What steps will reproduce the problem?
1. Start a PLC simulator on a remote PC.
2. Start the test program locally.
3. Kill the simulator.
4. Observe the CPU usage on the PC.
What is the expected output? What do you see instead?
Read/Write function should return with an error.
What version of the product are you using? On what operating system?
WinXP / Win2000 NModBus V1.0
Please provide any additional information below.
Basically in the ReadRequestResponse() method in ModbusTcpTransport.cs the
code is not looking for '0' bytes during the return. So it keeps in the
tight loop while not reading anything. The '0' bytes indicates that the
pipe is closed. Attached is our solution to fix the issue. You will
notice that we also added several more constructors.
Original issue reported on code.google.com by mccar...@att.net on 25 Apr 2007 at 7:37