Open ptruman opened 10 months ago
Ok - tried a manual command and ou_low_noise does exist as a query parameter, but when I've set it on a remote, and queried via POST, the value remains 0
How many indoor units do you have? I believe low noise mode is only available if you have a single indoor unit. I have 2 indoor units and see the same behaviour as you.
4 internal, 1 external - and I can't see anything about it not being able to used with multiple IU? Have you got a manual page showing that?
Its better to manually set the AC to low noise using the DIP SWITCH on the pcb
Just change it back when the winter is over
Just to update - according to my manual, the OU Low Noise is only selectable when there is 1 (single) IU. Multiple IU = "cannot be set". I doubt the integration will know that more than one IU is linked to the same single OU - but if it could, it could be "hidden"
It's winter, so having all my Indoor Units on heat makes the Outdoor Unit "noisy" :) Tried setting "Low Noise" (from one device) and the UI showed it set, then unset about 5 seconds later.
Using the remote works. Not looked too hard yet, but logging for now.