Active Battery Control FoxESS H3 MinSoC not changed back after charging is finished #16326

Open Gics78 opened 4 days ago

Gics78 commented 4 days ago

Describe the bug

Active Battery Control to protect the battery from discharge protection seem to work in setting the minimal SoC (MinSoc) to the current or prespecified value. But after charging is completed it is not reset to the original value. So the battery is essentially crippled because it will not discharge any further until I change the MinSoc manually. [site ] ERROR battery mode: read tcp 172.23.0.2:45672->192.168.178.8:502: i/o timeout

Steps to reproduce

  1. Beginn Charging 2.End charging
  2. Check MinSoc, set to current SoC and not the typical MinSoc ...

Configuration details

H3 10.0.E Firmware 2.01., Slave 1.03.; BMS 1.017

Log details

[ocpp ] TRACE 2024/09/25 19:58:59 handling incoming CALL [63200794-c46d-4772-ae13-dac67cbf4b13, MeterValues] from 60AH73B037AQ016
[ocpp ] TRACE 2024/09/25 19:58:59 sent CALL RESULT [63200794-c46d-4772-ae13-dac67cbf4b13] for 60AH73B037AQ016
[ocpp ] TRACE 2024/09/25 19:58:59 sent JSON message to 60AH73B037AQ016: [3,"63200794-c46d-4772-ae13-dac67cbf4b13",{}]
[lp-1 ] DEBUG 2024/09/25 19:59:02 set charge mode: now
[site ] DEBUG 2024/09/25 19:59:02 ----
[lp-1 ] DEBUG 2024/09/25 19:59:02 charge power: 0W
[lp-1 ] DEBUG 2024/09/25 19:59:02 charge currents: [0 0 0]A
[modbus] TRACE 2024/09/25 19:59:02 modbus: send 39 4e 00 00 00 06 01 03 79 1a 00 01
[modbus] TRACE 2024/09/25 19:59:02 modbus: recv 39 4e 00 00 00 05 01 03 02 00 00
[modbus] TRACE 2024/09/25 19:59:02 modbus: send 39 4f 00 00 00 06 01 03 79 1d 00 01
[modbus] TRACE 2024/09/25 19:59:02 modbus: recv 39 4f 00 00 00 05 01 03 02 00 00
[site ] DEBUG 2024/09/25 19:59:02 pv power: 0W
[modbus] TRACE 2024/09/25 19:59:02 modbus: send 39 50 00 00 00 06 01 03 79 3c 00 01
[modbus] TRACE 2024/09/25 19:59:02 modbus: recv 39 50 00 00 00 05 01 03 02 02 a4
[modbus] TRACE 2024/09/25 19:59:02 modbus: send 39 51 00 00 00 06 01 03 79 3e 00 01
[modbus] TRACE 2024/09/25 19:59:02 modbus: recv 39 51 00 00 00 05 01 03 02 00 5c
[site ] DEBUG 2024/09/25 19:59:02 battery soc: 92%
[site ] DEBUG 2024/09/25 19:59:02 battery power: 676W
[modbus] TRACE 2024/09/25 19:59:02 modbus: send 39 52 00 00 00 06 01 03 79 32 00 01
[modbus] TRACE 2024/09/25 19:59:02 modbus: recv 39 52 00 00 00 05 01 03 02 ff 3f
[modbus] TRACE 2024/09/25 19:59:02 modbus: send 39 53 00 00 00 06 01 03 79 33 00 01
[modbus] TRACE 2024/09/25 19:59:02 modbus: recv 39 53 00 00 00 05 01 03 02 00 31
[modbus] TRACE 2024/09/25 19:59:02 modbus: send 39 54 00 00 00 06 01 03 79 34 00 01
[modbus] TRACE 2024/09/25 19:59:02 modbus: recv 39 54 00 00 00 05 01 03 02 00 91
[site ] DEBUG 2024/09/25 19:59:02 grid meter: -1W
[modbus] TRACE 2024/09/25 19:59:02 modbus: send 39 55 00 00 00 06 01 03 7d 0c 00 02
[modbus] TRACE 2024/09/25 19:59:02 modbus: recv 39 55 00 00 00 07 01 03 04 00 00 e4 e8
[site ] DEBUG 2024/09/25 19:59:02 site power: 675W
[lp-1 ] DEBUG 2024/09/25 19:59:02 charge voltages: [232 233 234]V
[lp-1 ] DEBUG 2024/09/25 19:59:02 detected connected phases: 3p
[lp-1 ] DEBUG 2024/09/25 19:59:02 charge total import: 133.150kWh
[lp-1 ] DEBUG 2024/09/25 19:59:02 charger status: B
[ocpp ] TRACE 2024/09/25 19:59:02 enqueued CALL [3997912919, SetChargingProfile] for 60AH73B037AQ016
[ocpp ] TRACE 2024/09/25 19:59:02 dispatched request 3997912919 for 60AH73B037AQ016
[ocpp ] TRACE 2024/09/25 19:59:02 sent JSON message to 60AH73B037AQ016: [2,"3997912919","SetChargingProfile",{"connectorId":1,"csChargingProfiles":{"chargingProfileId":64,"stackLevel":9,"chargingProfilePurpose":"TxDefaultProfile","chargingProfileKind":"Absolute","chargingSchedule":{"startSchedule":"2024-09-25T17:59:02Z","chargingRateUnit":"A","chargingSchedulePeriod":[{"startPeriod":0,"limit":16}]}}}]
[ocpp ] TRACE 2024/09/25 19:59:02 started timeout timer for 60AH73B037AQ016
[ocpp ] TRACE 2024/09/25 19:59:03 received JSON message from 60AH73B037AQ016: [3,"3997912919",{"status":"Accepted"}]
[ocpp ] TRACE 2024/09/25 19:59:03 handling incoming CALL RESULT [3997912919] from 60AH73B037AQ016
[ocpp ] TRACE 2024/09/25 19:59:03 completed request 3997912919 for 60AH73B037AQ016
[lp-1 ] DEBUG 2024/09/25 19:59:03 max charge current: 16A
[site ] DEBUG 2024/09/25 19:59:03 ----
[lp-1 ] DEBUG 2024/09/25 19:59:03 charge power: 0W
[ocpp ] TRACE 2024/09/25 19:59:03 60AH73B037AQ016 ready to transmit again
[lp-1 ] DEBUG 2024/09/25 19:59:03 charge currents: [0 0 0]A
[modbus] TRACE 2024/09/25 19:59:03 modbus: send 39 56 00 00 00 06 01 03 79 1a 00 01
[ocpp ] TRACE 2024/09/25 19:59:03 timeout canceled for 60AH73B037AQ016
[modbus] TRACE 2024/09/25 19:59:03 modbus: recv 39 56 00 00 00 05 01 03 02 00 00
[modbus] TRACE 2024/09/25 19:59:03 modbus: send 39 57 00 00 00 06 01 03 79 1d 00 01
[modbus] TRACE 2024/09/25 19:59:03 modbus: recv 39 57 00 00 00 05 01 03 02 00 00
[site ] DEBUG 2024/09/25 19:59:03 pv power: 0W
[modbus] TRACE 2024/09/25 19:59:03 modbus: send 39 58 00 00 00 06 01 03 79 3c 00 01
[modbus] TRACE 2024/09/25 19:59:03 modbus: recv 39 58 00 00 00 05 01 03 02 02 a1
[modbus] TRACE 2024/09/25 19:59:03 modbus: send 39 59 00 00 00 06 01 03 79 3e 00 01
[modbus] TRACE 2024/09/25 19:59:03 modbus: recv 39 59 00 00 00 05 01 03 02 00 5c
[site ] DEBUG 2024/09/25 19:59:03 battery soc: 92%
[site ] DEBUG 2024/09/25 19:59:03 battery power: 673W
[modbus] TRACE 2024/09/25 19:59:03 modbus: send 39 5a 00 00 00 06 01 03 79 32 00 01
[modbus] TRACE 2024/09/25 19:59:03 modbus: recv 39 5a 00 00 00 05 01 03 02 ff 26
[modbus] TRACE 2024/09/25 19:59:03 modbus: send 39 5b 00 00 00 06 01 03 79 33 00 01
[modbus] TRACE 2024/09/25 19:59:03 modbus: recv 39 5b 00 00 00 05 01 03 02 00 34
[modbus] TRACE 2024/09/25 19:59:03 modbus: send 39 5c 00 00 00 06 01 03 79 34 00 01
[modbus] TRACE 2024/09/25 19:59:03 modbus: recv 39 5c 00 00 00 05 01 03 02 00 8c
[site ] DEBUG 2024/09/25 19:59:03 grid meter: 26W
[modbus] TRACE 2024/09/25 19:59:03 modbus: send 39 5d 00 00 00 06 01 03 7d 0c 00 02
[modbus] TRACE 2024/09/25 19:59:03 modbus: recv 39 5d 00 00 00 07 01 03 04 00 00 e4 e8
[site ] DEBUG 2024/09/25 19:59:03 site power: 699W
[lp-1 ] DEBUG 2024/09/25 19:59:03 charge voltages: [232 233 234]V
[lp-1 ] DEBUG 2024/09/25 19:59:03 detected connected phases: 3p
[lp-1 ] DEBUG 2024/09/25 19:59:03 charge total import: 133.150kWh
[lp-1 ] DEBUG 2024/09/25 19:59:03 charger status: B
[mqtt ] TRACE 2024/09/25 19:59:07 recv SoC_Genesis: '{"SoC_Display":87,"raw":"102E620105FFFB74210F012C01012C112210101010101145239A99E800006411240003E8107A400025AE000000000000260010111011AAAA"}'
[ocpp ] TRACE 2024/09/25 19:59:09 received JSON message from 60AH73B037AQ016: [2,"f8baa584-6e81-48d5-934d-d81ef86c1ada","MeterValues",{"connectorId":1,"transactionId":1727026609,"meterValue":[{"timestamp":"2024-09-25T17:59:09Z","sampledValue":[{"value":"232.19","context":"Sample.Periodic","format":"Raw","measurand":"Voltage","phase":"L1","unit":"V"},{"value":"233.45","context":"Sample.Periodic","format":"Raw","measurand":"Voltage","phase":"L2","unit":"V"},{"value":"233.80","context":"Sample.Periodic","format":"Raw","measurand":"Voltage","phase":"L3","unit":"V"},{"value":"0.00","context":"Sample.Periodic","format":"Raw","measurand":"Current.Import","phase":"L1","unit":"A"},{"value":"0.00","context":"Sample.Periodic","format":"Raw","measurand":"Current.Import","phase":"L2","unit":"A"},{"value":"0.00","context":"Sample.Periodic","format":"Raw","measurand":"Current.Import","phase":"L3","unit":"A"},{"value":"0","context":"Sample.Periodic","format":"Raw","measurand":"Power.Active.Import","unit":"W"},{"value":"133150","context":"Sample.Periodic","format":"Raw","measurand":"Energy.Active.Import.Register","unit":"Wh"}]}]}]
[ocpp ] TRACE 2024/09/25 19:59:09 handling incoming CALL [f8baa584-6e81-48d5-934d-d81ef86c1ada, MeterValues] from 60AH73B037AQ016
[ocpp ] TRACE 2024/09/25 19:59:09 sent CALL RESULT [f8baa584-6e81-48d5-934d-d81ef86c1ada] for 60AH73B037AQ016
[ocpp ] TRACE 2024/09/25 19:59:09 sent JSON message to 60AH73B037AQ016: [3,"f8baa584-6e81-48d5-934d-d81ef86c1ada",{}]
