5.8.2 - Chiller - Air-Cooled Condenser Power #209

Closed GoogleCodeExporter closed 9 years ago

GoogleCodeExporter commented 9 years ago
What NACM Section(s) are relevant to this issue?
5.8.2 - Chiller - Air-Cooled Condenser Power

Explanation of issue:
Table 110.2-D specifies that air-cooled chillers without condensers must be 
rated with matching condensers and comply with the air-cooled chiller 
efficiency requirements.  I.e., the COP data entered for these chillers must 
include the condenser power.  Therefore, there should not be data entered for 
this descriptor.  

Proposed resolution:
Delete this descriptor from the ACM. 

Please provide any additional information below.

Original issue reported on code.google.com by rhedr...@archenergy.com on 22 Apr 2013 at 10:35

GoogleCodeExporter commented 9 years ago
I agree - making this change 5/2/13 - see change notes

Original comment by JohnJArent on 2 May 2013 at 4:48