Sorry I missed your call, on another line.
I like Option A since it is, general, but from a standards/input perspective,
almost now one knows how much power these fans really consume. Usually, all
that is known is the nameplate hp of the draft fan. I would suggest that we
actually add two terms:
Boiler:DraftFanHp -> Units = hp, this would be defined in the ACM and be what
the user inputs. The ACM would dictate rules for how the nameplate draft fan
power is converted to the parasitic power value
Boiler:ParasiticLoad -> Units = W. Definition follows E+ documentation.
Original comment by da...@360-analytics.com
on 9 May 2013 at 8:53
SOunds good. I will add to master update list and ask John to make
corresponding changes to the ACM.
Original comment by rhedr...@archenergy.com
on 10 May 2013 at 3:07