Open Deiwa52 opened 2 years ago

Deiwa52 commented 2 years ago

Hallo, i am trying to Setup the Same configuration with openHAB, Heidelberg Energy Control Wallbox and the Same ModeBus Getway. But i am Not able to communicate with the Wallbox. Could you Share the Settings of the Modbus Gateway USR-DR302? Thanks

fzahn commented 2 years ago

On page serial port: Set SerialPort to 19200,8,Even,1 Local Port 501, Work Mode "TCP Server" only click option "SImilar RFC2217 On page Expand function: only activate "TCP server-kick off old connection" and "Modbus TCP"

Deiwa52 commented 2 years ago

Hello , Thanks a lot for the quick response!!! The Communication between openHAB and the Gateway looks good now.

I changed The DIP Switches on the Wallbox regarding the documantation of the Manual but the Wallbox LED‘s are flashing (sie times white and 3 times blue) so the Box says Communication Problem with the Master Box ???

I only have One Box and setup this Box as Slave is this correct?

Could you Share your DIP Switch Settings ?

Thanks Michael

Von meinem iPhone gesendet

Am 14.09.2021 um 15:53 schrieb Florian Zahn @.***>:

 On page serial port: Set SerialPort to 19200,8,Even,1 Local Port 501, Work Mode "TCP Server" only click option "SImilar RFC2217 On page Expand function: only activate "TCP server-kick off old connection" and "Modbus TCP"

— You are receiving this because you authored the thread. Reply to this email directly, view it on GitHub, or unsubscribe. Triage notifications on the go with GitHub Mobile for iOS or Android.

Deiwa52 commented 2 years ago

Hello,

It’s working now!! I found my mistake Boy the DIP Switch S2… so everything ok 👌

Thanks a lot for Support

Michael

Von meinem iPhone gesendet

Am 18.09.2021 um 15:53 schrieb Michael Teuber @.***>:

Hello , Thanks a lot for the quick response!!! The Communication between openHAB and the Gateway looks good now.

I changed The DIP Switches on the Wallbox regarding the documantation of the Manual but the Wallbox LED‘s are flashing (sie times white and 3 times blue) so the Box says Communication Problem with the Master Box ???

I only have One Box and setup this Box as Slave is this correct?

Could you Share your DIP Switch Settings ?

Thanks Michael

Von meinem iPhone gesendet

Am 14.09.2021 um 15:53 schrieb Florian Zahn @.***>:

 On page serial port: Set SerialPort to 19200,8,Even,1 Local Port 501, Work Mode "TCP Server" only click option "SImilar RFC2217 On page Expand function: only activate "TCP server-kick off old connection" and "Modbus TCP"

— You are receiving this because you authored the thread. Reply to this email directly, view it on GitHub, or unsubscribe. Triage notifications on the go with GitHub Mobile for iOS or Android.