Closed Oktonaut closed 2 months ago
This switch was reported in #1415 as telegram 0x48D, offset 3, bit 6. Could you check with custom entity the value of 0x48D, offset 3 and if there is a change.
What exactly should I enter in the form fields for an individual entity?
I would say this:
but Value-Type UINT will also do. You'll get a EA0 entiy in dashboard and mqtt as custom_data. Check if it changes when the heater switches.
Here it looks a little different:
When switched off, this returns the value: 08
Due to the current outside temperature, it is not turning on at the moment.
So wait for colder tempertures and check. Or is there a testmenu where you can manual set the output?
This cannot be switched manually. But today it was cold enough that the heat pump switched to defrost mode. However, the entity set unfortunately has nothing to do with the EA0 switching output. Even though the value changed twice at the end of the defrosting process, it unfortunately does not correspond to EA0.
Are there any other possible values that I should log? There will be more and more spring and therefore not many cold days to be able to do this...
I can't think of any. Maybe there's a Test Function to simulate the switching on/off of the outdoor unit. Those Buderus systems usually come with test like these which the service guys use
PROBLEM DESCRIPTION
Last year I replaced our Buderus GB142-15 condensing boiler with a split heat pump. This is the Logatherm WLW 166i-10 E (indoor unit) in conjunction with WLW-8 SP AR (outdoor unit). EMS-ESP recognized the new device immediately. I just adjusted the inadequate naming of some entities.
So that the condensation drain on the outdoor unit no longer freezes, I retrofitted the heating cable from Buderus. Unfortunately, the associated entity: hpea0 / condensate pan heater (EA0) remains continuously OFF. In order to be able to check the actual status of the heating cable, I connected a Shelly and was able to determine that it was switched on correctly.
REQUESTED INFORMATION
EXPECTED BEHAVIOUR
The entity should always reflect the actual status of the output.
SCREENSHOTS
ADDITIONAL CONTEXT
Add any other context about the problem here.
For your information, here are the entity names I made