Open joesinger12 opened 1 year ago
The E+ hourly output: Output:Variable,,Plant Supply Side Unmet Demand Rate,hourly; can't be used for case of WSHP water loop.
An alternative solution is required unless we can control the supply side outlet temperature and not the boiler outlet temperature. An alternative solution is to use post-process calculated values and shows not compliance when:
note: pump heat is not added into the flow so we don't need to consider the pump heat.
Original comment by: joesinger12
I've figured out the cause of the WSHP water loop not controlling the water temperature at the supply side outlet but at the boiler and cooling tower outlet. The cause of this behavior is the PlantEquipmentOperation:ComponentSetpoint is added to the PlantEquipmentOperationSchemes in EnergyPlus. We can control the supply outlet temperature by removing PlantEquipmentOperation:ComponentSetpoint from the scheme list. I've done some tests and confirmed it, see attached files. we can also remove the SetpointManagers which are added to the outlet of the boiler and the cooling tower since they are added only for PlantEquipmentOperation:ComponentSetpoint and are redundant after the scheme removal.
Once we can control the supply outlet temperature we can eliminate all the positive "Plant Supply Side Unmet Demand Rate" if the equipment can provide sufficient heating or cooling. So, "Plant Supply Side Unmet Demand Rate" can be a good option for determining UMLH.
Another option is to use the supply outlet temperature to determine UMLH, but beware that the outlet temperature can be out of bounds when there is no demand and we should not count those hours as UMLH.
Original comment by: joesinger12
5/3/2023: As per CEC coordination meeting notes o Push to future release o Interim fix: Implement checks for coil to plant sizing in 3.0
Original comment by: joesinger12
Original comment by: joesinger12
Issue
When Load Passing was first implemented (For MF WSHP and FPFC) we identified there is an issue that we do not have a mechanism to determine whether the plant equipment can actually meet the load.
Potential Solution
Add E+ hourly output: Output:Variable,,Plant Supply Side Unmet Demand Rate,hourly; Use this output to generate a plant UMLH OR Calculate % of annual load not met And enforce on that
Reported by: joesinger12
Original Ticket: cbecc-com/tickets/3491