What NACM Section(s) are relevant to this issue?
5.8.2 - Chiller - Air-Cooled Condenser Power
Explanation of issue:
Table 110.2-D specifies that air-cooled chillers without condensers must be
rated with matching condensers and comply with the air-cooled chiller
efficiency requirements. I.e., the COP data entered for these chillers must
include the condenser power. Therefore, there should not be data entered for
this descriptor.
Proposed resolution:
Delete this descriptor from the ACM.
Please provide any additional information below.