Closed romain145 closed 6 years ago
Possible duplicate of #160. Trace log on serial is needed to check values.
Current [0-5A] MID point:
**TRACE [2017-12-09 18:23:10]: Voltage range: 0.000000 - 40.000000V **TRACE [2017-12-09 18:23:10]: ADC=0.191949 **TRACE [2017-12-09 18:24:13]: ADC check failed: level=2.425000, adc=-0.005169, diff=2.430169, allowedDiff=0.475000
Current [0-5A] MAX point:
**TRACE [2017-12-09 18:25:50]: ADC check failed: level=4.800000, adc=-0.005322, diff=4.805322, allowedDiff=0.475000
Current [0-500mA] MID point:
**TRACE [2017-12-09 18:27:03]: ADC check failed: level=0.242500, adc=-0.000502, diff=0.243002, allowedDiff=0.095000
Current [0-500mA] MAX point:
**TRACE [2017-12-09 18:27:55]: ADC check failed: level=0.480000, adc=-0.000486, diff=0.480486, allowedDiff=0.095000
Channel 2 Current MID point:
**TRACE [2017-12-09 18:29:17]: Voltage range: 0.000000 - 40.000000V **TRACE [2017-12-09 18:29:17]: ADC=0.234834 **TRACE [2017-12-09 18:30:30]: ADC check failed: level=2.425000, adc=-0.005322, diff=2.430321, allowedDiff=0.475000
Also, clicking "Change" after setting a calibration value doesn't re-enable the output.
Do you have load connected during current calibration?
Yes, but it seems that my load impedance was way too low for the PSU. I'm trying with a 1 Ohm load now and went through the calibration!
For some calibration, clicking "Change" after setting a calibration value doesn't re-enable the output.
Yes, but it seems that my load impedance was way too low for the PSU. I'm trying with a 1 Ohm load now and went through the calibration!
You mean your load is too high, since measured current is zero. Use resistor that is lower then about 4 Ohms as it's clearly stated here.
For some calibration, clicking "Change" after setting a calibration value doesn't re-enable the output.
Please be more specific. Which "Change" button/option?
The multimeter was correctly measuring the current so I'm not sure what the deal was... Indeed, by using a 1-4 Ohm load, the calibration procedure runs just fine. Great job !
The Change option is working, I noticed I blew the low amp range fuse on my multimeter (EEVBlog BM235). The multimeter case is rated 600mA, so I used it for the 500mA calibration; however, Dave fitted a 400mA fuse...
Closing
Expected behavior
When calibrating Ch1 MID point current, I should be able to enter the value I measured: 2.492 (A).
Actual behavior
The screen displays an error "Value out of range".
How to reproduce
Enter 2.492 for current MID point calibration.