Thread of the problem discussed here: https://support.industry.siemens.com/tf/ww/en/posts/154843/
If you use the integrated routing you should not use the device Access, you must use the S7ONLINE access, then the Routing addresses are filled out from the system automatic.
If you use the Device you must insert all relevant information:
Check NCM Project PC/PG object and verify if correct Interface is selected and active. Check IP address matching and load correct config if necessary. Siemens PG/PC Configuration and Diagnostic application in Control Panel must have S7 selected to ISO(CP1613)