atwhaley / cfast

Automatically exported from code.google.com/p/cfast
0 stars 2 forks source link

Upper layer temperature is the same for various mechanical flow rates. #113

Closed GoogleCodeExporter closed 9 years ago

GoogleCodeExporter commented 9 years ago
What steps will reproduce the problem?
1.   One compartment (7.92mW x11.46mD x4.48mH); the walls, floor, ceiling are 
all concrete.

2.   No horizon flow vent and no vertical vent.  One mechanical flow vent (from 
outside to compartment 1), with various flow rates, e.g., 0.0 m3/sec, 0.1 
m3/sec, 0.236 m3/sec, 0.493 m3/sec, and 5.0 m3/sec.

3.   One fire object; the growth time is 300 sec., the maximal Q is 9690 kW.

What is the expected output? What do you see instead?

The upper layer temperature as a function of time should be different for 
different mechnical flow rate.  But it turns out the temperature is the same 
for the aforementioned various mechanical flow rates.

What version of the product are you using? On what operating system?

CFAST v6.2.0, Window 7.

Please provide any additional information below.

Original issue reported on code.google.com by m...@llnl.gov on 22 Apr 2014 at 7:03

Attachments:

GoogleCodeExporter commented 9 years ago
With no normal vents to relieve the pressure, the compartment nearly instantly 
go to a very high pressure. Which causes the mechanical ventilation system to 
shutdown (default is for the system to stop flow when pressure in compartment 
reaches 300 Pa. With the fire specified, the pressure reaches nearly 50000 Pa, 
hopefully a non-physical result for an actual space.

Thus, there is no real difference regardless of the flowrate specified.  The 
solution would be to include appropriate leakage or other ventilation so that 
pressure did not build to unrealistic levels.

Original comment by rpea...@gmail.com on 28 Feb 2015 at 12:51