Batteriesteuerung funktioniert nicht bei Solaredge #12994

Closed Cytron1980 closed 6 months ago

Cytron1980 commented 6 months ago

Describe the bug

Batterie wird trotz Anzeige "gesperrt" beim Modus "Schnell" entladen. Aufgefallen heute. Ha die letzten Tage aber funktioniert. Abwahl der Funktion, Neustart von EVCC und Modus-Umstellung hat nicht geholfen.

Steps to reproduce

  1. Auto anschließen 2.Modus "Schnell" aktivieren

Configuration details

# open evcc at http://evcc.local:7070
network:
  schema: http
  host: evcc.local # .local suffix announces the hostname on MDNS
  port: 7070

log: debug
levels:
  cache: error

# unique installation id
plant: 40e7a34a253eb356e07322451451f552e79457aa1fd68cf282472088ac0f1c4b

interval: 10s # control cycle interval

sponsortoken: XXXXXXX

# sponsors can set telemetry: true to enable anonymous data aggregation
# see https://github.com/evcc-io/evcc/discussions/4554
telemetry: false

meters:
- type: template
  template: solaredge-hybrid 
  id: 1  
  host: 192.168.2.201  
  port: 1502  
  usage: grid  
  modbus: tcpip  
  name: grid1
- type: template
  template: solaredge-hybrid 
  id: 1  
  host: 192.168.2.201  
  port: 1502  
  usage: pv  
  modbus: tcpip  
  name: pv2
- type: template
  template: solaredge-hybrid 
  id: 1  
  host: 192.168.2.201  
  port: 1502  
  usage: battery  
  modbus: tcpip  
  name: battery3

chargers:
- type: template
  template: easee 
  user: XXXteme.com  
  password: XXX  
  charger: XXX 
  timeout: 10s  
  name: wallbox

vehicles:
- type: template
  template: vw 
  title: ID4 Pro  
  user: XXX 
  password: XXX
  vin: XXX  
  capacity: 77  
  timeout: 10s  
  name: ev4

loadpoints:
- title: HWW10
  charger: wallbox
  mode: pv
  phases: 0

site:
  title: HWW 10
  meters:
    grid: grid1
    pv:
    - pv2
    battery:
    - battery3

