Closed GoogleCodeExporter closed 9 years ago
Original comment by da...@360-analytics.com
on 21 Jun 2012 at 5:34
I will have to review the E+ model to see if we are lacking any important
inputs that would be entered by the user. I currently have an input for total
cooling capacity and another for sensible heat capacity, which can be used by
the software to calculate SHR.
The coil bypass factor (if we keep it) will not be used by E+. Perhaps it would
be cleaner to add an additional building descriptor for "Coil Latent Modeling
Method" which would have 1 of 2 values, and then that would trigger the use of
a list of inputs depending upon the choice (which would normally be fixed for a
given program).
As much as I would like to remove the BF from the ACM, it seems to have a
significant effect on the cooling kWh, so we may need to keep it.
Original comment by JohnJArent
on 22 Jun 2012 at 10:27
Original comment by JohnJArent
on 27 Jun 2012 at 9:40
Current plan is to:
1. Keep Coil Bypass Factor specified as fixed default by equipment type
2. Keep Coil Bypass Factor performance curves with fixed defaults
3. EnergyPlus can determine Sensible Heat Ratio from Total Cooling Capacity and
Sensible Heat Capacity
Any other inputs required for EnergyPlus?
Original comment by JohnJArent
on 6 Jul 2012 at 11:57
The curve "Total Cooling Capacity Function of Flow Fraction" appears to be
important for determining the DX coil capacity at reduced flow rates, which in
turn, will impact the latent coil capacity. Since the System 5 is a PVAV w/ DX
coil, I think this curve is important to define in the ACM.
Other than this, I would have to dig into the the equations deeper and run some
simulations to provide any more input. Perhaps Kyle or some of the other E+
experts at NREL would have some better insight.
Original comment by da...@360-analytics.com
on 7 Jul 2012 at 6:28
The solution is to add a Coil Latent Modeling Method building descriptor that
indicates which model is to be used:
bypass factor (DOE-2)
NTU effectiveness (EnergyPlus)
Coil Bypass and Coil Bypass Factor Adjustment Curve are only applicable to the
"bypass factor" method.
Add a Total Cooling Capacity function of flow" curve to ACM and Appendix 5.7.
Curve shall be fixed in proposed and standard design.
updating ACM in v1.6, need to add new performance curve in Appendix 5.7.
Original comment by JohnJArent
on 27 Mar 2013 at 6:19
Reviewed and confirmed in v1.6. Adding relevant terms to SDD master update list
Original comment by da...@360-analytics.com
on 3 Apr 2013 at 12:48
Original issue reported on code.google.com by
da...@360-analytics.com
on 21 Jun 2012 at 5:28