[ocpp ] TRACE 2024/09/25 19:59:12 received JSON message from 60AH73B037AQ016: [2,"16e3e0aa-8190-4d23-b372-d6a51ee99d88","StatusNotification",{"connectorId":1,"errorCode":"NoError","status":"Charging","timestamp":"2024-09-25T17:59:12Z"}]
[ocpp ] TRACE 2024/09/25 19:59:12 handling incoming CALL [16e3e0aa-8190-4d23-b372-d6a51ee99d88, StatusNotification] from 60AH73B037AQ016
[ocpp ] TRACE 2024/09/25 19:59:12 sent CALL RESULT [16e3e0aa-8190-4d23-b372-d6a51ee99d88] for 60AH73B037AQ016
[ocpp ] TRACE 2024/09/25 19:59:12 sent JSON message to 60AH73B037AQ016: [3,"16e3e0aa-8190-4d23-b372-d6a51ee99d88",{}]
[site ] DEBUG 2024/09/25 19:59:13 ----
[lp-1 ] DEBUG 2024/09/25 19:59:13 charge power: 0W
[lp-1 ] DEBUG 2024/09/25 19:59:13 charge currents: [0 0 0]A
[modbus] TRACE 2024/09/25 19:59:13 modbus: send 39 5e 00 00 00 06 01 03 79 1a 00 01
[modbus] TRACE 2024/09/25 19:59:13 modbus: recv 39 5e 00 00 00 05 01 03 02 00 00
[modbus] TRACE 2024/09/25 19:59:13 modbus: send 39 5f 00 00 00 06 01 03 79 1d 00 01
[modbus] TRACE 2024/09/25 19:59:13 modbus: recv 39 5f 00 00 00 05 01 03 02 00 00
[site ] DEBUG 2024/09/25 19:59:13 pv power: 0W
[modbus] TRACE 2024/09/25 19:59:13 modbus: send 39 60 00 00 00 06 01 03 79 3c 00 01
[modbus] TRACE 2024/09/25 19:59:13 modbus: recv 39 60 00 00 00 05 01 03 02 02 86
[modbus] TRACE 2024/09/25 19:59:13 modbus: send 39 61 00 00 00 06 01 03 79 3e 00 01
[modbus] TRACE 2024/09/25 19:59:13 modbus: recv 39 61 00 00 00 05 01 03 02 00 5c
[site ] DEBUG 2024/09/25 19:59:13 battery soc: 92%
[site ] DEBUG 2024/09/25 19:59:13 battery power: 646W
[modbus] TRACE 2024/09/25 19:59:13 modbus: send 39 62 00 00 00 06 01 03 79 32 00 01
[modbus] TRACE 2024/09/25 19:59:13 modbus: recv 39 62 00 00 00 05 01 03 02 ff 39
[modbus] TRACE 2024/09/25 19:59:13 modbus: send 39 63 00 00 00 06 01 03 79 33 00 01
[modbus] TRACE 2024/09/25 19:59:13 modbus: recv 39 63 00 00 00 05 01 03 02 00 36
[modbus] TRACE 2024/09/25 19:59:13 modbus: send 39 64 00 00 00 06 01 03 79 34 00 01
[modbus] TRACE 2024/09/25 19:59:13 modbus: recv 39 64 00 00 00 05 01 03 02 00 7d
[site ] DEBUG 2024/09/25 19:59:13 grid meter: 20W
[modbus] TRACE 2024/09/25 19:59:13 modbus: send 39 65 00 00 00 06 01 03 7d 0c 00 02
[modbus] TRACE 2024/09/25 19:59:13 modbus: recv 39 65 00 00 00 07 01 03 04 00 00 e4 e8
[site ] DEBUG 2024/09/25 19:59:13 site power: 666W
[lp-1 ] DEBUG 2024/09/25 19:59:13 charge voltages: [232 233 234]V
[lp-1 ] DEBUG 2024/09/25 19:59:13 detected connected phases: 3p
[lp-1 ] DEBUG 2024/09/25 19:59:13 charge total import: 133.150kWh
[lp-1 ] DEBUG 2024/09/25 19:59:13 charger status: C
[lp-1 ] DEBUG 2024/09/25 19:59:13 charge start energy: 133.150kWh
[lp-1 ] INFO 2024/09/25 19:59:13 start charging ->
[lp-1 ] DEBUG 2024/09/25 19:59:13 wake-up timer: stop
[db ] TRACE 2024/09/25 19:59:13 INSERT INTO `sessions` (`created`,`finished`,`loadpoint`,`identifier`,`vehicle`,`odometer`,`meter_start_kwh`,`meter_end_kwh`,`charged_kwh`,`charge_duration`,`solar_percentage`,`price`,`price_per_kwh`,`co2_per_kwh`) VALUES ("2024-09-25 19:59:13.524","0000-00-00 00:00:00","Garage","evcc","GV70e",NULL,133.15,NULL,0,NULL,NULL,NULL,NULL,NULL) RETURNING `id` 1 <nil>
[lp-1 ] DEBUG 2024/09/25 19:59:13 soc estimated: 87.00% (vehicle: 87.00%)
[lp-1 ] DEBUG 2024/09/25 19:59:13 vehicle soc: 87%
[ocpp ] TRACE 2024/09/25 19:59:19 received JSON message from 60AH73B037AQ016: [2,"641ec745-9f95-4731-9cdf-d183c18b9bf0","MeterValues",{"connectorId":1,"transactionId":1727026609,"meterValue":[{"timestamp":"2024-09-25T17:59:19Z","sampledValue":[{"value":"231.29","context":"Sample.Periodic","format":"Raw","measurand":"Voltage","phase":"L1","unit":"V"},{"value":"232.49","context":"Sample.Periodic","format":"Raw","measurand":"Voltage","phase":"L2","unit":"V"},{"value":"232.85","context":"Sample.Periodic","format":"Raw","measurand":"Voltage","phase":"L3","unit":"V"},{"value":"6.64","context":"Sample.Periodic","format":"Raw","measurand":"Current.Import","phase":"L1","unit":"A"},{"value":"6.42","context":"Sample.Periodic","format":"Raw","measurand":"Current.Import","phase":"L2","unit":"A"},{"value":"6.72","context":"Sample.Periodic","format":"Raw","measurand":"Current.Import","phase":"L3","unit":"A"},{"value":"4470","context":"Sample.Periodic","format":"Raw","measurand":"Power.Active.Import","unit":"W"},{"value":"133150","context":"Sample.Periodic","format":"Raw","measurand":"Energy.Active.Import.Register","unit":"Wh"}]}]}]
[ocpp ] TRACE 2024/09/25 19:59:19 handling incoming CALL [641ec745-9f95-4731-9cdf-d183c18b9bf0, MeterValues] from 60AH73B037AQ016
[ocpp ] TRACE 2024/09/25 19:59:19 sent CALL RESULT [641ec745-9f95-4731-9cdf-d183c18b9bf0] for 60AH73B037AQ016
[ocpp ] TRACE 2024/09/25 19:59:19 sent JSON message to 60AH73B037AQ016: [3,"641ec745-9f95-4731-9cdf-d183c18b9bf0",{}]
[ocpp ] TRACE 2024/09/25 19:59:21 received JSON message from 60AH73B037AQ016: [2,"d3cef1ce-a477-48a4-a915-c334d50c86e1","Heartbeat",{}]
[ocpp ] TRACE 2024/09/25 19:59:21 handling incoming CALL [d3cef1ce-a477-48a4-a915-c334d50c86e1, Heartbeat] from 60AH73B037AQ016
[ocpp ] TRACE 2024/09/25 19:59:21 sent CALL RESULT [d3cef1ce-a477-48a4-a915-c334d50c86e1] for 60AH73B037AQ016
[ocpp ] TRACE 2024/09/25 19:59:21 sent JSON message to 60AH73B037AQ016: [3,"d3cef1ce-a477-48a4-a915-c334d50c86e1",{"currentTime":"2024-09-25T17:59:21Z"}]
[site ] DEBUG 2024/09/25 19:59:23 ----
[lp-1 ] DEBUG 2024/09/25 19:59:23 charge power: 4470W
[lp-1 ] DEBUG 2024/09/25 19:59:23 charge currents: [6.64 6.42 6.72]A
[modbus] TRACE 2024/09/25 19:59:23 modbus: send 39 66 00 00 00 06 01 03 79 3e 00 01
[modbus] TRACE 2024/09/25 19:59:23 modbus: recv 39 66 00 00 00 05 01 03 02 00 5c
[modbus] TRACE 2024/09/25 19:59:23 modbus: send 39 67 00 00 00 06 01 06 a0 31 00 5c
[ocpp ] TRACE 2024/09/25 19:59:29 received JSON message from 60AH73B037AQ016: [2,"b794c099-6e6e-4add-92c4-24746024a979","MeterValues",{"connectorId":1,"transactionId":1727026609,"meterValue":[{"timestamp":"2024-09-25T17:59:29Z","sampledValue":[{"value":"229.93","context":"Sample.Periodic","format":"Raw","measurand":"Voltage","phase":"L1","unit":"V"},{"value":"230.92","context":"Sample.Periodic","format":"Raw","measurand":"Voltage","phase":"L2","unit":"V"},{"value":"231.56","context":"Sample.Periodic","format":"Raw","measurand":"Voltage","phase":"L3","unit":"V"},{"value":"15.29","context":"Sample.Periodic","format":"Raw","measurand":"Current.Import","phase":"L1","unit":"A"},{"value":"15.23","context":"Sample.Periodic","format":"Raw","measurand":"Current.Import","phase":"L2","unit":"A"},{"value":"15.35","context":"Sample.Periodic","format":"Raw","measurand":"Current.Import","phase":"L3","unit":"A"},{"value":"10500","context":"Sample.Periodic","format":"Raw","measurand":"Power.Active.Import","unit":"W"},{"value":"133180","context":"Sample.Periodic","format":"Raw","measurand":"Energy.Active.Import.Register","unit":"Wh"}]}]}]
[ocpp ] TRACE 2024/09/25 19:59:29 handling incoming CALL [b794c099-6e6e-4add-92c4-24746024a979, MeterValues] from 60AH73B037AQ016
[ocpp ] TRACE 2024/09/25 19:59:29 sent CALL RESULT [b794c099-6e6e-4add-92c4-24746024a979] for 60AH73B037AQ016
[ocpp ] TRACE 2024/09/25 19:59:29 sent JSON message to 60AH73B037AQ016: [3,"b794c099-6e6e-4add-92c4-24746024a979",{}]
[site ] ERROR 2024/09/25 19:59:33 battery mode: read tcp 172.23.0.2:34104->192.168.178.8:502: i/o timeout
[modbus] TRACE 2024/09/25 19:59:33 modbus: send 39 68 00 00 00 06 01 03 79 1a 00 01
[modbus] TRACE 2024/09/25 19:59:33 modbus: recv 39 68 00 00 00 05 01 03 02 00 00
[modbus] TRACE 2024/09/25 19:59:33 modbus: send 39 69 00 00 00 06 01 03 79 1d 00 01
[modbus] TRACE 2024/09/25 19:59:33 modbus: recv 39 69 00 00 00 05 01 03 02 00 00
[site ] DEBUG 2024/09/25 19:59:33 pv power: 0W
[modbus] TRACE 2024/09/25 19:59:33 modbus: send 39 6a 00 00 00 06 01 03 79 3c 00 01
[modbus] TRACE 2024/09/25 19:59:33 modbus: recv 39 6a 00 00 00 05 01 03 02 00 00
[modbus] TRACE 2024/09/25 19:59:33 modbus: send 39 6b 00 00 00 06 01 03 79 3e 00 01
[modbus] TRACE 2024/09/25 19:59:33 modbus: recv 39 6b 00 00 00 05 01 03 02 00 5c
[site ] DEBUG 2024/09/25 19:59:33 battery soc: 92%
[site ] DEBUG 2024/09/25 19:59:33 battery power: 0W
[modbus] TRACE 2024/09/25 19:59:33 modbus: send 39 6c 00 00 00 06 01 03 79 32 00 01
