Closed GoogleCodeExporter closed 9 years ago
AEC recommends:
Receptacle (Radiative = 0.20, Latent = 0.00, Convective = 0.80, Lost = 0.00)
Gas Equipment (Radiative = 0.15, Latent = 0.20, Convective = 0.65, Lost = 0.00)
For receptacle and gas equipment, the latent fraction and convective/radiative
splits are prescribed values. Recommendations are based on ASHRAE 2009 HOF with
rough assumptions of what non-process equipment is typical.
For Process, Electrical and Process, Gas inputs, since these are optional and
highly application dependent, we recommend that these splits can be set by the
user, with baseline same as proposed.
Original comment by JohnJArent
on 5 Apr 2013 at 4:21
Revising status to resolved but leaving open since rules do not completely
reflect what is indicated for process loads; see rules for:
Spc:ProcElecRadFrac
Spc:ProcGasPwrDens
Original comment by da...@360-analytics.com
on 24 Sep 2013 at 1:45
Rules now match the ACM
Original comment by ncz...@archenergy.com
on 15 Nov 2013 at 7:35
Original issue reported on code.google.com by
da...@360-analytics.com
on 25 Mar 2013 at 8:35