Closed VesaliaBricks closed 8 months ago
I have done some testing on my part and I can see correct values without any conversion. Not sure what the value you are receiving represents. Could it be a faulty sensor? Have you checked the values in the Panasonic app?
Here is a screenshot from the parameter values on my pump:
Thank you for your response and for the latest migration!
Apparently, my older ACs do not provide their measured insideTemps and instead report 126. I have found this a few times in my searches. My newer AC reports correctly. In the App, the older ACs have a greyed out display for insideTemp without a value.
I guess I just couldn't imagine an AC not reporting their insideTemps. I mean, they must have it as they attempt to reach and maintain their target temp....
Have a nice weekend!
I understand the device node returns capabilities and settings of a single device. The parameters field shows the current values of my AC.
However, the field parameters.insideTemperature shows a value of 126, which doesn't make sense as neither °C nor °F. As I assume my AC has a thermometer for the inside temp (parameters.OUTTemperature looks plausible) for reaching its target, I was wondering if there is a known conversion for it.
Other than that, I'm very happy with your package, thank you! Sebastian