[modbus] TRACE 2024/09/25 19:59:33 modbus: recv 39 6c 00 00 00 05 01 03 02 f0 19
[modbus] TRACE 2024/09/25 19:59:33 modbus: send 39 6d 00 00 00 06 01 03 79 33 00 01
[modbus] TRACE 2024/09/25 19:59:33 modbus: recv 39 6d 00 00 00 05 01 03 02 f0 f3
[modbus] TRACE 2024/09/25 19:59:33 modbus: send 39 6e 00 00 00 06 01 03 79 34 00 01
[modbus] TRACE 2024/09/25 19:59:33 modbus: recv 39 6e 00 00 00 05 01 03 02 f1 3d
[site ] DEBUG 2024/09/25 19:59:33 grid meter: 11703W
[modbus] TRACE 2024/09/25 19:59:33 modbus: send 39 6f 00 00 00 06 01 03 7d 0c 00 02
[modbus] TRACE 2024/09/25 19:59:33 modbus: recv 39 6f 00 00 00 07 01 03 04 00 00 e4 e9
[site ] DEBUG 2024/09/25 19:59:33 site power: 11703W
[lp-1 ] DEBUG 2024/09/25 19:59:33 charge voltages: [230 231 232]V
[lp-1 ] DEBUG 2024/09/25 19:59:33 detected connected phases: 3p
[lp-1 ] DEBUG 2024/09/25 19:59:33 detected active phases: 3p
[lp-1 ] DEBUG 2024/09/25 19:59:33 charge total import: 133.180kWh
[lp-1 ] DEBUG 2024/09/25 19:59:33 charger status: C
[lp-1 ] DEBUG 2024/09/25 19:59:33 soc estimated: 87.03% (vehicle: 87.00%)
[lp-1 ] DEBUG 2024/09/25 19:59:33 vehicle soc: 87%
[site ] DEBUG 2024/09/25 19:59:33 ----
[lp-1 ] DEBUG 2024/09/25 19:59:33 charge power: 10500W
[lp-1 ] DEBUG 2024/09/25 19:59:33 charge currents: [15.3 15.2 15.3]A
[modbus] TRACE 2024/09/25 19:59:33 modbus: send 39 70 00 00 00 06 01 03 79 3e 00 01
[modbus] TRACE 2024/09/25 19:59:33 modbus: recv 39 70 00 00 00 05 01 03 02 00 5c
[modbus] TRACE 2024/09/25 19:59:33 modbus: send 39 71 00 00 00 06 01 06 a0 31 00 5c
[mqtt ] TRACE 2024/09/25 19:59:37 recv SoC_Genesis: '{"SoC_Display":87,"raw":"102E620105FFFB74210F012C00012C112210101010101145234999E800006410240003E8107A6D0025AE000000000000260010111011AAAA"}'
[ocpp ] TRACE 2024/09/25 19:59:39 received JSON message from 60AH73B037AQ016: [2,"cea5031a-8021-4002-901c-c2e51b47a943","MeterValues",{"connectorId":1,"transactionId":1727026609,"meterValue":[{"timestamp":"2024-09-25T17:59:40Z","sampledValue":[{"value":"229.91","context":"Sample.Periodic","format":"Raw","measurand":"Voltage","phase":"L1","unit":"V"},{"value":"230.91","context":"Sample.Periodic","format":"Raw","measurand":"Voltage","phase":"L2","unit":"V"},{"value":"231.45","context":"Sample.Periodic","format":"Raw","measurand":"Voltage","phase":"L3","unit":"V"},{"value":"15.26","context":"Sample.Periodic","format":"Raw","measurand":"Current.Import","phase":"L1","unit":"A"},{"value":"15.21","context":"Sample.Periodic","format":"Raw","measurand":"Current.Import","phase":"L2","unit":"A"},{"value":"15.34","context":"Sample.Periodic","format":"Raw","measurand":"Current.Import","phase":"L3","unit":"A"},{"value":"10490","context":"Sample.Periodic","format":"Raw","measurand":"Power.Active.Import","unit":"W"},{"value":"133220","context":"Sample.Periodic","format":"Raw","measurand":"Energy.Active.Import.Register","unit":"Wh"}]}]}]
[ocpp ] TRACE 2024/09/25 19:59:39 handling incoming CALL [cea5031a-8021-4002-901c-c2e51b47a943, MeterValues] from 60AH73B037AQ016
[ocpp ] TRACE 2024/09/25 19:59:39 sent CALL RESULT [cea5031a-8021-4002-901c-c2e51b47a943] for 60AH73B037AQ016
[ocpp ] TRACE 2024/09/25 19:59:39 sent JSON message to 60AH73B037AQ016: [3,"cea5031a-8021-4002-901c-c2e51b47a943",{}]
[db ] TRACE 2024/09/25 19:59:42 INSERT INTO `settings` (`key`,`value`) VALUES ("lp1.minCurrent","6"),("lp1.maxCurrent","16"),("lp1.phasesConfigured","3"),("adminPassword","$2a$10$jw6Q7BLbtkTUp2YwNjc7aetpQXS3xi1Lc8tCfjYuxFHfkRh877nvK"),("jwtSecretKey","ddaf99063f9ef1bd5d6f75c60e4109f39e2011fb8c2cf9cdfc77ced75dbee8a7"),("lp1.mode","now"),("lp1.smartCostLimit","0.22"),("batteryDischargeControl","true"),("prioritySoc","60"),("bufferSoc","85"),("bufferStartSoc","0"),("batteryGridChargeLimit","0.16") ON CONFLICT (`key`) DO UPDATE SET `value`=`excluded`.`value` 12 <nil>
[site ] ERROR 2024/09/25 19:59:43 battery mode: read tcp 172.23.0.2:50312->192.168.178.8:502: i/o timeout
[modbus] TRACE 2024/09/25 19:59:43 modbus: send 39 72 00 00 00 06 01 03 79 1a 00 01
[modbus] TRACE 2024/09/25 19:59:43 modbus: recv 39 72 00 00 00 05 01 03 02 00 00
[modbus] TRACE 2024/09/25 19:59:43 modbus: send 39 73 00 00 00 06 01 03 79 1d 00 01
[modbus] TRACE 2024/09/25 19:59:43 modbus: recv 39 73 00 00 00 05 01 03 02 00 00
[site ] DEBUG 2024/09/25 19:59:43 pv power: 0W
[modbus] TRACE 2024/09/25 19:59:43 modbus: send 39 74 00 00 00 06 01 03 79 3c 00 01
[modbus] TRACE 2024/09/25 19:59:43 modbus: recv 39 74 00 00 00 05 01 03 02 00 00
[modbus] TRACE 2024/09/25 19:59:43 modbus: send 39 75 00 00 00 06 01 03 79 3e 00 01
[modbus] TRACE 2024/09/25 19:59:44 modbus: recv 39 75 00 00 00 05 01 03 02 00 5c
[site ] DEBUG 2024/09/25 19:59:44 battery soc: 92%
[site ] DEBUG 2024/09/25 19:59:44 battery power: 0W
[modbus] TRACE 2024/09/25 19:59:44 modbus: send 39 76 00 00 00 06 01 03 79 32 00 01
[modbus] TRACE 2024/09/25 19:59:44 modbus: recv 39 76 00 00 00 05 01 03 02 f0 0d
[modbus] TRACE 2024/09/25 19:59:44 modbus: send 39 77 00 00 00 06 01 03 79 33 00 01
[modbus] TRACE 2024/09/25 19:59:44 modbus: recv 39 77 00 00 00 05 01 03 02 f0 f1
[modbus] TRACE 2024/09/25 19:59:44 modbus: send 39 78 00 00 00 06 01 03 79 34 00 01
[modbus] TRACE 2024/09/25 19:59:44 modbus: recv 39 78 00 00 00 05 01 03 02 f1 45
[site ] DEBUG 2024/09/25 19:59:44 grid meter: 11709W
[modbus] TRACE 2024/09/25 19:59:44 modbus: send 39 79 00 00 00 06 01 03 7d 0c 00 02
[modbus] TRACE 2024/09/25 19:59:44 modbus: recv 39 79 00 00 00 07 01 03 04 00 00 e4 e9
[site ] DEBUG 2024/09/25 19:59:44 site power: 11709W
[lp-1 ] DEBUG 2024/09/25 19:59:44 charge voltages: [230 231 231]V
[lp-1 ] DEBUG 2024/09/25 19:59:44 detected connected phases: 3p
[lp-1 ] DEBUG 2024/09/25 19:59:44 detected active phases: 3p
[lp-1 ] DEBUG 2024/09/25 19:59:44 charge total import: 133.220kWh
[lp-1 ] DEBUG 2024/09/25 19:59:44 charger status: C
[lp-1 ] DEBUG 2024/09/25 19:59:44 soc estimated: 87.08% (vehicle: 87.00%)
[lp-1 ] DEBUG 2024/09/25 19:59:44 vehicle soc: 87%
[site ] DEBUG 2024/09/25 19:59:44 ----
[lp-1 ] DEBUG 2024/09/25 19:59:44 charge power: 10490W
[lp-1 ] DEBUG 2024/09/25 19:59:44 charge currents: [15.3 15.2 15.3]A
[modbus] TRACE 2024/09/25 19:59:44 modbus: send 39 7a 00 00 00 06 01 03 79 3e 00 01
[modbus] TRACE 2024/09/25 19:59:44 modbus: recv 39 7a 00 00 00 05 01 03 02 00 5c
[modbus] TRACE 2024/09/25 19:59:44 modbus: send 39 7b 00 00 00 06 01 06 a0 31 00 5c
[ocpp ] TRACE 2024/09/25 19:59:49 received JSON message from 60AH73B037AQ016: [2,"4a3a35cd-fe08-4002-b907-fe27b81fb034","MeterValues",{"connectorId":1,"transactionId":1727026609,"meterValue":[{"timestamp":"2024-09-25T17:59:50Z","sampledValue":[{"value":"230.06","context":"Sample.Periodic","format":"Raw","measurand":"Voltage","phase":"L1","unit":"V"},{"value":"230.96","context":"Sample.Periodic","format":"Raw","measurand":"Voltage","phase":"L2","unit":"V"},{"value":"231.56","context":"Sample.Periodic","format":"Raw","measurand":"Voltage","phase":"L3","unit":"V"},{"value":"15.32","context":"Sample.Periodic","format":"Raw","measurand":"Current.Import","phase":"L1","unit":"A"},{"value":"15.25","context":"Sample.Periodic","format":"Raw","measurand":"Current.Import","phase":"L2","unit":"A"},{"value":"15.39","context":"Sample.Periodic","format":"Raw","measurand":"Current.Import","phase":"L3","unit":"A"},{"value":"10530","context":"Sample.Periodic","format":"Raw","measurand":"Power.Active.Import","unit":"W"},{"value":"133250","context":"Sample.Periodic","format":"Raw","measurand":"Energy.Active.Import.Register","unit":"Wh"}]}]}]
[ocpp ] TRACE 2024/09/25 19:59:49 handling incoming CALL [4a3a35cd-fe08-4002-b907-fe27b81fb034, MeterValues] from 60AH73B037AQ016
[ocpp ] TRACE 2024/09/25 19:59:49 sent CALL RESULT [4a3a35cd-fe08-4002-b907-fe27b81fb034] for 60AH73B037AQ016
[ocpp ] TRACE 2024/09/25 19:59:49 sent JSON message to 60AH73B037AQ016: [3,"4a3a35cd-fe08-4002-b907-fe27b81fb034",{}]
[site ] ERROR 2024/09/25 19:59:54 battery mode: read tcp 172.23.0.2:45672->192.168.178.8:502: i/o timeout
[modbus] TRACE 2024/09/25 19:59:54 modbus: send 39 7c 00 00 00 06 01 03 79 1a 00 01
[modbus] TRACE 2024/09/25 19:59:54 modbus: recv 39 7c 00 00 00 05 01 03 02 00 00