tariffs:
  grid:
    # either
    type: tibber
    token: "XXX" # access token

Log details

[site  ] DEBUG 2024/03/16 17:07:02 ----
[lp-1  ] DEBUG 2024/03/16 17:07:02 charge power: 0W
[site  ] DEBUG 2024/03/16 17:07:02 pv power: 566W
[site  ] DEBUG 2024/03/16 17:07:03 battery soc: 29%
[site  ] DEBUG 2024/03/16 17:07:03 battery power: -253W
[site  ] DEBUG 2024/03/16 17:07:03 grid meter: -2W
[site  ] DEBUG 2024/03/16 17:07:03 battery has priority at soc 29% (< 95%)
[site  ] DEBUG 2024/03/16 17:07:03 site power: -2W
[lp-1  ] DEBUG 2024/03/16 17:07:03 charge currents: [0.009 0.011 0.009]A
[lp-1  ] DEBUG 2024/03/16 17:07:03 charge total import: 2419.467kWh
[lp-1  ] DEBUG 2024/03/16 17:07:03 charger status: B
[site  ] DEBUG 2024/03/16 17:07:12 ----
[lp-1  ] DEBUG 2024/03/16 17:07:12 charge power: 0W
[site  ] DEBUG 2024/03/16 17:07:13 pv power: 549W
[site  ] DEBUG 2024/03/16 17:07:13 battery soc: 29%
[site  ] DEBUG 2024/03/16 17:07:13 battery power: -224W
[site  ] DEBUG 2024/03/16 17:07:13 grid meter: -10W
[site  ] DEBUG 2024/03/16 17:07:13 battery has priority at soc 29% (< 95%)
[site  ] DEBUG 2024/03/16 17:07:13 site power: -10W
[lp-1  ] DEBUG 2024/03/16 17:07:13 charge currents: [0.009 0.011 0.009]A
[lp-1  ] DEBUG 2024/03/16 17:07:13 charge total import: 2419.467kWh
[lp-1  ] DEBUG 2024/03/16 17:07:13 charger status: B
[site  ] DEBUG 2024/03/16 17:07:22 ----
[lp-1  ] DEBUG 2024/03/16 17:07:22 charge power: 0W
[site  ] DEBUG 2024/03/16 17:07:23 pv power: 562W
[site  ] DEBUG 2024/03/16 17:07:23 battery soc: 29%
[site  ] DEBUG 2024/03/16 17:07:23 battery power: -166W
[site  ] DEBUG 2024/03/16 17:07:23 grid meter: -58W
[site  ] DEBUG 2024/03/16 17:07:23 battery has priority at soc 29% (< 95%)
[site  ] DEBUG 2024/03/16 17:07:23 site power: -58W
[lp-1  ] DEBUG 2024/03/16 17:07:23 charge currents: [0.009 0.011 0.009]A
[lp-1  ] DEBUG 2024/03/16 17:07:23 charge total import: 2419.467kWh
[lp-1  ] DEBUG 2024/03/16 17:07:23 charger status: B
[site  ] DEBUG 2024/03/16 17:07:32 ----
[lp-1  ] DEBUG 2024/03/16 17:07:32 charge power: 0W
[site  ] DEBUG 2024/03/16 17:07:32 pv power: 578W
[site  ] DEBUG 2024/03/16 17:07:33 battery soc: 29%
[site  ] DEBUG 2024/03/16 17:07:33 battery power: -260W
[site  ] DEBUG 2024/03/16 17:07:33 grid meter: 15W
[site  ] DEBUG 2024/03/16 17:07:33 battery has priority at soc 29% (< 95%)
[site  ] DEBUG 2024/03/16 17:07:33 site power: 15W
[lp-1  ] DEBUG 2024/03/16 17:07:33 charge currents: [0.009 0.011 0.009]A
[lp-1  ] DEBUG 2024/03/16 17:07:33 charge total import: 2419.467kWh
[lp-1  ] DEBUG 2024/03/16 17:07:33 charger status: B
[site  ] DEBUG 2024/03/16 17:07:42 ----
[lp-1  ] DEBUG 2024/03/16 17:07:42 charge power: 0W
[site  ] DEBUG 2024/03/16 17:07:43 pv power: 554W
[site  ] DEBUG 2024/03/16 17:07:43 battery soc: 29%
[site  ] DEBUG 2024/03/16 17:07:43 battery power: -323W
[site  ] DEBUG 2024/03/16 17:07:43 grid meter: 30W
[site  ] DEBUG 2024/03/16 17:07:43 battery has priority at soc 29% (< 95%)
[site  ] DEBUG 2024/03/16 17:07:43 site power: 30W
[lp-1  ] DEBUG 2024/03/16 17:07:43 charge currents: [0.009 0.011 0.009]A
[lp-1  ] DEBUG 2024/03/16 17:07:43 charge total import: 2419.467kWh
