No Communication via Industrial Ethernet routed through PLC to Profibus System Drives #3

Open bestrateplc opened 7 years ago

bestrateplc commented 7 years ago

Check NCM Project PC/PG object and verify if correct Interface is selected and active. Check IP address matching and load correct config if necessary. Siemens PG/PC Configuration and Diagnostic application in Control Panel must have S7 selected to ISO(CP1613)

bestrateplc commented 7 years ago

Thread of the problem discussed here: https://support.industry.siemens.com/tf/ww/en/posts/154843/

If you use the integrated routing you should not use the device Access, you must use the S7ONLINE access, then the Routing addresses are filled out from the system automatic.

If you use the Device you must insert all relevant information:

  1. IP of the PLC
  2. Sub net ID to which the G120 is connected
  3. Target Address on the DP Sub net for the G120