Closed glowaa closed 4 months ago
please use source: github://gekkekoe/esphome-ecodan-hp@8a8a51de65731c120eb0168c350ba484ddecc54d in the meantime instead of @main in the yaml file.
or try to set the thermostats refresh to 60 or higher, it has to do with slow response from certain heat pumps.
Cant change source
INFO ESPHome 2024.5.4 INFO Reading configuration /config/esphome/pompa-ciepla.yaml... INFO Updating https://github.com/gekkekoe/esphome-ecodan-hp@main INFO Updating https://github.com/gekkekoe/esphome-ecodan-hp.git@8a8a51d Failed config
external_components: [source /config/esphome/pompa-ciepla.yaml:41]
couldn't find remote ref 8a8a51d. source: github://gekkekoe/esphome-ecodan-hp@8a8a51d components:
I have FTC6 board and it's working without problem before.
8a8a51de65731c120eb0168c350ba484ddecc54d
use full hash , click on link and copy hash or use above. github is annoying and makes a short version
Version 8a8a51de65731c120eb0168c350ba484ddecc54d is working stable without any problems for over a week
okay thanks it's related to the thermostats then. need more investigation
I've replaced the standard climate controls with a custom climate control. Try the latest and report back. If this still gives issues, then you can always use the previous working version.
After today climate actions heatpump is running even the temperature is bigger than on room sensor
climates don't turn on heating. it's only displaying. from your logging, I see that space heating was activated. that's why it's showing heating.
you have room temp target set at 24 degrees, the heat pump tries to heat to that temp.
I do see that dhw climate is also heating, thats the wrong status, I've fixed that.
I have set target to 20 degrees and 24 is currently on room sensor. Also DHW i set target to 47 degrees and 49.5 is currently on DHW sensor.
Heatpump was off before update, and after update has change to Heating.
that is weird. dhw indication had a bug, fixed. but normal climate should work properly.
the only set it does is setting the target temp depending on you operating mode. did you by change switched the modes in the thermostats? default it switches to cool flow for cooling and compensation for heating (can be change in yaml, but this is default). I do see that it was switched to compensation mode. that might have triggered it. generally you do not need to use the mode switches on the thermostat. just set it via the normal selector.
but I do see space heating activated(as final action), so something is requesting heat (thermostat can't do that, unless you set target above room temp (for room modes))
is it still giving issues? please post the operating modes, room temp sensor values, INx thermostats values
I have update to the newest version.
Now DHW seems be ok, but heating not. After update heatpump change automaticly to Heat Compensation Curve and heating start, after change to Heat Target Temperature still is heating and waterpump is active.
I just pushed an update, please test that. It's a bit difficult since I cannot reproduce it here. If it still gives issues, please revert to https://github.com/gekkekoe/esphome-ecodan-hp/commit/8a8a51de65731c120eb0168c350ba484ddecc54d
please post values from the ESPhome page. http://local_ip to get it. -Zone 1 Room Temp -Zone 1 Room Setpoint Value -Zone 1 Prohibit Heating -Zone 1 Prohibit Cooling Status -Operating mode (both of them) -In1, In5, In6 thermostats
After update sill heating and waterpump on
8a8a51d working values
3-way Valve OFF
Boiler Flow Temp 25.0 °C
Boiler Return Temp 25.0 °C
Booster Heater OFF
Compressor Frequency 0.00 Hz
Controller Version FTC6
Cool COP 0.00
Cool Consumed 0.00 kWh
Cool Delivered 0.00 kWh
DHW Off
DHW COP 2.91
DHW Consumed 0.88 kWh
DHW Current Temp 46.5 °C
DHW Delivered 2.56 kWh
DHW Forced OFF
DHW Max Temp Drop 8.0 °C
DHW Mode Eco
Eco
DHW Prohibit OFF
DHW Secondary Temp 25.0 °C
DHW Setpoint 47.0 °C
40.0
60.0
DHW Setpoint Value 47.0 °C
Defrost OFF
ESP IP 192.168.203.123
ESP Internal Temperature 76.7 °F
ESP SSID wifi
ESP Uptime 3808 s
ESP Version 2024.5.5
Estimated Output Power 0.000 kW
Feed Temp 29.0 °C
Flow Rate 0 L/min
Force DHW OFF
Heat Source Heatpump
Heating COP 8.83
Heating Consumed 0.06 kWh
Heating Delivered 0.53 kWh
Heatpump ON
Holiday Mode OFF
Holiday Mode OFF
Immersion Heater OFF
In1 Thermostat OFF
In5 Outdoor Thermostat OFF
In6 Thermostat 2 OFF
Legionella Prevention Temp 65.0 °C
Operating Runtime 3381 h
Operating mode Heat Target Temperature
Heat Target Temperature
Operation Mode Off
Output Power 0.000 kW
Outside Temp 19 °C
Refrigerant Condensing Temp 26.0 °C
Refrigerant Liquid Temp 27.5 °C
Return Temp 27.0 °C
Water Pump Status OFF
WiFi Signal % 68 %
WiFi Signal dB -66 dBm
Zone 1 H/C Setpoint 20.0 °C
5.0
60.0
Zone 1 H/C Setpoint Value 29.0 °C
Zone 1 Prohibit Cooling Status ON
Zone 1 Prohibit Heating OFF