[lp-1  ] DEBUG 2024/03/16 17:07:43 charger status: B
[lp-1  ] DEBUG 2024/03/16 17:07:45 set charge mode: now
[site  ] DEBUG 2024/03/16 17:07:45 ----
[lp-1  ] DEBUG 2024/03/16 17:07:45 charge power: 0W
[site  ] DEBUG 2024/03/16 17:07:45 pv power: 557W
[site  ] DEBUG 2024/03/16 17:07:45 battery soc: 29%
[site  ] DEBUG 2024/03/16 17:07:45 battery power: -303W
[site  ] DEBUG 2024/03/16 17:07:45 grid meter: -0W
[site  ] DEBUG 2024/03/16 17:07:45 battery has priority at soc 29% (< 95%)
[site  ] DEBUG 2024/03/16 17:07:45 site power: 0W
[lp-1  ] DEBUG 2024/03/16 17:07:45 charge currents: [0.009 0.011 0.009]A
[lp-1  ] DEBUG 2024/03/16 17:07:45 charge total import: 2419.467kWh
[lp-1  ] DEBUG 2024/03/16 17:07:45 charger status: B
[easee ] TRACE 2024/03/16 17:07:45 POST https://api.easee.com/api/chargers/EHNRT639/settings
[easee ] TRACE 2024/03/16 17:07:46 {"dynamicChargerCurrent":16}
--
[{"device":"EHNRT639","commandId":48,"ticks":638462020675439280}]
[easee ] TRACE 2024/03/16 17:07:47 ProductUpdate EHNRT639: (2024-03-16 16:07:47 +0000 UTC) DYNAMIC_CHARGER_CURRENT 16
[easee ] TRACE 2024/03/16 17:07:47 CommandResponse EHNRT639: {SerialNumber:EHNRT639 ID:48 Timestamp:2024-03-16 16:07:47.543928 +0000 UTC DeliveredAt:2024-03-16 16:07:47.715 +0000 UTC WasAccepted:true ResultCode:0 Comment: Ticks:638462020675439280}
[lp-1  ] DEBUG 2024/03/16 17:07:47 max charge current: 16A
[easee ] TRACE 2024/03/16 17:07:47 POST https://api.easee.com/api/chargers/EHNRT639/commands/resume_charging
[easee ] TRACE 2024/03/16 17:07:47 {"device":"EHNRT639","commandId":48,"ticks":638462020687760190}
[easee ] TRACE 2024/03/16 17:07:47 ProductUpdate EHNRT639: (2024-03-16 16:07:48 +0000 UTC) REASON_FOR_NO_CURRENT 8
[easee ] TRACE 2024/03/16 17:07:47 ProductUpdate EHNRT639: (2024-03-16 16:07:48 +0000 UTC) NUMBER_OF_CARS_CONNECTED 1
[easee ] TRACE 2024/03/16 17:07:47 ProductUpdate EHNRT639: (2024-03-16 16:07:48 +0000 UTC) NUMBER_OF_CARS_IN_QUEUE 1
[easee ] TRACE 2024/03/16 17:07:47 CommandResponse EHNRT639: {SerialNumber:EHNRT639 ID:48 Timestamp:2024-03-16 16:07:48.776019 +0000 UTC DeliveredAt:2024-03-16 16:07:48.755 +0000 UTC WasAccepted:true ResultCode:0 Comment: Ticks:638462020687760190}
[easee ] TRACE 2024/03/16 17:07:48 ProductUpdate EHNRT639: (2024-03-16 16:07:48 +0000 UTC) REASON_FOR_NO_CURRENT 100
[easee ] TRACE 2024/03/16 17:07:48 ProductUpdate EHNRT639: (2024-03-16 16:07:48 +0000 UTC) DYNAMIC_CHARGER_CURRENT 32
[easee ] TRACE 2024/03/16 17:07:48 ProductUpdate EHNRT639: (2024-03-16 16:07:49 +0000 UTC) REASON_FOR_NO_CURRENT 5
[easee ] TRACE 2024/03/16 17:07:48 ProductUpdate EHNRT639: (2024-03-16 16:07:49 +0000 UTC) NUMBER_OF_CARS_CHARGING 1
[easee ] TRACE 2024/03/16 17:07:48 ProductUpdate EHNRT639: (2024-03-16 16:07:49 +0000 UTC) NUMBER_OF_CARS_IN_QUEUE 0
[easee ] TRACE 2024/03/16 17:07:48 POST https://api.easee.com/api/chargers/EHNRT639/settings
[easee ] TRACE 2024/03/16 17:07:48 {"dynamicChargerCurrent":16}
--
[{"device":"EHNRT639","commandId":48,"ticks":638462020703168890}]
[easee ] TRACE 2024/03/16 17:07:49 ProductUpdate EHNRT639: (2024-03-16 16:07:49 +0000 UTC) CIRCUIT_TOTAL_ALLOCATED_PHASE_CONDUCTOR_CURRENT_L1 16
