Boost mode not error-free #1604

Open SeibeGitHub opened 7 months ago

SeibeGitHub commented 7 months ago

Buderus GB182i.2-20

BC400 V3.07.43

Boost works correctly from 1-4 hours, from 5 hours it is only active for 45 minutes. It seems as if calculations are being carried out in minutes with an 8-bit data type (decimal max 255) in the BC400. E.g. 4 hours = 240 minutes 5 hours = 300 minutes overflow! 300-255=45 can anyone confirm this? The error lies in the BC400 control

proddy commented 6 months ago

Perhaps @Bingo2023 can verify?

Bingo2023 commented 6 months ago

EMS-ESP Version 3.6.5-test.16

Set via Home Assistant and checked with Buderus App.

image

Seems like 8h is max, 1-8h are working in my system.

SeibeGitHub commented 6 months ago

Hello,

does boost really run for 8 hours? Or just 225 minutes for 8 hours. The quickest way to test the error is to turn on the boost for 5 hours and then it switches off after just 45 minutes. I have already been in contact with Buderus, they have confirmed the error and it should be fixed with new BC400 firmware in mid-2024.

Greetings

Ing-Dom commented 4 months ago

@SeibeGitHub they really talk to you?

I never got anyone from this company talking to me... which way did you contact them?

SeibeGitHub commented 4 months ago

Sehr geehrter Herr xxxxx,

nach Rückinfo unserer Entwicklungsabteilung ist in der Software der von Ihnen vermutete Fehler einprogrammiert. Mit einer neuen Softwareversion ist jedoch erst ab Mitte 2024 zu rechnen, Erst dann wird auch dieser Fehler dann bereinigt sein. Wir werden uns mit Ihnen in Verbindung setzen, wenn die neue Software zur Verfügung steht. Bis dahin bitten wir noch um etwas Geduld. Vielen Dank dafür.

Mit freundlichen Grüßen / Best regards

xxxx xxxx

Customer Care Center Esslingen (TTDB/SGS-SCU) Bosch Thermotechnik GmbH - Buderus Deutschland | Wolf-Hirth-Str. 8 | 73730 Esslingen | GERMANY | www.buderus.de SCU_SGS@buderus.de

I made a complaint through the installer and after Buderus customer service was at the house I had a contact person.