Closed schousda closed 1 month ago
here too, but it still works for me... insert the card, set the date and time to 23:59 and wait around 2 minutes (force the system to write a new dataset)
I tested this and there are some files now on my card. But none of them contains the message format. One is backup.par and the other is ctext.par. Is my heating not supported?
Part of the information from the backup.par:
++FileInfo++
2024-10-15_00:08:45 KD=Hargassner
2024-10-15_00:08:45 KT=Nano.2 25
2024-10-15_00:08:45 SW=V14.0k4
2024-10-15_00:08:45 HW=V1.1.5
2024-10-15_00:08:45 KN=1901142
++FileInfo_End++
My ctext.par:
++VersInfo++
V1.4v
++VersInfo_End++
++Parameterdaten++
Z61a;8;CLIENT 1; +-1234567890abcdefghijklmnopqrstuvwxyzABCDEFGHIJKLMNOPQRSTUVWXYZ ;M-Bus Clientname 1, Modul 1;
Z61b;8;CLIENT 2; +-1234567890abcdefghijklmnopqrstuvwxyzABCDEFGHIJKLMNOPQRSTUVWXYZ ;M-Bus Clientname 1, Modul 1;
Z61c;8;CLIENT 3; +-1234567890abcdefghijklmnopqrstuvwxyzABCDEFGHIJKLMNOPQRSTUVWXYZ ;M-Bus Clientname 1, Modul 1;
Z61d;8;CLIENT 4; +-1234567890abcdefghijklmnopqrstuvwxyzABCDEFGHIJKLMNOPQRSTUVWXYZ ;M-Bus Clientname 1, Modul 1;
Z61e;8;CLIENT 5; +-1234567890abcdefghijklmnopqrstuvwxyzABCDEFGHIJKLMNOPQRSTUVWXYZ ;M-Bus Clientname 1, Modul 1;
Z61f;8;CLIENT 6; +-1234567890abcdefghijklmnopqrstuvwxyzABCDEFGHIJKLMNOPQRSTUVWXYZ ;M-Bus Clientname 1, Modul 1;
Z61g;8;CLIENT 7; +-1234567890abcdefghijklmnopqrstuvwxyzABCDEFGHIJKLMNOPQRSTUVWXYZ ;M-Bus Clientname 1, Modul 1;
Z61h;8;CLIENT 8; +-1234567890abcdefghijklmnopqrstuvwxyzABCDEFGHIJKLMNOPQRSTUVWXYZ ;M-Bus Clientname 1, Modul 1;
Z61i;8;CLIENT 9; +-1234567890abcdefghijklmnopqrstuvwxyzABCDEFGHIJKLMNOPQRSTUVWXYZ ;M-Bus Clientname 1, Modul 1;
Z61j;8;CLIENT 10; +-1234567890abcdefghijklmnopqrstuvwxyzABCDEFGHIJKLMNOPQRSTUVWXYZ ;M-Bus Clientname 1, Modul 1;
Z61k;8;CLIENT 11; +-1234567890abcdefghijklmnopqrstuvwxyzABCDEFGHIJKLMNOPQRSTUVWXYZ ;M-Bus Clientname 1, Modul 1;
Z61l;8;CLIENT 12; +-1234567890abcdefghijklmnopqrstuvwxyzABCDEFGHIJKLMNOPQRSTUVWXYZ ;M-Bus Clientname 1, Modul 1;
Z61m;8;CLIENT 13; +-1234567890abcdefghijklmnopqrstuvwxyzABCDEFGHIJKLMNOPQRSTUVWXYZ ;M-Bus Clientname 1, Modul 1;
Z61n;8;CLIENT 14; +-1234567890abcdefghijklmnopqrstuvwxyzABCDEFGHIJKLMNOPQRSTUVWXYZ ;M-Bus Clientname 1, Modul 1;
Z61o;8;CLIENT 15; +-1234567890abcdefghijklmnopqrstuvwxyzABCDEFGHIJKLMNOPQRSTUVWXYZ ;M-Bus Clientname 1, Modul 1;
Z61p;8;CLIENT 16; +-1234567890abcdefghijklmnopqrstuvwxyzABCDEFGHIJKLMNOPQRSTUVWXYZ ;M-Bus Clientname 1, Modul 1;
Z61q;8;CLIENT 17; +-1234567890abcdefghijklmnopqrstuvwxyzABCDEFGHIJKLMNOPQRSTUVWXYZ ;M-Bus Clientname 1, Modul 1;
Z61r;8;CLIENT 18; +-1234567890abcdefghijklmnopqrstuvwxyzABCDEFGHIJKLMNOPQRSTUVWXYZ ;M-Bus Clientname 1, Modul 1;
Z61s;8;CLIENT 19; +-1234567890abcdefghijklmnopqrstuvwxyzABCDEFGHIJKLMNOPQRSTUVWXYZ ;M-Bus Clientname 1, Modul 1;
Z61t;8;CLIENT 20; +-1234567890abcdefghijklmnopqrstuvwxyzABCDEFGHIJKLMNOPQRSTUVWXYZ ;M-Bus Clientname 1, Modul 1;