[easee ] TRACE 2024/03/16 17:07:49 ProductUpdate EHNRT639: (2024-03-16 16:07:49 +0000 UTC) CIRCUIT_TOTAL_ALLOCATED_PHASE_CONDUCTOR_CURRENT_L2 16
[easee ] TRACE 2024/03/16 17:07:49 ProductUpdate EHNRT639: (2024-03-16 16:07:49 +0000 UTC) CIRCUIT_TOTAL_ALLOCATED_PHASE_CONDUCTOR_CURRENT_L3 16
[easee ] TRACE 2024/03/16 17:07:49 ProductUpdate EHNRT639: (2024-03-16 16:07:49 +0000 UTC) CHARGER_OP_MODE 6
[easee ] TRACE 2024/03/16 17:07:49 ProductUpdate EHNRT639: (2024-03-16 16:07:49 +0000 UTC) OUTPUT_PHASE 30
[easee ] TRACE 2024/03/16 17:07:49 ProductUpdate EHNRT639: (2024-03-16 16:07:49 +0000 UTC) OUTPUT_CURRENT 16
[easee ] TRACE 2024/03/16 17:07:49 ProductUpdate EHNRT639: (2024-03-16 16:07:50 +0000 UTC) REASON_FOR_NO_CURRENT 25
[easee ] TRACE 2024/03/16 17:07:49 CommandResponse EHNRT639: {SerialNumber:EHNRT639 ID:48 Timestamp:2024-03-16 16:07:50.316889 +0000 UTC DeliveredAt:2024-03-16 16:07:50.295 +0000 UTC WasAccepted:true ResultCode:0 Comment: Ticks:638462020703168890}
[easee ] TRACE 2024/03/16 17:07:50 ProductUpdate EHNRT639: (2024-03-16 16:07:50 +0000 UTC) DYNAMIC_CHARGER_CURRENT 16
[lp-1  ] DEBUG 2024/03/16 17:07:50 charger enable
[easee ] TRACE 2024/03/16 17:07:50 ProductUpdate EHNRT639: (2024-03-16 16:07:50 +0000 UTC) REASON_FOR_NO_CURRENT 78
[lp-1  ] DEBUG 2024/03/16 17:07:50 wake-up timer: start
[easee ] TRACE 2024/03/16 17:07:50 ProductUpdate EHNRT639: (2024-03-16 16:07:50 +0000 UTC) IN_CURRENT_T4 1.0640000104904175
[easee ] TRACE 2024/03/16 17:07:50 ProductUpdate EHNRT639: (2024-03-16 16:07:50 +0000 UTC) OUT_VOLT_PIN1_4 158.1219940185547
[easee ] TRACE 2024/03/16 17:07:50 ProductUpdate EHNRT639: (2024-03-16 16:07:50 +0000 UTC) OUT_VOLT_PIN1_5 161.90199279785156
[easee ] TRACE 2024/03/16 17:07:50 ProductUpdate EHNRT639: (2024-03-16 16:07:50 +0000 UTC) IN_CURRENT_T3 1.0499999523162842
[easee ] TRACE 2024/03/16 17:07:50 ProductUpdate EHNRT639: (2024-03-16 16:07:50 +0000 UTC) OUT_VOLT_PIN1_3 162.95399475097656
[easee ] TRACE 2024/03/16 17:07:50 ProductUpdate EHNRT639: (2024-03-16 16:07:50 +0000 UTC) CHARGER_OP_MODE 3
[easee ] TRACE 2024/03/16 17:07:50 ProductUpdate EHNRT639: (2024-03-16 16:07:50 +0000 UTC) PILOT_MODE C
[easee ] TRACE 2024/03/16 17:07:50 ProductUpdate EHNRT639: (2024-03-16 16:07:51 +0000 UTC) CIRCUIT_TOTAL_PHASE_CONDUCTOR_CURRENT_L1 1.0499999523162842
[easee ] TRACE 2024/03/16 17:07:50 ProductUpdate EHNRT639: (2024-03-16 16:07:51 +0000 UTC) CIRCUIT_TOTAL_PHASE_CONDUCTOR_CURRENT_L2 1.0640000104904175
[easee ] TRACE 2024/03/16 17:07:51 ProductUpdate EHNRT639: (2024-03-16 16:07:51 +0000 UTC) TOTAL_POWER 0.09600000083446503
[easee ] TRACE 2024/03/16 17:07:52 ProductUpdate EHNRT639: (2024-03-16 16:07:52 +0000 UTC) LEDMODE 24
[easee ] TRACE 2024/03/16 17:07:52 ProductUpdate EHNRT639: (2024-03-16 16:07:52 +0000 UTC) IN_CURRENT_T2 4.197999954223633
[site  ] DEBUG 2024/03/16 17:07:52 ----
[lp-1  ] DEBUG 2024/03/16 17:07:52 charge power: 96W
[site  ] DEBUG 2024/03/16 17:07:52 pv power: 564W
[site  ] DEBUG 2024/03/16 17:07:53 battery soc: 29%
[site  ] DEBUG 2024/03/16 17:07:53 battery power: -300W