[modbus] TRACE 2024/09/25 19:59:54 modbus: send 39 7d 00 00 00 06 01 03 79 1d 00 01
[modbus] TRACE 2024/09/25 19:59:54 modbus: recv 39 7d 00 00 00 05 01 03 02 00 00
[site ] DEBUG 2024/09/25 19:59:54 pv power: 0W
[modbus] TRACE 2024/09/25 19:59:54 modbus: send 39 7e 00 00 00 06 01 03 79 3c 00 01
[modbus] TRACE 2024/09/25 19:59:54 modbus: recv 39 7e 00 00 00 05 01 03 02 00 00
[modbus] TRACE 2024/09/25 19:59:54 modbus: send 39 7f 00 00 00 06 01 03 79 3e 00 01
[modbus] TRACE 2024/09/25 19:59:54 modbus: recv 39 7f 00 00 00 05 01 03 02 00 5c
[site ] DEBUG 2024/09/25 19:59:54 battery soc: 92%
[site ] DEBUG 2024/09/25 19:59:54 battery power: 0W
[modbus] TRACE 2024/09/25 19:59:54 modbus: send 39 80 00 00 00 06 01 03 79 32 00 01
[modbus] TRACE 2024/09/25 19:59:54 modbus: recv 39 80 00 00 00 05 01 03 02 f0 1a
[modbus] TRACE 2024/09/25 19:59:54 modbus: send 39 81 00 00 00 06 01 03 79 33 00 01
[modbus] TRACE 2024/09/25 19:59:55 modbus: recv 39 81 00 00 00 05 01 03 02 f0 f6
[modbus] TRACE 2024/09/25 19:59:55 modbus: send 39 82 00 00 00 06 01 03 79 34 00 01
[modbus] TRACE 2024/09/25 19:59:55 modbus: recv 39 82 00 00 00 05 01 03 02 f1 39
[site ] DEBUG 2024/09/25 19:59:55 grid meter: 11703W
[modbus] TRACE 2024/09/25 19:59:55 modbus: send 39 83 00 00 00 06 01 03 7d 0c 00 02
[modbus] TRACE 2024/09/25 19:59:55 modbus: recv 39 83 00 00 00 07 01 03 04 00 00 e4 e9
[site ] DEBUG 2024/09/25 19:59:55 site power: 11703W
[lp-1 ] DEBUG 2024/09/25 19:59:55 charge voltages: [230 231 232]V
[lp-1 ] DEBUG 2024/09/25 19:59:55 detected connected phases: 3p
[lp-1 ] DEBUG 2024/09/25 19:59:55 detected active phases: 3p
[lp-1 ] DEBUG 2024/09/25 19:59:55 charge total import: 133.250kWh
[lp-1 ] DEBUG 2024/09/25 19:59:55 charger status: C
[lp-1 ] DEBUG 2024/09/25 19:59:55 soc estimated: 87.12% (vehicle: 87.00%)
[lp-1 ] DEBUG 2024/09/25 19:59:55 vehicle soc: 87%
[site ] DEBUG 2024/09/25 19:59:55 ----
[lp-1 ] DEBUG 2024/09/25 19:59:55 charge power: 10530W
[lp-1 ] DEBUG 2024/09/25 19:59:55 charge currents: [15.3 15.2 15.4]A
[modbus] TRACE 2024/09/25 19:59:55 modbus: send 39 84 00 00 00 06 01 03 79 3e 00 01
[modbus] TRACE 2024/09/25 19:59:55 modbus: recv 39 84 00 00 00 05 01 03 02 00 5c
[modbus] TRACE 2024/09/25 19:59:55 modbus: send 39 85 00 00 00 06 01 06 a0 31 00 5c
[ocpp ] TRACE 2024/09/25 19:59:59 received JSON message from 60AH73B037AQ016: [2,"379059e8-ebb1-4b4e-9981-5769779c70b2","MeterValues",{"connectorId":1,"transactionId":1727026609,"meterValue":[{"timestamp":"2024-09-25T18:00:00Z","sampledValue":[{"value":"230.06","context":"Sample.Periodic","format":"Raw","measurand":"Voltage","phase":"L1","unit":"V"},{"value":"230.83","context":"Sample.Periodic","format":"Raw","measurand":"Voltage","phase":"L2","unit":"V"},{"value":"231.48","context":"Sample.Periodic","format":"Raw","measurand":"Voltage","phase":"L3","unit":"V"},{"value":"15.30","context":"Sample.Periodic","format":"Raw","measurand":"Current.Import","phase":"L1","unit":"A"},{"value":"15.23","context":"Sample.Periodic","format":"Raw","measurand":"Current.Import","phase":"L2","unit":"A"},{"value":"15.36","context":"Sample.Periodic","format":"Raw","measurand":"Current.Import","phase":"L3","unit":"A"},{"value":"10510","context":"Sample.Periodic","format":"Raw","measurand":"Power.Active.Import","unit":"W"},{"value":"133250","context":"Sample.Periodic","format":"Raw","measurand":"Energy.Active.Import.Register","unit":"Wh"}]}]}]
[ocpp ] TRACE 2024/09/25 19:59:59 handling incoming CALL [379059e8-ebb1-4b4e-9981-5769779c70b2, MeterValues] from 60AH73B037AQ016
[ocpp ] TRACE 2024/09/25 19:59:59 sent CALL RESULT [379059e8-ebb1-4b4e-9981-5769779c70b2] for 60AH73B037AQ016
[ocpp ] TRACE 2024/09/25 19:59:59 sent JSON message to 60AH73B037AQ016: [3,"379059e8-ebb1-4b4e-9981-5769779c70b2",{}]
[site ] ERROR 2024/09/25 20:00:05 battery mode: read tcp 172.23.0.2:48446->192.168.178.8:502: i/o timeout
[modbus] TRACE 2024/09/25 20:00:05 modbus: send 39 86 00 00 00 06 01 03 79 1a 00 01
[modbus] TRACE 2024/09/25 20:00:05 modbus: recv 39 86 00 00 00 05 01 03 02 00 00
[modbus] TRACE 2024/09/25 20:00:05 modbus: send 39 87 00 00 00 06 01 03 79 1d 00 01
[modbus] TRACE 2024/09/25 20:00:05 modbus: recv 39 87 00 00 00 05 01 03 02 00 00
[site ] DEBUG 2024/09/25 20:00:05 pv power: 0W
[modbus] TRACE 2024/09/25 20:00:05 modbus: send 39 88 00 00 00 06 01 03 79 3c 00 01
[modbus] TRACE 2024/09/25 20:00:05 modbus: recv 39 88 00 00 00 05 01 03 02 00 00
[modbus] TRACE 2024/09/25 20:00:05 modbus: send 39 89 00 00 00 06 01 03 79 3e 00 01
[modbus] TRACE 2024/09/25 20:00:05 modbus: recv 39 89 00 00 00 05 01 03 02 00 5c
[site ] DEBUG 2024/09/25 20:00:05 battery soc: 92%
[site ] DEBUG 2024/09/25 20:00:05 battery power: 0W
[modbus] TRACE 2024/09/25 20:00:05 modbus: send 39 8a 00 00 00 06 01 03 79 32 00 01
[modbus] TRACE 2024/09/25 20:00:05 modbus: recv 39 8a 00 00 00 05 01 03 02 f0 23
[modbus] TRACE 2024/09/25 20:00:05 modbus: send 39 8b 00 00 00 06 01 03 79 33 00 01
[modbus] TRACE 2024/09/25 20:00:05 modbus: recv 39 8b 00 00 00 05 01 03 02 f0 f6
[modbus] TRACE 2024/09/25 20:00:05 modbus: send 39 8c 00 00 00 06 01 03 79 34 00 01
[modbus] TRACE 2024/09/25 20:00:05 modbus: recv 39 8c 00 00 00 05 01 03 02 f1 3e
[site ] DEBUG 2024/09/25 20:00:05 grid meter: 11689W
[modbus] TRACE 2024/09/25 20:00:05 modbus: send 39 8d 00 00 00 06 01 03 7d 0c 00 02
[modbus] TRACE 2024/09/25 20:00:05 modbus: recv 39 8d 00 00 00 07 01 03 04 00 00 e4 ea
[site ] DEBUG 2024/09/25 20:00:05 site power: 11689W
[lp-1 ] DEBUG 2024/09/25 20:00:05 charge voltages: [230 231 231]V
[lp-1 ] DEBUG 2024/09/25 20:00:05 detected connected phases: 3p
[lp-1 ] DEBUG 2024/09/25 20:00:05 detected active phases: 3p
[lp-1 ] DEBUG 2024/09/25 20:00:05 charge total import: 133.250kWh
[lp-1 ] DEBUG 2024/09/25 20:00:05 charger status: C
[lp-1 ] DEBUG 2024/09/25 20:00:05 soc estimated: 87.12% (vehicle: 87.00%)
[lp-1 ] DEBUG 2024/09/25 20:00:05 vehicle soc: 87%
[site ] DEBUG 2024/09/25 20:00:05 ----
[lp-1 ] DEBUG 2024/09/25 20:00:05 charge power: 10510W
[lp-1 ] DEBUG 2024/09/25 20:00:05 charge currents: [15.3 15.2 15.4]A
[modbus] TRACE 2024/09/25 20:00:05 modbus: send 39 8e 00 00 00 06 01 03 79 3e 00 01
[modbus] TRACE 2024/09/25 20:00:06 modbus: recv 39 8e 00 00 00 05 01 03 02 00 5c
[modbus] TRACE 2024/09/25 20:00:06 modbus: send 39 8f 00 00 00 06 01 06 a0 31 00 5c
[mqtt ] TRACE 2024/09/25 20:00:07 recv SoC_Genesis: '{"SoC_Display":87,"raw":"102E620105FFFB74210F012C00012C112210101010101145234999E800006410240003E8107A6D0025AE000000000000260010111011AAAA"}'
[ocpp ] TRACE 2024/09/25 20:00:09 received JSON message from 60AH73B037AQ016: [2,"62e244bd-bd1a-4e0c-9a3c-acb4507f0903","MeterValues",{"connectorId":1,"transactionId":1727026609,"meterValue":[{"timestamp":"2024-09-25T18:00:10Z","sampledValue":[{"value":"230.10","context":"Sample.Periodic","format":"Raw","measurand":"Voltage","phase":"L1","unit":"V"},{"value":"230.89","context":"Sample.Periodic","format":"Raw","measurand":"Voltage","phase":"L2","unit":"V"},{"value":"231.55","context":"Sample.Periodic","format":"Raw","measurand":"Voltage","phase":"L3","unit":"V"},{"value":"15.30","context":"Sample.Periodic","format":"Raw","measurand":"Current.Import","phase":"L1","unit":"A"},{"value":"15.23","context":"Sample.Periodic","format":"Raw","measurand":"Current.Import","phase":"L2","unit":"A"},{"value":"15.36","context":"Sample.Periodic","format":"Raw","measurand":"Current.Import","phase":"L3","unit":"A"},{"value":"10510","context":"Sample.Periodic","format":"Raw","measurand":"Power.Active.Import","unit":"W"},{"value":"133290","context":"Sample.Periodic","format":"Raw","measurand":"Energy.Active.Import.Register","unit":"Wh"}]}]}]
[ocpp ] TRACE 2024/09/25 20:00:09 handling incoming CALL [62e244bd-bd1a-4e0c-9a3c-acb4507f0903, MeterValues] from 60AH73B037AQ016
[ocpp ] TRACE 2024/09/25 20:00:09 sent CALL RESULT [62e244bd-bd1a-4e0c-9a3c-acb4507f0903] for 60AH73B037AQ016
[ocpp ] TRACE 2024/09/25 20:00:09 sent JSON message to 60AH73B037AQ016: [3,"62e244bd-bd1a-4e0c-9a3c-acb4507f0903",{}]
[site ] ERROR 2024/09/25 20:00:16 battery mode: read tcp 172.23.0.2:38646->192.168.178.8:502: i/o timeout
[modbus] TRACE 2024/09/25 20:00:16 modbus: send 39 90 00 00 00 06 01 03 79 1a 00 01