Z61u;8;CLIENT 21; +-1234567890abcdefghijklmnopqrstuvwxyzABCDEFGHIJKLMNOPQRSTUVWXYZ ;M-Bus Clientname 1, Modul 1;
Z62a;8;CLIENT 1; +-1234567890abcdefghijklmnopqrstuvwxyzABCDEFGHIJKLMNOPQRSTUVWXYZ ;M-Bus Clientname 1, Modul 1;
Z62b;8;CLIENT 2; +-1234567890abcdefghijklmnopqrstuvwxyzABCDEFGHIJKLMNOPQRSTUVWXYZ ;M-Bus Clientname 1, Modul 1;
Z62c;8;CLIENT 3; +-1234567890abcdefghijklmnopqrstuvwxyzABCDEFGHIJKLMNOPQRSTUVWXYZ ;M-Bus Clientname 1, Modul 1;
Z62d;8;CLIENT 4; +-1234567890abcdefghijklmnopqrstuvwxyzABCDEFGHIJKLMNOPQRSTUVWXYZ ;M-Bus Clientname 1, Modul 1;
Z62e;8;CLIENT 5; +-1234567890abcdefghijklmnopqrstuvwxyzABCDEFGHIJKLMNOPQRSTUVWXYZ ;M-Bus Clientname 1, Modul 1;
Z62f;8;CLIENT 6; +-1234567890abcdefghijklmnopqrstuvwxyzABCDEFGHIJKLMNOPQRSTUVWXYZ ;M-Bus Clientname 1, Modul 1;
Z62g;8;CLIENT 7; +-1234567890abcdefghijklmnopqrstuvwxyzABCDEFGHIJKLMNOPQRSTUVWXYZ ;M-Bus Clientname 1, Modul 1;
Z62h;8;CLIENT 8; +-1234567890abcdefghijklmnopqrstuvwxyzABCDEFGHIJKLMNOPQRSTUVWXYZ ;M-Bus Clientname 1, Modul 1;
Z62i;8;CLIENT 9; +-1234567890abcdefghijklmnopqrstuvwxyzABCDEFGHIJKLMNOPQRSTUVWXYZ ;M-Bus Clientname 1, Modul 1;
Z62j;8;CLIENT 10; +-1234567890abcdefghijklmnopqrstuvwxyzABCDEFGHIJKLMNOPQRSTUVWXYZ ;M-Bus Clientname 1, Modul 1;
Z62k;8;CLIENT 11; +-1234567890abcdefghijklmnopqrstuvwxyzABCDEFGHIJKLMNOPQRSTUVWXYZ ;M-Bus Clientname 1, Modul 1;
Z62l;8;CLIENT 12; +-1234567890abcdefghijklmnopqrstuvwxyzABCDEFGHIJKLMNOPQRSTUVWXYZ ;M-Bus Clientname 1, Modul 1;
Z62m;8;CLIENT 13; +-1234567890abcdefghijklmnopqrstuvwxyzABCDEFGHIJKLMNOPQRSTUVWXYZ ;M-Bus Clientname 1, Modul 1;
Z62n;8;CLIENT 14; +-1234567890abcdefghijklmnopqrstuvwxyzABCDEFGHIJKLMNOPQRSTUVWXYZ ;M-Bus Clientname 1, Modul 1;
Z62o;8;CLIENT 15; +-1234567890abcdefghijklmnopqrstuvwxyzABCDEFGHIJKLMNOPQRSTUVWXYZ ;M-Bus Clientname 1, Modul 1;
Z62p;8;CLIENT 16; +-1234567890abcdefghijklmnopqrstuvwxyzABCDEFGHIJKLMNOPQRSTUVWXYZ ;M-Bus Clientname 1, Modul 1;
Z62q;8;CLIENT 17; +-1234567890abcdefghijklmnopqrstuvwxyzABCDEFGHIJKLMNOPQRSTUVWXYZ ;M-Bus Clientname 1, Modul 1;
Z62r;8;CLIENT 18; +-1234567890abcdefghijklmnopqrstuvwxyzABCDEFGHIJKLMNOPQRSTUVWXYZ ;M-Bus Clientname 1, Modul 1;
Z62s;8;CLIENT 19; +-1234567890abcdefghijklmnopqrstuvwxyzABCDEFGHIJKLMNOPQRSTUVWXYZ ;M-Bus Clientname 1, Modul 1;
Z62t;8;CLIENT 20; +-1234567890abcdefghijklmnopqrstuvwxyzABCDEFGHIJKLMNOPQRSTUVWXYZ ;M-Bus Clientname 1, Modul 1;
Z62u;8;CLIENT 21; +-1234567890abcdefghijklmnopqrstuvwxyzABCDEFGHIJKLMNOPQRSTUVWXYZ ;M-Bus Clientname 1, Modul 1;
++Parameterdaten_End++
I noticed, that this is the software version, which is already available in the existing code.
SW=V14.0k4
So, even i was not able to get the msgformat written to the SD card, i now see values in my HA.
Is there any list, which describes the values?
Thanks.
Hello, i tried to get the message format of my Nano PK. But the controller always tells me, that no SD card was found. Do not all controllers support SD cards? Any specific size or format to use? Thank you.