[easee ] TRACE 2024/03/16 17:07:53 ProductUpdate EHNRT639: (2024-03-16 16:07:53 +0000 UTC) IN_CURRENT_T5 14.092000007629395
[easee ] TRACE 2024/03/16 17:07:53 ProductUpdate EHNRT639: (2024-03-16 16:07:53 +0000 UTC) IN_VOLT_T2_T5 234.16700744628906
[easee ] TRACE 2024/03/16 17:07:53 ProductUpdate EHNRT639: (2024-03-16 16:07:53 +0000 UTC) IN_VOLT_T2_T4 233.0709991455078
[site  ] DEBUG 2024/03/16 17:07:53 grid meter: 10707W
[site  ] DEBUG 2024/03/16 17:07:53 battery has priority at soc 29% (< 95%)
[site  ] DEBUG 2024/03/16 17:07:53 site power: 10707W
[lp-1  ] DEBUG 2024/03/16 17:07:53 charge currents: [1.05 1.06 14.1]A
[lp-1  ] DEBUG 2024/03/16 17:07:53 charge total import: 2419.467kWh
[easee ] TRACE 2024/03/16 17:07:53 ProductUpdate EHNRT639: (2024-03-16 16:07:53 +0000 UTC) TEMP_MAX 16
[easee ] TRACE 2024/03/16 17:07:53 ProductUpdate EHNRT639: (2024-03-16 16:07:53 +0000 UTC) IN_VOLT_T2_T3 227.2989959716797
[lp-1  ] DEBUG 2024/03/16 17:07:53 charger status: C
[lp-1  ] INFO 2024/03/16 17:07:53 start charging ->
[lp-1  ] DEBUG 2024/03/16 17:07:53 wake-up timer: stop
[easee ] TRACE 2024/03/16 17:07:54 ProductUpdate EHNRT639: (2024-03-16 16:07:54 +0000 UTC) CIRCUIT_TOTAL_PHASE_CONDUCTOR_CURRENT_L3 14.092000007629395
[lp-1  ] DEBUG 2024/03/16 17:07:54 soc estimated: 46.13% (vehicle: 46.00%)
[lp-1  ] DEBUG 2024/03/16 17:07:54 vehicle soc: 46%
[lp-1  ] DEBUG 2024/03/16 17:07:54 vehicle soc limit: 80%
[lp-1  ] DEBUG 2024/03/16 17:07:54 vehicle range: 174km
[site  ] DEBUG 2024/03/16 17:07:54 set battery mode: hold
[easee ] TRACE 2024/03/16 17:07:55 ProductUpdate EHNRT639: (2024-03-16 16:07:56 +0000 UTC) CIRCUIT_TOTAL_PHASE_CONDUCTOR_CURRENT_L1 15.161999702453613
[easee ] TRACE 2024/03/16 17:07:55 ProductUpdate EHNRT639: (2024-03-16 16:07:56 +0000 UTC) CIRCUIT_TOTAL_PHASE_CONDUCTOR_CURRENT_L2 15.229000091552734
[easee ] TRACE 2024/03/16 17:07:57 ProductUpdate EHNRT639: (2024-03-16 16:07:57 +0000 UTC) IN_CURRENT_T2 0.3709999918937683
[easee ] TRACE 2024/03/16 17:07:57 ProductUpdate EHNRT639: (2024-03-16 16:07:57 +0000 UTC) IN_CURRENT_T4 15.210000038146973
[easee ] TRACE 2024/03/16 17:07:57 ProductUpdate EHNRT639: (2024-03-16 16:07:57 +0000 UTC) OUT_VOLT_PIN1_4 229.91900634765625
[easee ] TRACE 2024/03/16 17:07:57 ProductUpdate EHNRT639: (2024-03-16 16:07:57 +0000 UTC) OUT_VOLT_PIN1_5 235.45799255371094
[easee ] TRACE 2024/03/16 17:07:57 ProductUpdate EHNRT639: (2024-03-16 16:07:57 +0000 UTC) IN_CURRENT_T3 15.180000305175781
[easee ] TRACE 2024/03/16 17:07:57 ProductUpdate EHNRT639: (2024-03-16 16:07:57 +0000 UTC) TOTAL_POWER 10.487000465393066
[easee ] TRACE 2024/03/16 17:07:57 ProductUpdate EHNRT639: (2024-03-16 16:07:57 +0000 UTC) OUT_VOLT_PIN1_3 235.42999267578125
[easee ] TRACE 2024/03/16 17:07:58 ProductUpdate EHNRT639: (2024-03-16 16:07:58 +0000 UTC) IN_CURRENT_T5 15.248000144958496
[easee ] TRACE 2024/03/16 17:07:59 ProductUpdate EHNRT639: (2024-03-16 16:07:59 +0000 UTC) CIRCUIT_TOTAL_PHASE_CONDUCTOR_CURRENT_L3 15.248000144958496
[site  ] DEBUG 2024/03/16 17:08:02 ----
[lp-1  ] DEBUG 2024/03/16 17:08:02 charge power: 10487W
[site  ] DEBUG 2024/03/16 17:08:02 pv power: 513W
