SolarEngineering - System Voltage Map #328

Closed drdanley closed 9 years ago

drdanley commented 9 years ago

Using model "drd se test 1 MW near ss" with feeder "drd ta2015 test 1MW near SS": The triplex meter voltages show minimum voltages of just below 118V at various. However, the "system voltage map" shows a large number of meters as "blue" which indicates meter voltages as low as 110V. These also do not appear to change over time.

image

dpinney commented 9 years ago

Node voltages on map are at primary voltages (in 120 V equivalent scale); meter voltage chart shows secondary voltages.

Unassigning Pooja.

Leaving issue open to track design questions. Add secondary system to voltage map? Change scale?

dpinney commented 9 years ago

PNNL Enhancement Suggestions for solarEngineering that we should also do:

dpinney commented 9 years ago

Merging with #318.