[modbus] TRACE 2024/09/25 20:00:16 modbus: recv 39 90 00 00 00 05 01 03 02 00 00
[modbus] TRACE 2024/09/25 20:00:16 modbus: send 39 91 00 00 00 06 01 03 79 1d 00 01
[modbus] TRACE 2024/09/25 20:00:16 modbus: recv 39 91 00 00 00 05 01 03 02 00 00
[site ] DEBUG 2024/09/25 20:00:16 pv power: 0W
[modbus] TRACE 2024/09/25 20:00:16 modbus: send 39 92 00 00 00 06 01 03 79 3c 00 01
[modbus] TRACE 2024/09/25 20:00:16 modbus: recv 39 92 00 00 00 05 01 03 02 00 00
[modbus] TRACE 2024/09/25 20:00:16 modbus: send 39 93 00 00 00 06 01 03 79 3e 00 01
[modbus] TRACE 2024/09/25 20:00:16 modbus: recv 39 93 00 00 00 05 01 03 02 00 5c
[site ] DEBUG 2024/09/25 20:00:16 battery soc: 92%
[site ] DEBUG 2024/09/25 20:00:16 battery power: 0W
[modbus] TRACE 2024/09/25 20:00:16 modbus: send 39 94 00 00 00 06 01 03 79 32 00 01
[modbus] TRACE 2024/09/25 20:00:16 modbus: recv 39 94 00 00 00 05 01 03 02 f0 33
[modbus] TRACE 2024/09/25 20:00:16 modbus: send 39 95 00 00 00 06 01 03 79 33 00 01
[modbus] TRACE 2024/09/25 20:00:16 modbus: recv 39 95 00 00 00 05 01 03 02 f0 fd
[modbus] TRACE 2024/09/25 20:00:16 modbus: send 39 96 00 00 00 06 01 03 79 34 00 01
[modbus] TRACE 2024/09/25 20:00:16 modbus: recv 39 96 00 00 00 05 01 03 02 f1 39
[site ] DEBUG 2024/09/25 20:00:16 grid meter: 11671W
[modbus] TRACE 2024/09/25 20:00:16 modbus: send 39 97 00 00 00 06 01 03 7d 0c 00 02
[modbus] TRACE 2024/09/25 20:00:16 modbus: recv 39 97 00 00 00 07 01 03 04 00 00 e4 ea
[site ] DEBUG 2024/09/25 20:00:16 site power: 11671W
[lp-1 ] DEBUG 2024/09/25 20:00:16 charge voltages: [230 231 232]V
[lp-1 ] DEBUG 2024/09/25 20:00:16 detected connected phases: 3p
[lp-1 ] DEBUG 2024/09/25 20:00:16 detected active phases: 3p
[lp-1 ] DEBUG 2024/09/25 20:00:16 charge total import: 133.290kWh
[lp-1 ] DEBUG 2024/09/25 20:00:16 charger status: C
[lp-1 ] DEBUG 2024/09/25 20:00:16 soc estimated: 87.16% (vehicle: 87.00%)
[lp-1 ] DEBUG 2024/09/25 20:00:16 vehicle soc: 87%
[site ] DEBUG 2024/09/25 20:00:16 ----
[lp-1 ] DEBUG 2024/09/25 20:00:16 charge power: 10510W
[lp-1 ] DEBUG 2024/09/25 20:00:16 charge currents: [15.3 15.2 15.4]A
[modbus] TRACE 2024/09/25 20:00:16 modbus: send 39 98 00 00 00 06 01 03 79 3e 00 01
[modbus] TRACE 2024/09/25 20:00:16 modbus: recv 39 98 00 00 00 05 01 03 02 00 5c
[modbus] TRACE 2024/09/25 20:00:16 modbus: send 39 99 00 00 00 06 01 06 a0 31 00 5c
[lp-1 ] DEBUG 2024/09/25 20:00:19 set charge mode: off
[ocpp ] TRACE 2024/09/25 20:00:20 received JSON message from 60AH73B037AQ016: [2,"67b9913a-8fd9-4bed-a0c2-989fb83ba46e","MeterValues",{"connectorId":1,"transactionId":1727026609,"meterValue":[{"timestamp":"2024-09-25T18:00:20Z","sampledValue":[{"value":"230.08","context":"Sample.Periodic","format":"Raw","measurand":"Voltage","phase":"L1","unit":"V"},{"value":"230.99","context":"Sample.Periodic","format":"Raw","measurand":"Voltage","phase":"L2","unit":"V"},{"value":"231.57","context":"Sample.Periodic","format":"Raw","measurand":"Voltage","phase":"L3","unit":"V"},{"value":"15.30","context":"Sample.Periodic","format":"Raw","measurand":"Current.Import","phase":"L1","unit":"A"},{"value":"15.22","context":"Sample.Periodic","format":"Raw","measurand":"Current.Import","phase":"L2","unit":"A"},{"value":"15.35","context":"Sample.Periodic","format":"Raw","measurand":"Current.Import","phase":"L3","unit":"A"},{"value":"10510","context":"Sample.Periodic","format":"Raw","measurand":"Power.Active.Import","unit":"W"},{"value":"133330","context":"Sample.Periodic","format":"Raw","measurand":"Energy.Active.Import.Register","unit":"Wh"}]}]}]
[ocpp ] TRACE 2024/09/25 20:00:20 handling incoming CALL [67b9913a-8fd9-4bed-a0c2-989fb83ba46e, MeterValues] from 60AH73B037AQ016
[ocpp ] TRACE 2024/09/25 20:00:20 sent CALL RESULT [67b9913a-8fd9-4bed-a0c2-989fb83ba46e] for 60AH73B037AQ016
[ocpp ] TRACE 2024/09/25 20:00:20 sent JSON message to 60AH73B037AQ016: [3,"67b9913a-8fd9-4bed-a0c2-989fb83ba46e",{}]
[ocpp ] TRACE 2024/09/25 20:00:21 received JSON message from 60AH73B037AQ016: [2,"48bde596-b90d-47b9-87bc-dc99492cc31a","Heartbeat",{}]
[ocpp ] TRACE 2024/09/25 20:00:21 handling incoming CALL [48bde596-b90d-47b9-87bc-dc99492cc31a, Heartbeat] from 60AH73B037AQ016
[ocpp ] TRACE 2024/09/25 20:00:21 sent CALL RESULT [48bde596-b90d-47b9-87bc-dc99492cc31a] for 60AH73B037AQ016
[ocpp ] TRACE 2024/09/25 20:00:21 sent JSON message to 60AH73B037AQ016: [3,"48bde596-b90d-47b9-87bc-dc99492cc31a",{"currentTime":"2024-09-25T18:00:21Z"}]
[site ] ERROR 2024/09/25 20:00:26 battery mode: read tcp 172.23.0.2:60170->192.168.178.8:502: i/o timeout
[modbus] TRACE 2024/09/25 20:00:26 modbus: send 39 9a 00 00 00 06 01 03 79 1a 00 01
[modbus] TRACE 2024/09/25 20:00:26 modbus: recv 39 9a 00 00 00 05 01 03 02 00 00
[modbus] TRACE 2024/09/25 20:00:26 modbus: send 39 9b 00 00 00 06 01 03 79 1d 00 01
[modbus] TRACE 2024/09/25 20:00:26 modbus: recv 39 9b 00 00 00 05 01 03 02 00 00
[site ] DEBUG 2024/09/25 20:00:26 pv power: 0W
[modbus] TRACE 2024/09/25 20:00:26 modbus: send 39 9c 00 00 00 06 01 03 79 3c 00 01
[modbus] TRACE 2024/09/25 20:00:26 modbus: recv 39 9c 00 00 00 05 01 03 02 00 00
[modbus] TRACE 2024/09/25 20:00:26 modbus: send 39 9d 00 00 00 06 01 03 79 3e 00 01
[modbus] TRACE 2024/09/25 20:00:27 modbus: recv 39 9d 00 00 00 05 01 03 02 00 5c
[site ] DEBUG 2024/09/25 20:00:27 battery soc: 92%
[site ] DEBUG 2024/09/25 20:00:27 battery power: 0W
[modbus] TRACE 2024/09/25 20:00:27 modbus: send 39 9e 00 00 00 06 01 03 79 32 00 01
[modbus] TRACE 2024/09/25 20:00:27 modbus: recv 39 9e 00 00 00 05 01 03 02 f0 1c
[modbus] TRACE 2024/09/25 20:00:27 modbus: send 39 9f 00 00 00 06 01 03 79 33 00 01
[modbus] TRACE 2024/09/25 20:00:27 modbus: recv 39 9f 00 00 00 05 01 03 02 f0 f5
[modbus] TRACE 2024/09/25 20:00:27 modbus: send 39 a0 00 00 00 06 01 03 79 34 00 01
[modbus] TRACE 2024/09/25 20:00:27 modbus: recv 39 a0 00 00 00 05 01 03 02 f1 1e
[site ] DEBUG 2024/09/25 20:00:27 grid meter: 11729W
[modbus] TRACE 2024/09/25 20:00:27 modbus: send 39 a1 00 00 00 06 01 03 7d 0c 00 02
[modbus] TRACE 2024/09/25 20:00:27 modbus: recv 39 a1 00 00 00 07 01 03 04 00 00 e4 ea
[site ] DEBUG 2024/09/25 20:00:27 site power: 11729W
[lp-1 ] DEBUG 2024/09/25 20:00:27 charge voltages: [230 231 232]V
[lp-1 ] DEBUG 2024/09/25 20:00:27 detected connected phases: 3p
[lp-1 ] DEBUG 2024/09/25 20:00:27 detected active phases: 3p
[lp-1 ] DEBUG 2024/09/25 20:00:27 charge total import: 133.330kWh
[lp-1 ] DEBUG 2024/09/25 20:00:27 charger status: C
[lp-1 ] DEBUG 2024/09/25 20:00:27 soc estimated: 87.21% (vehicle: 87.00%)
[lp-1 ] DEBUG 2024/09/25 20:00:27 vehicle soc: 87%
[ocpp ] TRACE 2024/09/25 20:00:27 enqueued CALL [2598597378, SetChargingProfile] for 60AH73B037AQ016
[ocpp ] TRACE 2024/09/25 20:00:27 dispatched request 2598597378 for 60AH73B037AQ016
[ocpp ] TRACE 2024/09/25 20:00:27 sent JSON message to 60AH73B037AQ016: [2,"2598597378","SetChargingProfile",{"connectorId":1,"csChargingProfiles":{"chargingProfileId":64,"stackLevel":9,"chargingProfilePurpose":"TxDefaultProfile","chargingProfileKind":"Absolute","chargingSchedule":{"startSchedule":"2024-09-25T18:00:27Z","chargingRateUnit":"A","chargingSchedulePeriod":[{"startPeriod":0,"limit":0}]}}}]
[ocpp ] TRACE 2024/09/25 20:00:27 started timeout timer for 60AH73B037AQ016
[ocpp ] TRACE 2024/09/25 20:00:27 received JSON message from 60AH73B037AQ016: [3,"2598597378",{"status":"Accepted"}]
[ocpp ] TRACE 2024/09/25 20:00:27 handling incoming CALL RESULT [2598597378] from 60AH73B037AQ016
[ocpp ] TRACE 2024/09/25 20:00:27 completed request 2598597378 for 60AH73B037AQ016
[lp-1 ] DEBUG 2024/09/25 20:00:27 charger disable
[ocpp ] TRACE 2024/09/25 20:00:27 60AH73B037AQ016 ready to transmit again
[lp-1 ] DEBUG 2024/09/25 20:00:27 wake-up timer: stop
[site ] DEBUG 2024/09/25 20:00:27 ----
[lp-1 ] DEBUG 2024/09/25 20:00:27 charge power: 10510W
[ocpp ] TRACE 2024/09/25 20:00:27 timeout canceled for 60AH73B037AQ016
[lp-1 ] DEBUG 2024/09/25 20:00:27 charge currents: [15.3 15.2 15.3]A
[modbus] TRACE 2024/09/25 20:00:27 modbus: send 39 a2 00 00 00 06 01 03 79 1a 00 01
[modbus] TRACE 2024/09/25 20:00:27 modbus: recv 39 a2 00 00 00 05 01 03 02 00 00