[site  ] DEBUG 2024/03/16 17:08:03 battery soc: 29%
[site  ] DEBUG 2024/03/16 17:08:03 battery power: 5001W
[site  ] DEBUG 2024/03/16 17:08:03 grid meter: 5490W
[site  ] DEBUG 2024/03/16 17:08:03 site power: 10491W
[lp-1  ] DEBUG 2024/03/16 17:08:03 charge currents: [15.2 15.2 15.2]A
[lp-1  ] DEBUG 2024/03/16 17:08:03 detected active phases: 3p
[lp-1  ] DEBUG 2024/03/16 17:08:03 charge total import: 2419.467kWh
[lp-1  ] DEBUG 2024/03/16 17:08:03 charger status: C
[lp-1  ] DEBUG 2024/03/16 17:08:03 soc estimated: 46.13% (vehicle: 46.00%)
[lp-1  ] DEBUG 2024/03/16 17:08:03 vehicle soc: 46%
[lp-1  ] DEBUG 2024/03/16 17:08:03 vehicle soc limit: 80%
[lp-1  ] DEBUG 2024/03/16 17:08:03 vehicle range: 174km
[lp-1  ] DEBUG 2024/03/16 17:08:04 set charge mode: off
[site  ] DEBUG 2024/03/16 17:08:04 ----
[lp-1  ] DEBUG 2024/03/16 17:08:04 charge power: 10487W
[site  ] DEBUG 2024/03/16 17:08:04 pv power: 527W
[site  ] DEBUG 2024/03/16 17:08:04 battery soc: 29%
[site  ] DEBUG 2024/03/16 17:08:04 battery power: 5002W
[site  ] DEBUG 2024/03/16 17:08:04 grid meter: 5502W
[site  ] DEBUG 2024/03/16 17:08:04 site power: 10504W
[lp-1  ] DEBUG 2024/03/16 17:08:04 charge currents: [15.2 15.2 15.2]A
[lp-1  ] DEBUG 2024/03/16 17:08:04 detected active phases: 3p
[lp-1  ] DEBUG 2024/03/16 17:08:04 charge total import: 2419.467kWh
[lp-1  ] DEBUG 2024/03/16 17:08:04 charger status: C
[lp-1  ] DEBUG 2024/03/16 17:08:04 soc estimated: 46.13% (vehicle: 46.00%)
[lp-1  ] DEBUG 2024/03/16 17:08:04 vehicle soc: 46%
[lp-1  ] DEBUG 2024/03/16 17:08:04 vehicle soc limit: 80%
[lp-1  ] DEBUG 2024/03/16 17:08:04 vehicle range: 174km
[easee ] TRACE 2024/03/16 17:08:04 POST https://api.easee.com/api/chargers/EHNRT639/commands/pause_charging
[easee ] TRACE 2024/03/16 17:08:04 {"device":"EHNRT639","commandId":48,"ticks":638462020860117190}
[easee ] TRACE 2024/03/16 17:08:05 CommandResponse EHNRT639: {SerialNumber:EHNRT639 ID:48 Timestamp:2024-03-16 16:08:06.011719 +0000 UTC DeliveredAt:2024-03-16 16:08:06.015 +0000 UTC WasAccepted:true ResultCode:0 Comment: Ticks:638462020860117190}
[easee ] TRACE 2024/03/16 17:08:05 ProductUpdate EHNRT639: (2024-03-16 16:08:06 +0000 UTC) DYNAMIC_CHARGER_CURRENT 0
[easee ] TRACE 2024/03/16 17:08:06 ProductUpdate EHNRT639: (2024-03-16 16:08:06 +0000 UTC) REASON_FOR_NO_CURRENT 52
[easee ] TRACE 2024/03/16 17:08:06 ProductUpdate EHNRT639: (2024-03-16 16:08:06 +0000 UTC) NUMBER_OF_CARS_CONNECTED 0
[easee ] TRACE 2024/03/16 17:08:06 ProductUpdate EHNRT639: (2024-03-16 16:08:06 +0000 UTC) NUMBER_OF_CARS_CHARGING 0
[easee ] TRACE 2024/03/16 17:08:06 ProductUpdate EHNRT639: (2024-03-16 16:08:06 +0000 UTC) OUTPUT_CURRENT 0
[easee ] TRACE 2024/03/16 17:08:07 ProductUpdate EHNRT639: (2024-03-16 16:08:07 +0000 UTC) CIRCUIT_TOTAL_ALLOCATED_PHASE_CONDUCTOR_CURRENT_L1 0
[easee ] TRACE 2024/03/16 17:08:07 ProductUpdate EHNRT639: (2024-03-16 16:08:07 +0000 UTC) CIRCUIT_TOTAL_ALLOCATED_PHASE_CONDUCTOR_CURRENT_L2 0
[easee ] TRACE 2024/03/16 17:08:07 ProductUpdate EHNRT639: (2024-03-16 16:08:07 +0000 UTC) CIRCUIT_TOTAL_ALLOCATED_PHASE_CONDUCTOR_CURRENT_L3 0
[easee ] TRACE 2024/03/16 17:08:07 ProductUpdate EHNRT639: (2024-03-16 16:08:07 +0000 UTC) LEDMODE 23
