Hi everyone, first of all i want to say THANK YOU! Thank you for the great package and thanks for the detailed instructions. This is the first "Issue" i open on git hub so please have merci when i don't provide all necessary information from the beginning.

State of the Art:

Issue:

temporary solution:

Is there a better solution for resetting the ads nodes?

Thank you for any kind of feedback !

nodedebug

PLCHome commented 4 years ago

The node project runs on the Beckhoff IPC (locally)

Sorry that doesn't work

The connection works well and satisfying

This can not really be

This is due to the fact that Beckhoff works via the IP address and not via the NET-ID and Prort. Everything goes to the software router on the PLC. If you are working with static IP addresses, you can register a 2nd IP address with its own NET ID and enter the 2nd IP in the connection node, then that works.