Zone 1 Room Setpoint 22.5 °C
8.0
28.0
Zone 1 Room Setpoint Value 22.5 °C
Zone 1 Room Temp 24.5 °C
AND values after latest update
3-way Valve OFF
Boiler Flow Temp 25.0 °C
Boiler Return Temp 25.0 °C
Booster Heater OFF
Compressor Frequency 0.00 Hz
Controller Version FTC6
Cool COP 0.00
Cool Consumed 0.00 kWh
Cool Delivered 0.00 kWh
DHW Off
DHW COP 2.91
DHW Climate IDLE Current: 46.5, Target: 47.0
5.0
60.0
Mode:
HEAT
DHW Consumed 0.88 kWh
DHW Current Temp 46.5 °C
DHW Delivered 2.56 kWh
DHW Forced OFF
DHW Max Temp Drop 8.0 °C
DHW Mode Eco
Eco
DHW Prohibit OFF
DHW Secondary Temp 25.0 °C
DHW Setpoint Value 47.0 °C
Defrost OFF
ESP IP 192.168.203.123
ESP Internal Temperature 80.0 °F
ESP SSID wifi
ESP Uptime 233 s
ESP Version 2024.5.5
Estimated Output Power 0.000 kW
Feed Temp 22.5 °C
Flow Rate 13 L/min
Force DHW OFF
Heat Source Heatpump
Heating COP 8.83
Heating Consumed 0.06 kWh
Heating Delivered 0.53 kWh
Heatpump ON
Holiday Mode OFF
Holiday Mode OFF
Immersion Heater OFF
In1 Thermostat OFF
In5 Outdoor Thermostat OFF
In6 Thermostat 2 OFF
Legionella Prevention Temp 65.0 °C
Operating Runtime 3381 h
Operation Mode Space Heating
Output Power 0.000 kW
Outside Temp 19 °C
Refrigerant Condensing Temp 26.0 °C
Refrigerant Liquid Temp 27.5 °C
Return Temp 22.5 °C
Selected operating mode Heat Target Temperature
Heat Target Temperature
Water Pump Status ON
WiFi Signal % 60 %
WiFi Signal dB -70 dBm
Zone 1 Climate HEATING Current: 24.5, Target: 22.5
5.0
60.0
Mode:
HEAT
Zone 1 H/C Setpoint Value 23.0 °C
Zone 1 Prohibit Cooling Status ON
Zone 1 Prohibit Heating OFF
Zone 1 Room Setpoint Value 22.5 °C
Zone 1 Room Temp 24.5 °C
I do have climate on heat as well, if set to off it restore itsef to heat immediatly, pump stay off probably because i did set Heating prohibited in this season. Got this from log [16:25:32][W][select:111][serial_rx_task]: 'Modalità Funzionamento' - Option Heat Compensation Curve is not a valid option
Yesterday was ok
the climate shows the selected heating/cooling mode. So heating when you have selected 'heat flow/room temp/compensation curve'. The action indicate if it's actually busy. It will show Idle probably in your case. Once it's heating, you will see the action turn into heating.
You can configure the heating/cooling switch. see updated readme. But it only switches to that mode. Regarding the error, I think it's an translation issue. check if options for mode select is okay ?
@glowaa I see space heating is active, but compressor is at 0hz. but pump is on. This is probably during startup. The selected mode is space heating, So would not expect it to be active. can you try to poweroff the unit (via circuit breaker) and turn it on again? Is it still giving issues?
If I select heat temp, then it looks like this: It's idle, but currently in one of the heating modes
Seems be working ok now. I will wait what about actions from node-red automotion.
good, so the not updating is solved with these custom climates? Did you had any automations that uses the number sliders ? You should change that to the climate ones. I've temporary enabled the sliders, but will remove them once there are no complaints about the climates.
Automotions works, but ESP statuses is not stable
For now https://github.com/gekkekoe/esphome-ecodan-hp/commit/8a8a51de65731c120eb0168c350ba484ddecc54d is one without this issue.
hmm try to run https://github.com/gekkekoe/esphome-ecodan-hp/commit/8a8a51de65731c120eb0168c350ba484ddecc54d and monitor DHW mode. The climates should not affect that sensor. Could be that wifi is dropping. I made some small improvements, please test latest and report back. Also try https://github.com/gekkekoe/esphome-ecodan-hp/commit/8a8a51de65731c120eb0168c350ba484ddecc54d for a couple of hours and compare dhw mode.
On https://github.com/gekkekoe/esphome-ecodan-hp/commit/8a8a51de65731c120eb0168c350ba484ddecc54d whole week without this issue and wifi is not droping i have that checked on my AP.
Newest version not install.
HARDWARE: ESP32 240MHz, 320KB RAM, 4MB Flash
configure cooling/heating action in ecodan-esphome.yaml (see readme, default cooling/heating switch needs to be defined) add these lines https://github.com/gekkekoe/esphome-ecodan-hp/blob/050785cb841b0f7b7c852d27532ab3b0f526fa9e/ecodan-esphome.yaml#L4-L7 you can configure the default cool/heat switch yourself this way. it's a new breaking change.
Seems to be working ok now.
good, I think it's a timing issue, I turned of the climate, but latest version changes that. it's display only.
After you added climate control, DHW current temp not updating. Also heatpump frequently update a lot of statuses.
Example DHW Mode
June 1, 2024 Changed to Eco 12:50:57 PM - 35 seconds ago Became unavailable 12:50:56 PM - 36 seconds ago Changed to Eco 12:44:57 PM - 7 minutes ago Became unavailable [cleaned up log]