[easee ] TRACE 2024/03/16 17:08:07 ProductUpdate EHNRT639: (2024-03-16 16:08:07 +0000 UTC) IN_CURRENT_T4 0.10499999672174454
[easee ] TRACE 2024/03/16 17:08:07 ProductUpdate EHNRT639: (2024-03-16 16:08:07 +0000 UTC) IN_CURRENT_T5 0.10899999737739563
[easee ] TRACE 2024/03/16 17:08:07 ProductUpdate EHNRT639: (2024-03-16 16:08:07 +0000 UTC) OUT_VOLT_PIN1_4 75.49099731445312
[easee ] TRACE 2024/03/16 17:08:07 ProductUpdate EHNRT639: (2024-03-16 16:08:07 +0000 UTC) OUT_VOLT_PIN1_5 66.18000030517578
[easee ] TRACE 2024/03/16 17:08:07 ProductUpdate EHNRT639: (2024-03-16 16:08:07 +0000 UTC) IN_CURRENT_T3 0.1080000028014183
[easee ] TRACE 2024/03/16 17:08:07 ProductUpdate EHNRT639: (2024-03-16 16:08:07 +0000 UTC) TOTAL_POWER 0
[easee ] TRACE 2024/03/16 17:08:07 ProductUpdate EHNRT639: (2024-03-16 16:08:07 +0000 UTC) OUT_VOLT_PIN1_3 57.303001403808594
[easee ] TRACE 2024/03/16 17:08:07 ProductUpdate EHNRT639: (2024-03-16 16:08:07 +0000 UTC) CHARGER_OP_MODE 2
[easee ] TRACE 2024/03/16 17:08:07 ProductUpdate EHNRT639: (2024-03-16 16:08:07 +0000 UTC) OUTPUT_PHASE 0
[easee ] TRACE 2024/03/16 17:08:07 ProductUpdate EHNRT639: (2024-03-16 16:08:07 +0000 UTC) PILOT_MODE B
[lp-1  ] DEBUG 2024/03/16 17:08:07 charger disable
[lp-1  ] DEBUG 2024/03/16 17:08:07 wake-up timer: stop
[site  ] DEBUG 2024/03/16 17:08:07 set battery mode: normal
[easee ] TRACE 2024/03/16 17:08:08 ProductUpdate EHNRT639: (2024-03-16 16:08:08 +0000 UTC) CIRCUIT_TOTAL_PHASE_CONDUCTOR_CURRENT_L1 0.1080000028014183
[easee ] TRACE 2024/03/16 17:08:08 ProductUpdate EHNRT639: (2024-03-16 16:08:08 +0000 UTC) CIRCUIT_TOTAL_PHASE_CONDUCTOR_CURRENT_L2 0.10499999672174454
[easee ] TRACE 2024/03/16 17:08:08 ProductUpdate EHNRT639: (2024-03-16 16:08:08 +0000 UTC) CIRCUIT_TOTAL_PHASE_CONDUCTOR_CURRENT_L3 0.10899999737739563
[site  ] DEBUG 2024/03/16 17:08:12 ----
[lp-1  ] DEBUG 2024/03/16 17:08:12 charge power: 0W
[site  ] DEBUG 2024/03/16 17:08:13 pv power: 554W
[site  ] DEBUG 2024/03/16 17:08:13 battery soc: 29%
[site  ] DEBUG 2024/03/16 17:08:13 battery power: 2950W
[site  ] DEBUG 2024/03/16 17:08:13 grid meter: -3232W
[site  ] DEBUG 2024/03/16 17:08:13 site power: -282W
[lp-1  ] DEBUG 2024/03/16 17:08:13 charge currents: [0.108 0.105 0.109]A
[lp-1  ] DEBUG 2024/03/16 17:08:13 charge total import: 2419.467kWh
[lp-1  ] DEBUG 2024/03/16 17:08:13 charger status: B
[lp-1  ] INFO 2024/03/16 17:08:13 stop charging <-
[lp-1  ] DEBUG 2024/03/16 17:08:13 charge total import: 2419.467kWh
[easee ] TRACE 2024/03/16 17:08:13 ProductUpdate EHNRT639: (2024-03-16 16:08:13 +0000 UTC) OUT_VOLT_PIN1_4 0.13500000536441803
[easee ] TRACE 2024/03/16 17:08:13 ProductUpdate EHNRT639: (2024-03-16 16:08:13 +0000 UTC) OUT_VOLT_PIN1_5 1.9240000247955322
[easee ] TRACE 2024/03/16 17:08:13 ProductUpdate EHNRT639: (2024-03-16 16:08:13 +0000 UTC) OUT_VOLT_PIN1_3 0.9940000176429749
[lp-1  ] DEBUG 2024/03/16 17:08:14 soc estimated: 46.13% (vehicle: 46.00%)
[lp-1  ] DEBUG 2024/03/16 17:08:14 vehicle soc: 46%
[lp-1  ] DEBUG 2024/03/16 17:08:14 vehicle soc limit: 80%
[lp-1  ] DEBUG 2024/03/16 17:08:14 vehicle range: 174km

