Storefront Glazing - U- Factor, SHGC, VT #49

Closed theoryshaw closed 9 years ago

theoryshaw commented 9 years ago

Hi @AnisGitHub, (ping @tfodden)

Using this markedup elevation here, I was wondering if you could help me determine the storefront glazing types (in terms of U- Factor, SHGC, VT) of the various conditions around the building?

As you can see, I have the polycarbonate figured out based on the NFRC test they provided, but need help pulling out the correct (U- Factor, SHGC, VT) values out of the following storefront documentation...

http://www.tubeliteinc.com/wp-content/uploads/2014/02/T14000_Thermal_Simulation_AAMA_507_2006.pdf

http://www.tubeliteinc.com/wp-content/uploads/2014/02/B6911_01-116-45-r0-T14000_Standard-061512-NFRC_100-200.pdf

The documentation is a little cryptic for my eyes and could use some help to make sure i'm deciphering it correctly.

Thanks Much, Ryan

theoryshaw commented 9 years ago

Thanks @AnisGitHub... this is what i sent to the mechanical sub: https://github.com/OpeningDesign/Sports_Complex/blob/b7ebb4428c155649574f6150bf61b459a06b2631/Transfer/20150625%20-%20glazing%20types/20150625%20-%20XSC%20-%20glazing.pdf