[modbus] TRACE 2024/09/25 20:00:27 modbus: send 39 a3 00 00 00 06 01 03 79 1d 00 01
[ocpp ] TRACE 2024/09/25 20:00:27 received JSON message from 60AH73B037AQ016: [2,"a0b2fff2-49c1-4683-8a1d-72eba6364709","StatusNotification",{"connectorId":1,"errorCode":"NoError","status":"SuspendedEVSE","timestamp":"2024-09-25T18:00:28Z"}]
[ocpp ] TRACE 2024/09/25 20:00:27 handling incoming CALL [a0b2fff2-49c1-4683-8a1d-72eba6364709, StatusNotification] from 60AH73B037AQ016
[ocpp ] TRACE 2024/09/25 20:00:27 sent CALL RESULT [a0b2fff2-49c1-4683-8a1d-72eba6364709] for 60AH73B037AQ016
[ocpp ] TRACE 2024/09/25 20:00:27 sent JSON message to 60AH73B037AQ016: [3,"a0b2fff2-49c1-4683-8a1d-72eba6364709",{}]
[modbus] TRACE 2024/09/25 20:00:27 modbus: recv 39 a3 00 00 00 05 01 03 02 00 00
[site ] DEBUG 2024/09/25 20:00:27 pv power: 0W
[modbus] TRACE 2024/09/25 20:00:27 modbus: send 39 a4 00 00 00 06 01 03 79 3c 00 01
[modbus] TRACE 2024/09/25 20:00:27 modbus: recv 39 a4 00 00 00 05 01 03 02 00 00
[modbus] TRACE 2024/09/25 20:00:27 modbus: send 39 a5 00 00 00 06 01 03 79 3e 00 01
[modbus] TRACE 2024/09/25 20:00:28 modbus: recv 39 a5 00 00 00 05 01 03 02 00 5c
[site ] DEBUG 2024/09/25 20:00:28 battery soc: 92%
[site ] DEBUG 2024/09/25 20:00:28 battery power: 0W
[modbus] TRACE 2024/09/25 20:00:28 modbus: send 39 a6 00 00 00 06 01 03 79 32 00 01
[modbus] TRACE 2024/09/25 20:00:28 modbus: recv 39 a6 00 00 00 05 01 03 02 f0 25
[modbus] TRACE 2024/09/25 20:00:28 modbus: send 39 a7 00 00 00 06 01 03 79 33 00 01
[modbus] TRACE 2024/09/25 20:00:28 modbus: recv 39 a7 00 00 00 05 01 03 02 f3 73
[modbus] TRACE 2024/09/25 20:00:28 modbus: send 39 a8 00 00 00 06 01 03 79 34 00 01
[modbus] TRACE 2024/09/25 20:00:28 modbus: recv 39 a8 00 00 00 05 01 03 02 f3 b6
[site ] DEBUG 2024/09/25 20:00:28 grid meter: 10418W
[modbus] TRACE 2024/09/25 20:00:28 modbus: send 39 a9 00 00 00 06 01 03 7d 0c 00 02
[modbus] TRACE 2024/09/25 20:00:28 modbus: recv 39 a9 00 00 00 07 01 03 04 00 00 e4 ea
[site ] DEBUG 2024/09/25 20:00:28 site power: 10418W
[lp-1 ] DEBUG 2024/09/25 20:00:28 charge voltages: [230 231 232]V
[lp-1 ] DEBUG 2024/09/25 20:00:28 detected connected phases: 3p
[lp-1 ] DEBUG 2024/09/25 20:00:28 detected active phases: 3p
[lp-1 ] DEBUG 2024/09/25 20:00:28 charge total import: 133.330kWh
[lp-1 ] DEBUG 2024/09/25 20:00:28 charger status: B
[lp-1 ] DEBUG 2024/09/25 20:00:28 charge final energy: 0.180kWh
[lp-1 ] INFO 2024/09/25 20:00:28 stop charging <-
[lp-1 ] DEBUG 2024/09/25 20:00:28 charge total import: 133.330kWh
[db ] TRACE 2024/09/25 20:00:28 UPDATE `sessions` SET `created`="2024-09-25 19:59:13.524",`finished`="2024-09-25 20:00:28.275",`loadpoint`="Garage",`identifier`="evcc",`vehicle`="GV70e",`odometer`=NULL,`meter_start_kwh`=133.15,`meter_end_kwh`=133.33,`charged_kwh`=0.18000000000000682,`charge_duration`="1m15s",`solar_percentage`=0,`price`=0.06472800000000174,`price_per_kwh`=0.35959999999999603,`co2_per_kwh`=182.00000000000475 WHERE `id` = 24 1 <nil>
[lp-1 ] DEBUG 2024/09/25 20:00:28 soc estimated: 87.21% (vehicle: 87.00%)
[lp-1 ] DEBUG 2024/09/25 20:00:28 vehicle soc: 87%
[site ] DEBUG 2024/09/25 20:00:28 ----
[lp-1 ] DEBUG 2024/09/25 20:00:28 charge power: 10510W
[lp-1 ] DEBUG 2024/09/25 20:00:28 charge currents: [15.3 15.2 15.3]A
[modbus] TRACE 2024/09/25 20:00:28 modbus: send 39 aa 00 00 00 06 01 03 79 1a 00 01
[modbus] TRACE 2024/09/25 20:00:28 modbus: recv 39 aa 00 00 00 05 01 03 02 00 00
[modbus] TRACE 2024/09/25 20:00:28 modbus: send 39 ab 00 00 00 06 01 03 79 1d 00 01
[modbus] TRACE 2024/09/25 20:00:28 modbus: recv 39 ab 00 00 00 05 01 03 02 00 00
[site ] DEBUG 2024/09/25 20:00:28 pv power: 0W
[modbus] TRACE 2024/09/25 20:00:28 modbus: send 39 ac 00 00 00 06 01 03 79 3c 00 01
[modbus] TRACE 2024/09/25 20:00:28 modbus: recv 39 ac 00 00 00 05 01 03 02 00 00
[modbus] TRACE 2024/09/25 20:00:28 modbus: send 39 ad 00 00 00 06 01 03 79 3e 00 01
[modbus] TRACE 2024/09/25 20:00:28 modbus: recv 39 ad 00 00 00 05 01 03 02 00 5c
[site ] DEBUG 2024/09/25 20:00:28 battery soc: 92%
[site ] DEBUG 2024/09/25 20:00:28 battery power: 0W
[modbus] TRACE 2024/09/25 20:00:28 modbus: send 39 ae 00 00 00 06 01 03 79 32 00 01
[modbus] TRACE 2024/09/25 20:00:28 modbus: recv 39 ae 00 00 00 05 01 03 02 f6 bf
[modbus] TRACE 2024/09/25 20:00:28 modbus: send 39 af 00 00 00 06 01 03 79 33 00 01
[modbus] TRACE 2024/09/25 20:00:28 modbus: recv 39 af 00 00 00 05 01 03 02 fb b2
[modbus] TRACE 2024/09/25 20:00:28 modbus: send 39 b0 00 00 00 06 01 03 79 34 00 01
[modbus] TRACE 2024/09/25 20:00:28 modbus: recv 39 b0 00 00 00 05 01 03 02 fb fa
[site ] DEBUG 2024/09/25 20:00:28 grid meter: 4501W
[modbus] TRACE 2024/09/25 20:00:28 modbus: send 39 b1 00 00 00 06 01 03 7d 0c 00 02
[modbus] TRACE 2024/09/25 20:00:28 modbus: recv 39 b1 00 00 00 07 01 03 04 00 00 e4 ea
[site ] DEBUG 2024/09/25 20:00:28 site power: 4501W
[lp-1 ] DEBUG 2024/09/25 20:00:28 charge voltages: [230 231 232]V
[lp-1 ] DEBUG 2024/09/25 20:00:28 detected connected phases: 3p
[lp-1 ] DEBUG 2024/09/25 20:00:28 charge total import: 133.330kWh
[lp-1 ] DEBUG 2024/09/25 20:00:28 charger status: B
[ocpp ] TRACE 2024/09/25 20:00:30 received JSON message from 60AH73B037AQ016: [2,"718be7e8-05cd-4f8e-b230-fca45e6a1b5d","MeterValues",{"connectorId":1,"transactionId":1727026609,"meterValue":[{"timestamp":"2024-09-25T18:00:30Z","sampledValue":[{"value":"232.33","context":"Sample.Periodic","format":"Raw","measurand":"Voltage","phase":"L1","unit":"V"},{"value":"233.35","context":"Sample.Periodic","format":"Raw","measurand":"Voltage","phase":"L2","unit":"V"},{"value":"233.88","context":"Sample.Periodic","format":"Raw","measurand":"Voltage","phase":"L3","unit":"V"},{"value":"0.57","context":"Sample.Periodic","format":"Raw","measurand":"Current.Import","phase":"L1","unit":"A"},{"value":"0.56","context":"Sample.Periodic","format":"Raw","measurand":"Current.Import","phase":"L2","unit":"A"},{"value":"0.63","context":"Sample.Periodic","format":"Raw","measurand":"Current.Import","phase":"L3","unit":"A"},{"value":"160","context":"Sample.Periodic","format":"Raw","measurand":"Power.Active.Import","unit":"W"},{"value":"133360","context":"Sample.Periodic","format":"Raw","measurand":"Energy.Active.Import.Register","unit":"Wh"}]}]}]
[ocpp ] TRACE 2024/09/25 20:00:30 handling incoming CALL [718be7e8-05cd-4f8e-b230-fca45e6a1b5d, MeterValues] from 60AH73B037AQ016
[ocpp ] TRACE 2024/09/25 20:00:30 sent CALL RESULT [718be7e8-05cd-4f8e-b230-fca45e6a1b5d] for 60AH73B037AQ016
[ocpp ] TRACE 2024/09/25 20:00:30 sent JSON message to 60AH73B037AQ016: [3,"718be7e8-05cd-4f8e-b230-fca45e6a1b5d",{}]
[site ] DEBUG 2024/09/25 20:00:33 ----
[lp-1 ] DEBUG 2024/09/25 20:00:33 charge power: 160W
[lp-1 ] DEBUG 2024/09/25 20:00:33 charge currents: [0.57 0.56 0.63]A
[modbus] TRACE 2024/09/25 20:00:33 modbus: send 39 b2 00 00 00 06 01 03 79 1a 00 01
[modbus] TRACE 2024/09/25 20:00:33 modbus: recv 39 b2 00 00 00 05 01 03 02 00 00
[modbus] TRACE 2024/09/25 20:00:33 modbus: send 39 b3 00 00 00 06 01 03 79 1d 00 01
[modbus] TRACE 2024/09/25 20:00:33 modbus: recv 39 b3 00 00 00 05 01 03 02 00 00
[site ] DEBUG 2024/09/25 20:00:33 pv power: 0W
[modbus] TRACE 2024/09/25 20:00:33 modbus: send 39 b4 00 00 00 06 01 03 79 3c 00 01
[modbus] TRACE 2024/09/25 20:00:33 modbus: recv 39 b4 00 00 00 05 01 03 02 00 00
[modbus] TRACE 2024/09/25 20:00:33 modbus: send 39 b5 00 00 00 06 01 03 79 3e 00 01
[modbus] TRACE 2024/09/25 20:00:33 modbus: recv 39 b5 00 00 00 05 01 03 02 00 5c
[site ] DEBUG 2024/09/25 20:00:33 battery soc: 92%
[site ] DEBUG 2024/09/25 20:00:33 battery power: 0W
[modbus] TRACE 2024/09/25 20:00:33 modbus: send 39 b6 00 00 00 06 01 03 79 32 00 01
[modbus] TRACE 2024/09/25 20:00:33 modbus: recv 39 b6 00 00 00 05 01 03 02 fe 1e
[modbus] TRACE 2024/09/25 20:00:33 modbus: send 39 b7 00 00 00 06 01 03 79 33 00 01
[modbus] TRACE 2024/09/25 20:00:33 modbus: recv 39 b7 00 00 00 05 01 03 02 ff 14
[modbus] TRACE 2024/09/25 20:00:33 modbus: send 39 b8 00 00 00 06 01 03 79 34 00 01
[modbus] TRACE 2024/09/25 20:00:33 modbus: recv 39 b8 00 00 00 05 01 03 02 ff 67
[site ] DEBUG 2024/09/25 20:00:33 grid meter: 871W
[modbus] TRACE 2024/09/25 20:00:33 modbus: send 39 b9 00 00 00 06 01 03 7d 0c 00 02