What type of operating system are you running?

Windows

Version

0.124.10

andig commented 6 months ago
[site  ] DEBUG 2024/03/16 17:07:54 set battery mode: hold
[site  ] DEBUG 2024/03/16 17:08:03 battery power: 5001W

@premultiply hast Du eine Idee?

mucki12 commented 6 months ago

Gibt es da vielleicht einen Zusammenhang? https://github.com/evcc-io/evcc/discussions/12990

Gotcha1980 commented 6 months ago

Es gibt eine neue Funktion bei solaredge die nennt sich Time of Use wenn man die zum testen einstellt und danach wieder auf Maximum Self consumption wechselt steht der Control Mode nicht mehr auf Remote image

Cytron1980 commented 6 months ago

Das kann es tatsächlich sein. Habe die Tage den Modus wieder auf "maximalen eigenverbrauch" gestellt. Werde morgen nochmal zurück stellen und testen.

Cytron1980 commented 6 months ago

Gerade getestet. Im Modus "Nutzungszeit" klappt alles wie gewollt. Scheint also daher zu kommen.

Gotcha1980 commented 6 months ago

Genau weil beim Time of Use mode wird der Wechselrichter auf Remote gestellt. In der Setapp heißt der Modus Time of Use + Remote.

Mir ist das auch nur aufgefallen weil ich ebenfalls einen solaredge Wechselrichter habe und genau das gleiche Problem hatte. 😬

Cytron1980 commented 6 months ago

Also einfach nur die Zeiten raus nehmen und in dem Modus belassen?

Gotcha1980 commented 6 months ago

Entweder so, wobei ich glaube ohne Zeiten geht das nicht, oder über die Modbus Multi Integration den Control Mode händisch auf Remote stellen. Oder mit der setapp direkt am Wechselrichter das einstellen. Hier mal ein Bild aus Homeassistant von meinem Wechselrichter. image

Cytron1980 commented 6 months ago

Habe nur den ioBroker. Ich glaube dort ist das der Mode 4 beim Storage Control Mode... ich werde das mal testen. Aber eigentlich sollte EVCC unabhängig vom Batterie Management doch den Speicher sperren können (Mode auf 4 schreiben) so habe ich das vorher ja auch gelöst obwohl der Modus auf maximaler Eigenverbrauch stand, hat er den Mode 4 geschrieben und auch beibehalte.

Cytron1980 commented 6 months ago

Habe jetzt den Modus erstmal wieder aktiviert und die nutzungzeit nur auf Dezember und Januar begrenzt...somit sollte es erstmal funktionieren.

andig commented 6 months ago

Hier scheint im Template ja ein Hinweis zu fehlen, welcher Modus verwendet werden darf oder auch nicht. Was wäre das konkret? Ein PR wäre Klasse!

Cytron1980 commented 6 months ago

Hilf mir auf die Sprünge- PR?! Kann ich da weiterhelfen? Was bedeutet dies in dem Zusammenhang hier? VG

andig commented 6 months ago

Pull Request. Zur Ergänzung des SE Templates um den entsprechenden Hinweis.

Cytron1980 commented 6 months ago

Okay. Werde ich machen.

Edit: Ein PR zu erstellen scheint mir doch komplizierter als gedacht. Kann mir da jemand bei helfen bzw. einen erstellen? Sorry, ist für mich nicht tägliche Praxis mich auf Github zu bewegen...

StefanSchoof commented 6 months ago

Am einfachsten im Browser https://github.com/evcc-io/evcc/blob/master/templates/definition/meter/solaredge-hybrid.yaml öffnen und dann edit in place klicken. Dann Text anpassen und dann commit und pull request öffnen. Gibt unter https://docs.github.com/de/repositories/working-with-files/managing-files/editing-files eine Anleitung

Cytron1980 commented 6 months ago

Habe ich jetzt mal gemacht.hoffe das war so richtig.

andig commented 6 months ago

Ist drin- vielen Dank!