11/14/2017 JA working on cooling tower efficiency requirements for CEC
Original comment by: joesinger12
12/4/17 RH - CBECC-Com updates to specify the flow/hp for the baseline to be 60 gpm/hp for all towers >= 300 tons in climate zones other than 3 and 5, and 42.1 gpm/hp for all towers in CZ 3 and 5, and all towers < 300 tons in all climate zones
Original comment by: joesinger12
12/5/17 RH - Change to baseline cooling tower efficiency for 2019 and added checkcode rules to check for minimum cooling tower mandatory minimum efficiencies.
Commit @ r5215/5216
Original comment by: joesinger12
Original comment by: joesinger12
Original comment by: joesinger12
Updates for SPV efficiency committed to /branches/RulesetDev_19-0-2_Issue2546+2543.
Original comment by: joesinger12
Original comment by: joesinger12
Original comment by: joesinger12
Reopening for RH to make updates to rules for the cooling tower efficiency .
Original comment by: joesinger12
In testing merge of 2019 updates to trunk, I found that the 2016 SPVAC/SPVHP min efficiency rule values were not correct. This was fixed for 2019, but wanted to confirm that the 2016 SP2 should include this correction. 2016 SPVAC/SPVHP efficiency requirements were based on Appliance Std Table C-5, whereas the correct reference is 2016 Std Table 110.2-E.
Also, not yet addressed in 2019 or 2016 are the min efficiency rules for non-weatherized space constrained SPV systems. Should this be added for 2019.0.3/2016 SP2?
Original comment by: joesinger12
Made minor update to reference Table 110.2-E for mandatory minimums of SPVHPs. Reference Appliance Efficiency Regaultions for air conditioners with SEER ratings.
Original comment by: joesinger12
Original comment by: joesinger12
Moving to Dev Milestone
Original comment by: joesinger12
Original comment by: joesinger12
2019 NR Case Measure for Fan System Power Reference - http://title24stakeholders.com/proposal-based-on-ashrae-90-1-2016/
DR - List includes: SPVAC (Cooling Mode) <= 65000 Btuh SPVHP (Cooling Mode) <= 65000 Btuh SPVHP (Heating Mode) <= 65000 Btuh Propeller or axial fan closed-circuit cooling towers
Reported by: joesinger12
Original Ticket: cbecc-com/tickets/2543