Taylor Engineering also agrees with restricting user entry of data for large DX
equipment, but Martha Brook wishes to keep this option open.
No change required for now.
Original comment by JohnJArent
on 2 May 2013 at 5:34
Reopening this as "Discussion" - Roger wishes to not allow this in the ACM (and
I agree with that approach), but it is currently in place, and Martha Brook
wants this option. Recommend having a brief discussion with Martha about it
before removing it.
Original comment by JohnJArent
on 22 Nov 2013 at 6:29
The resolution is to eliminate user entry of performance curves for large DX
equipment (>135,000 Btu/h nominal capacity). For units with capacity >65 kBtu/h
and <135 kBtu/h, the ACM compliance software vendor may work with manufacturers
to develop performance curves that are applicable for specific equipment.
See attached.
Original comment by JohnJArent
on 4 Dec 2013 at 6:43