The BACKPRESS PV is mapped to signal 1064: StatusLinePressure. That signal is reported with values 0xfffe. The correct signal is 1101: FlowBlockBackPressure which is reported with a more realistic value 28 (mbar).
BACKPRESS
1064: StatusLinePressure
0xfffe
1101: FlowBlockBackPressure
28
Note that the display in #30 shows units of bar, not mbar.