Open SvenTej opened 11 months ago
After I used the data now and tried to implement some error handling for broken sensors in the PLC I detected some additional issues:
If I disconnect a sensor After about 5 seconds, the temp in the devicelist shows "OK" (not the temp any more), the value in com.victronenerg.temperature, dbus-obj-path \Status (Modbus ID 3305) shows still 0, whereas the temperature (dbus-obj-path Temperature, Modbus 3304) shows already 0. After about 90 seconds after that, the Status chenges to 1 and display shows "unconnected".
If I then reconnect it in some cases I saw status going to 0 some seconds before tempreature has the correct value.
Is this by design?
S.
What I now also found: After each restart, the Modbus Device IDs change. So the device ID of a sensor is not preserved after a restart
Hello,
I don't use the Modbus service yet. I have to check what can be done there. Maybe it's an ID conflict. I have to build a test setup first
best regards Rikkert-RS
First of all: Cool stuff, thanks for it.
I connected 3 18B20 sensors and up to now it works like a charm.
The only issue I have: I read the temps from my Siemens LOGO! 8.3 SPS to use it as inputs for a fan control in my control cabinet. This reading is done via MODBUS TCP.
It works for the 1 wire sensors but not for the CPU.
The CPU Temp states to be device 100 (system?) and if I use 100 as UID for the MODBUS the Venus OS shows an Error that it cannot find the function.
Is this a known issue?
Greets from Stuttgart, Germany