Closed martin131 closed 1 month ago
Hello @martin131 ,
I'm sorry but I don't understand what you think is wrong and what you want. Can you follow the template please ? "I see ..." but "I want that ..."
@ jmcollin78 As it takes about 2 minutes for the valve to open, the switch should not be turned on as often as shown in the screenshot. Is there any way to set a minimum time for the switch to be on?
I don't think it behaved like this last winter, is it possible?
You have some parameters like: min activation delay (in advanced menu) that can help. Your configuration seems correct: minimal_activation_delay_sec: 300. So it means the activation of the switch is for 5 min at minima.
But I understand you have a valve (a TRV ?). I wonder if controling a valve through a switch is a good idea. A switch is reputed to be instantaneous on or off not to take 2 minutes to open.
It is not TRV. There are only two positions - OPEN and CLOSE.
Are you sure the parameter minimal_activation_delay_sec is working correctly?
That is indeed a TRV. It requires a couple minutes to fully open or fully close. Obviously, using a switch is not the greatest idea, however there doesn't seem to be a good plugin to overcome the limitations with it. So I'm also using this thermostat on a single TRV.
Are you sure the parameter minimal_activation_delay_sec is working correctly?
Yes. I do a test today and it is working as expected.
There is a problem in your configuration: the minimal_activation_delay is 5 min (300 sec) but the cycle is also 5 min. So the activation will occurs only if the on_percent is 100%.
This parameter should be configured having in mind this rules: at each cycle, the algo calculates a on_time_sec which is the on_percent x cycle. If the resulting value is < minimal_activation_delay, then the activation of the switch is canceled.
If your valve take 5 minutes to opens (!! how is that possible ...) , you should set the minimal_activation_delay to 5 min but the cycle to let says 15 min. So that, it will never start opening the valve for less that 5 minutes.
Thank you very much :-) I just changed the cycle time to 15 minutes, we will see.
And yes, it really does take 5 minutes to open. It is a slow but absolutely silent valve.
I will close the issue. Please reopen if you think there is still an issue
Hi, is there any better way how can I control my thermostat? I am using 230 V valves (https://www.elektrobock.cz/termoelektricky-pohon/p1734) controlled by the Sonoff board.
It takes a few minutes to open valves and vtherm is controlling switches too often, I think.
config: