No running due to mechanical ventilation from compartment to outside #49

Closed GoogleCodeExporter closed 9 years ago

GoogleCodeExporter commented 9 years ago
version : CFAST 6.1.1.54
OS : window XP

Happy New Year to CFAST users.

Without mechanical ventilation, it works.
If I input mechanical ventilation from compartment #1 to outside, error 
message shows, which tells it needs #2 compartment.

I built #2 compartment and by use of horizontal walls to open, then, the 
messsage comes; "Fatal: Horizontal flow vent 2 is not connected between 
two existing compartments. Select compartment connections."

Is there any way to make forced ventilation from 1 compartment to outside 
or from outside to 1 compartment?

In addition, is there any way to make opening from 1 compartment to 
outside by use of horizontal flow vents?

I attach my file with revised thermal.csv and object files.

Original issue reported on code.google.com by jmh...@gmail.com on 4 Jan 2010 at 2:27

Attachments:

GoogleCodeExporter commented 9 years ago
Problem with test case is not mechanical ventilation which works fine.  Problem 
was an ill-defined heat transfer 
connection on the Surface Connections tab of CEdit.  When there is a problem 
running a specific test case, pose 
the question on the CFAST discussion group at 
http://groups.google.com/group/cfast rather than submitting a 
bug report for the model for a faster response.

Original comment by cfastdev@gmail.com on 3 Feb 2010 at 5:57