size On
\note Specifies the basis for sizing the system supply air flow rate
\note Sensible and VentilationRequirement are the only available options
\note Sensible uses the zone design air flow rates
\note VentilationRequirement uses the system ventilation requirement
\type choice
\key Sensible
\key Total
\key VentilationRequirement
\default Sensible
A4 , \field Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
\note Electric Input Ratio (EIR) as a function of Part Load Ratio (PLR)
\note EIR = 1/COP
\required-field
\type object-list
\object-list QuadraticCurves
\object-list UniVariateTables
\minimum 1
Output:IlluminanceMap,
N4 , \field Number of X Grid Points
\note Maximum number of total grid points must be <= 2500 (X*Y)
\type integer
\minimum> 0
\default 2
N7 ; \field Number of Y Grid Points
\note Maximum number of total grid points must be <= 2500 (X*Y)
\type integer
\minimum> 0
\default 2
@wfbuhl Sometime during v8.3.0, in Sizing:System, field Type of Load to Size On, the key choice "Total" was uncommented and added to the I/O ref as a valid choice, but no explanation was added (in IDD or I/O Ref). Looking at the code, the getinput takes it but I don't see Sensible or Total making any difference in the actual sizing code. Is this a real choice or not?
1.17.10.2 Field: Type of Load to Size On The user specified type of load on which to size the central system. The choices are Sensible, Total and VentilationRequirement. Sensible means that the central system supply air flow rate will be determined by combining the zone design air flow rates, which have been calculated to meet the zone sensible loads from the design days. VentilationRequirement means that the central system supply air flow rate will be determined by the system ventilation requirement. In addition Sensible tells the program to size the central cooling coil using entering air flow rate and air conditions at the sensible load peak; Total indicates that the program should size the central cooling coil at the air flow rate and conditions at the total load peak. The central heating coil is always sized at the conditions at the peak sensible heating load.
I think it is explained in the above IO Ref; though the word "Total" should be italicized in the IO Ref doc. The issue as I now vaguely remember it is that the central cooling coil was always being sized on the flow rate at the sensible peak; now it can be sized on the flow rate at the total peak. This was part of the coil vs space peak issue. In the code you'll see it used in function GetCoilDesFlowT. So it is a real choice. I would just comment that the notes in the IDD are now incorrect and looks like it was never altered to reflect "total" becoming an active key value.
@wfbuhl Duh - I guess I missed the last sentence because it's not italicized. I'll fix that. And now I see it gets transferred to .CoolingPeakLoadType which then gets used in GetCoilDesFlow. Thanks for pointing me in the right direction.
@wfbuhl And just to clarify - the system supply air flow rate will be the same with Sensible and Total? Just the coil sizing will change between these two?
Yes
On Mon, Dec 7, 2015 at 11:11 AM, Michael J. Witte notifications@github.com wrote:
@wfbuhl https://github.com/wfbuhl And just to clarify - the system supply air flow rate will be the same with Sensible and Total? Just the coil sizing will change between these two?
— Reply to this email directly or view it on GitHub https://github.com/NREL/EnergyPlus/issues/5241#issuecomment-162627884.
Closed via #5352