[modbus] TRACE 2024/09/25 20:00:33 modbus: recv 39 b9 00 00 00 07 01 03 04 00 00 e4 ea
[site ] DEBUG 2024/09/25 20:00:33 site power: 871W
[lp-1 ] DEBUG 2024/09/25 20:00:33 charge voltages: [232 233 234]V
[lp-1 ] DEBUG 2024/09/25 20:00:33 detected connected phases: 3p
[lp-1 ] DEBUG 2024/09/25 20:00:33 charge total import: 133.360kWh
[lp-1 ] DEBUG 2024/09/25 20:00:33 charger status: B
[mqtt ] TRACE 2024/09/25 20:00:37 recv SoC_Genesis: '{"SoC_Display":87.5,"raw":"102E620105FFFB74210F012C01012C11221010101010114423FA99E800006410240003E8107A940025AF000000000000260010111011AAAA"}'
[ocpp ] TRACE 2024/09/25 20:00:40 received JSON message from 60AH73B037AQ016: [2,"9cb1c476-d339-480c-a5e9-1c18d3adbe03","MeterValues",{"connectorId":1,"transactionId":1727026609,"meterValue":[{"timestamp":"2024-09-25T18:00:40Z","sampledValue":[{"value":"232.30","context":"Sample.Periodic","format":"Raw","measurand":"Voltage","phase":"L1","unit":"V"},{"value":"233.37","context":"Sample.Periodic","format":"Raw","measurand":"Voltage","phase":"L2","unit":"V"},{"value":"233.79","context":"Sample.Periodic","format":"Raw","measurand":"Voltage","phase":"L3","unit":"V"},{"value":"0.00","context":"Sample.Periodic","format":"Raw","measurand":"Current.Import","phase":"L1","unit":"A"},{"value":"0.00","context":"Sample.Periodic","format":"Raw","measurand":"Current.Import","phase":"L2","unit":"A"},{"value":"0.00","context":"Sample.Periodic","format":"Raw","measurand":"Current.Import","phase":"L3","unit":"A"},{"value":"0","context":"Sample.Periodic","format":"Raw","measurand":"Power.Active.Import","unit":"W"},{"value":"133360","context":"Sample.Periodic","format":"Raw","measurand":"Energy.Active.Import.Register","unit":"Wh"}]}]}]
[ocpp ] TRACE 2024/09/25 20:00:40 handling incoming CALL [9cb1c476-d339-480c-a5e9-1c18d3adbe03, MeterValues] from 60AH73B037AQ016
[ocpp ] TRACE 2024/09/25 20:00:40 sent CALL RESULT [9cb1c476-d339-480c-a5e9-1c18d3adbe03] for 60AH73B037AQ016
[ocpp ] TRACE 2024/09/25 20:00:40 sent JSON message to 60AH73B037AQ016: [3,"9cb1c476-d339-480c-a5e9-1c18d3adbe03",{}]
[db ] TRACE 2024/09/25 20:00:42 INSERT INTO `settings` (`key`,`value`) VALUES ("lp1.minCurrent","6"),("lp1.maxCurrent","16"),("lp1.phasesConfigured","3"),("adminPassword","$2a$10$jw6Q7BLbtkTUp2YwNjc7aetpQXS3xi1Lc8tCfjYuxFHfkRh877nvK"),("jwtSecretKey","ddaf99063f9ef1bd5d6f75c60e4109f39e2011fb8c2cf9cdfc77ced75dbee8a7"),("lp1.mode","off"),("lp1.smartCostLimit","0.22"),("batteryDischargeControl","true"),("prioritySoc","60"),("bufferSoc","85"),("bufferStartSoc","0"),("batteryGridChargeLimit","0.16") ON CONFLICT (`key`) DO UPDATE SET `value`=`excluded`.`value` 12 <nil>
[site ] DEBUG 2024/09/25 20:00:43 ----
[lp-1 ] DEBUG 2024/09/25 20:00:43 charge power: 0W
[lp-1 ] DEBUG 2024/09/25 20:00:43 charge currents: [0 0 0]A
[modbus] TRACE 2024/09/25 20:00:43 modbus: send 39 ba 00 00 00 06 01 03 79 1a 00 01
[modbus] TRACE 2024/09/25 20:00:43 modbus: recv 39 ba 00 00 00 05 01 03 02 00 00
[modbus] TRACE 2024/09/25 20:00:43 modbus: send 39 bb 00 00 00 06 01 03 79 1d 00 01
[modbus] TRACE 2024/09/25 20:00:43 modbus: recv 39 bb 00 00 00 05 01 03 02 00 00
[site ] DEBUG 2024/09/25 20:00:43 pv power: 0W
[modbus] TRACE 2024/09/25 20:00:43 modbus: send 39 bc 00 00 00 06 01 03 79 3c 00 01
[modbus] TRACE 2024/09/25 20:00:43 modbus: recv 39 bc 00 00 00 05 01 03 02 00 00
[modbus] TRACE 2024/09/25 20:00:43 modbus: send 39 bd 00 00 00 06 01 03 79 3e 00 01
[modbus] TRACE 2024/09/25 20:00:43 modbus: recv 39 bd 00 00 00 05 01 03 02 00 5c
[site ] DEBUG 2024/09/25 20:00:43 battery soc: 92%
[site ] DEBUG 2024/09/25 20:00:43 battery power: 0W
[modbus] TRACE 2024/09/25 20:00:43 modbus: send 39 be 00 00 00 06 01 03 79 32 00 01
[modbus] TRACE 2024/09/25 20:00:43 modbus: recv 39 be 00 00 00 05 01 03 02 fe 19
[modbus] TRACE 2024/09/25 20:00:43 modbus: send 39 bf 00 00 00 06 01 03 79 33 00 01
[modbus] TRACE 2024/09/25 20:00:43 modbus: recv 39 bf 00 00 00 05 01 03 02 ff 17
[modbus] TRACE 2024/09/25 20:00:43 modbus: send 39 c0 00 00 00 06 01 03 79 34 00 01
[modbus] TRACE 2024/09/25 20:00:43 modbus: recv 39 c0 00 00 00 05 01 03 02 ff 63
[site ] DEBUG 2024/09/25 20:00:43 grid meter: 877W
[modbus] TRACE 2024/09/25 20:00:43 modbus: send 39 c1 00 00 00 06 01 03 7d 0c 00 02
[modbus] TRACE 2024/09/25 20:00:43 modbus: recv 39 c1 00 00 00 07 01 03 04 00 00 e4 eb
[site ] DEBUG 2024/09/25 20:00:43 site power: 877W
[lp-1 ] DEBUG 2024/09/25 20:00:43 charge voltages: [232 233 234]V
[lp-1 ] DEBUG 2024/09/25 20:00:43 detected connected phases: 3p
[lp-1 ] DEBUG 2024/09/25 20:00:43 charge total import: 133.360kWh
[lp-1 ] DEBUG 2024/09/25 20:00:43 charger status: B
[ocpp ] TRACE 2024/09/25 20:00:50 received JSON message from 60AH73B037AQ016: [2,"3c374810-6fd9-4db4-ba59-2b1c4c58dae1","MeterValues",{"connectorId":1,"transactionId":1727026609,"meterValue":[{"timestamp":"2024-09-25T18:00:50Z","sampledValue":[{"value":"232.11","context":"Sample.Periodic","format":"Raw","measurand":"Voltage","phase":"L1","unit":"V"},{"value":"233.36","context":"Sample.Periodic","format":"Raw","measurand":"Voltage","phase":"L2","unit":"V"},{"value":"233.73","context":"Sample.Periodic","format":"Raw","measurand":"Voltage","phase":"L3","unit":"V"},{"value":"0.00","context":"Sample.Periodic","format":"Raw","measurand":"Current.Import","phase":"L1","unit":"A"},{"value":"0.00","context":"Sample.Periodic","format":"Raw","measurand":"Current.Import","phase":"L2","unit":"A"},{"value":"0.00","context":"Sample.Periodic","format":"Raw","measurand":"Current.Import","phase":"L3","unit":"A"},{"value":"0","context":"Sample.Periodic","format":"Raw","measurand":"Power.Active.Import","unit":"W"},{"value":"133360","context":"Sample.Periodic","format":"Raw","measurand":"Energy.Active.Import.Register","unit":"Wh"}]}]}]
[ocpp ] TRACE 2024/09/25 20:00:50 handling incoming CALL [3c374810-6fd9-4db4-ba59-2b1c4c58dae1, MeterValues] from 60AH73B037AQ016
[ocpp ] TRACE 2024/09/25 20:00:50 sent CALL RESULT [3c374810-6fd9-4db4-ba59-2b1c4c58dae1] for 60AH73B037AQ016
[ocpp ] TRACE 2024/09/25 20:00:50 sent JSON message to 60AH73B037AQ016: [3,"3c374810-6fd9-4db4-ba59-2b1c4c58dae1",{}]
[site ] DEBUG 2024/09/25 20:00:53 ----
[lp-1 ] DEBUG 2024/09/25 20:00:53 charge power: 0W
[lp-1 ] DEBUG 2024/09/25 20:00:53 charge currents: [0 0 0]A
[modbus] TRACE 2024/09/25 20:00:53 modbus: send 39 c2 00 00 00 06 01 03 79 1a 00 01
[modbus] TRACE 2024/09/25 20:00:53 modbus: recv 39 c2 00 00 00 05 01 03 02 00 00
[modbus] TRACE 2024/09/25 20:00:53 modbus: send 39 c3 00 00 00 06 01 03 79 1d 00 01
[modbus] TRACE 2024/09/25 20:00:53 modbus: recv 39 c3 00 00 00 05 01 03 02 00 00
[site ] DEBUG 2024/09/25 20:00:53 pv power: 0W
[modbus] TRACE 2024/09/25 20:00:53 modbus: send 39 c4 00 00 00 06 01 03 79 3c 00 01
[modbus] TRACE 2024/09/25 20:00:53 modbus: recv 39 c4 00 00 00 05 01 03 02 00 00
[modbus] TRACE 2024/09/25 20:00:53 modbus: send 39 c5 00 00 00 06 01 03 79 3e 00 01
[modbus] TRACE 2024/09/25 20:00:53 modbus: recv 39 c5 00 00 00 05 01 03 02 00 5c
[site ] DEBUG 2024/09/25 20:00:53 battery soc: 92%
[site ] DEBUG 2024/09/25 20:00:53 battery power: 0W
[modbus] TRACE 2024/09/25 20:00:53 modbus: send 39 c6 00 00 00 06 01 03 79 32 00 01
[modbus] TRACE 2024/09/25 20:00:53 modbus: recv 39 c6 00 00 00 05 01 03 02 fe 22
[modbus] TRACE 2024/09/25 20:00:53 modbus: send 39 c7 00 00 00 06 01 03 79 33 00 01
[modbus] TRACE 2024/09/25 20:00:53 modbus: recv 39 c7 00 00 00 05 01 03 02 ff 16
[modbus] TRACE 2024/09/25 20:00:53 modbus: send 39 c8 00 00 00 06 01 03 79 34 00 01
[modbus] TRACE 2024/09/25 20:00:53 modbus: recv 39 c8 00 00 00 05 01 03 02 ff 69
[site ] DEBUG 2024/09/25 20:00:53 grid meter: 863W
[modbus] TRACE 2024/09/25 20:00:53 modbus: send 39 c9 00 00 00 06 01 03 7d 0c 00 02
[modbus] TRACE 2024/09/25 20:00:53 modbus: recv 39 c9 00 00 00 07 01 03 04 00 00 e4 eb
[site ] DEBUG 2024/09/25 20:00:53 site power: 863W
[lp-1 ] DEBUG 2024/09/25 20:00:53 charge voltages: [232 233 234]V
[lp-1 ] DEBUG 2024/09/25 20:00:53 detected connected phases: 3p
[lp-1 ] DEBUG 2024/09/25 20:00:53 charge total import: 133.360kWh
[lp-1 ] DEBUG 2024/09/25 20:00:53 charger status: B

