The two batteries don't know about each other. This is important so you can simulate multiple battery options at the same time and see how much each one would save you without them competing. If you want to simulate 2 power walls you should create a single custom battery with twice the capacity, charge and discharge rates of a single power wall.
On Sat, 9 Sept 2023, 10:58 mikeykau, @.***> wrote:
This is more of a how to question. I want to simulate two Powerwalls. I set them both up, but when my house is consuming 6kW, both batteries discharge at 5kW, with the simulated grid being 1kW. It should instead show 3kW coming from each battery in this scenario, and zero from grid. Is it possible I have configured something wrong?
— Reply to this email directly, view it on GitHub https://github.com/hif2k1/battery_sim/issues/94, or unsubscribe https://github.com/notifications/unsubscribe-auth/AFAIZGMTJN4WB7WO4VVKPM3XZQ4UJANCNFSM6AAAAAA4RK3VYE . You are receiving this because you are subscribed to this thread.Message ID: @.***>
This is more of a how to question. I want to simulate two Powerwalls. I set them both up, but when my house is consuming 6kW, both batteries discharge at 5kW, with the simulated grid being 1kW. It should instead show 3kW coming from each battery in this scenario, and zero from grid. Is it possible I have configured something wrong?