I have the Motologix activated on my YRC1000 and Motologix project installed on my PLC. I am able to read in status from the YRC1000 trough the mlx interface, but I am not able to run the robot from the Motologix interface in the PLC. I suspect this is du to my YRC 1000 parameter are not updated according to https://motologix.yaskawa.eu/setup-robot/part-number/215313/#parameter-settings.
If i get this right, I don't have access to change all this parameters and need help with this from Yaskawa?
It appears that my issues were likely related to a ROS installation running within Motoplus. I resolved the problem by disabling the ROS Motoplus package, and now everything is functioning properly.
I have the Motologix activated on my YRC1000 and Motologix project installed on my PLC. I am able to read in status from the YRC1000 trough the mlx interface, but I am not able to run the robot from the Motologix interface in the PLC. I suspect this is du to my YRC 1000 parameter are not updated according to https://motologix.yaskawa.eu/setup-robot/part-number/215313/#parameter-settings. If i get this right, I don't have access to change all this parameters and need help with this from Yaskawa?