What type of operating system are you running?

Linux

Nightly build

Version

0.130.12

thse22 commented 4 days ago

Hi, can you check your evcc.yaml configuration. You need a minsoc value. It does not remember your old minsoc... I use the following:

andig commented 4 days ago

You need a minsoc value

No. Evcc has safe defaults of 20/95% for that.

Gics78 commented 4 days ago

Unfortunately andig is correct. Minsoc in .yaml doesn't change anything, still the same problem and the same battery mode timeout errors.

andig commented 3 days ago

Die Frage hier ist doch, warum setzen des Battery Mode zu einem Fehler führt:

[site ] ERROR 2024/09/25 19:59:33 battery mode: read tcp 172.23.0.2:34104->192.168.178.8:502: i/o timeout

Lässt sich das auch mit

evcc charger

nachvollziehen?

/cc @thse22

Gics78 commented 3 days ago

Teste ich nachher! Und die Anschlussfrage: das initiale Setzen des MinSoc durch EVCC scheint ja trotz Fehlermeldung zu funktionieren, das am Ende des Ladevorgangs aber nicht. Warum?

Von meinem iPhone gesendet


Von: andig @.> Gesendet: Thursday, September 26, 2024 8:51:59 AM An: evcc-io/evcc @.> Cc: Gics78 @.>; Author @.> Betreff: Re: [evcc-io/evcc] Active Battery Control FoxESS H3 MinSoC not changed back after charging is finished (Issue #16326)

Die Frage hier ist doch, warum setzen des Battery Mode zu einem Fehler führt:

[site ] ERROR 2024/09/25 19:59:33 battery mode: read tcp 172.23.0.2:34104->192.168.178.8:502: i/o timeout

Lässt sich das auch mit

evcc charger

nachvollziehen?

/cc @thse22https://github.com/thse22

— Reply to this email directly, view it on GitHubhttps://github.com/evcc-io/evcc/issues/16326#issuecomment-2376078644, or unsubscribehttps://github.com/notifications/unsubscribe-auth/BBTOR7RU4CAMDHWPBKO3LADZYOVI7AVCNFSM6AAAAABO3EZW5KVHI2DSMVQWIX3LMV43OSLTON2WKQ3PNVWWK3TUHMZDGNZWGA3TQNRUGQ. You are receiving this because you authored the thread.Message ID: @.***>

Gics78 commented 3 days ago

Lässt sich das auch mit evcc charger nachvollziehen?

Ja, selber Modbus Timeout Fehler. Ich habe mal interessehalber die HA Modbus-Integration installiert. Mit der kann ich den MinSoc bzw. auch den Workmode (self-use -> Backup) erfolgreich steuern, allerdings kommt bei Workmode (nicht beim Einstellen des MinSoc) auch eine Fehlermeldung zurück Start: 41000; values: [2]; slave: 1 from tcp://192.168.178.8:502: Modbus Error: [Input/Output] Modbus Error: [Invalid Message] No response received, expected at least 8 bytes (0 received)

Vielleicht ein ähnliches Problem?

andig commented 3 days ago

Tja. Jetzt ist die Frage warum? Was sagt der Hersteller?

Gics78 commented 1 day ago

FoxEss sagt dass es eine offene API gibt. Nachdem ich aber stark annehme dass EVCC das lokal über den Modbus umsetzt ist doch vielmehr die Frage wie das umgesetzt wurde? Möglicherweise bestehen die Probleme weil FoxEss mit neueren Firmware die Register verändert hat? Einen Changelog dazu gibt es leider nie. Ich versuche nochmal die aktuellen Register bei Foxess nachzufragen (die mann dann aber nie veröffentlichen darf).

andig commented 1 day ago

Wozu fehleranfällige Cloud APIs wenn man das Problem lokal lösen kann? Ihr seid die Kunden- macht Druck beim Hersteller! Ansonsten müsste jemand die Cloud API implementieren. Seitens Core Team gibts keine Kapazität schlechtere Lösungen als notwendig zu bauen.

Gics78 commented 1 day ago

@ andigDa bin ich voll bei Dir! Am 28.09.2024 um 11:30 schrieb andig @.***>: Wozu fehleranfällige Cloud APIs wenn man das Problem lokal lösen kann? Ihr seid die Kunden- macht Druck beim Hersteller! Ansonsten müsste jemand die Cloud API implementieren. Seitens Core Team gibts keine Kapazität schlechtere Lösungen als notwendig zu bauen.

—Reply to this email directly, view it on GitHub, or unsubscribe.You are receiving this because you authored the thread.Message ID: @.***>