5.8.2 - Confirm chiller curves to be included in Appendix 5.7 #219

Closed GoogleCodeExporter closed 9 years ago

GoogleCodeExporter commented 9 years ago
What NACM Section(s) are relevant to this issue?
5.8.2 Chillers
  Chiller Cooling Capacity Adjustment Curve 
  Electric Chiller Cooling Efficiency Adjustment Curves

Explanation of issue:
I am in the processor incorporating the updatin Appendix 5.7 with the current 
chiller curve data, and want to confirm the following:

1) The PATH A and B curves are currently the only curves applicable to modeling 
water-cooled chillers for compliance analysis  

2) Taylor includes Path A and B curves EIR_fPLT&dT that are valid for DOE-2.2. 

Proposed resolution:
1) The tables in the ACM text that include other water-cooled chiller curves 
are not used and should not be included in the Appendix 5.7 workbook. 

2)  Include the Path A&B EIR_fPLT&dT curves in Appendix 5.7 so that compliance 
tools that support these curves can use them.

Please provide any additional information below.
Attached is the workbook that includes the Path A+B curves.

Original issue reported on code.google.com by da...@360-analytics.com on 10 May 2013 at 8:36

Attachments:

GoogleCodeExporter commented 9 years ago
Changing status to Resolved. There are some issues with some of the chiller 
curves that have been converted to SI, but I believe this is a separate issue.

Original comment by JohnJArent on 30 May 2013 at 6:46

GoogleCodeExporter commented 9 years ago
Resolution implemented in Appendix 5.7 and ACM.  Closing issue and assume 
John/Roger will open new issue related to other chiller curve issues.

Original comment by da...@360-analytics.com on 24 Sep 2013 at 9:29

GoogleCodeExporter commented 9 years ago

Original comment by da...@360-analytics.com on 24 Sep 2013 at 9:29