joesinger12 / TestTicketTransfer

0 stars 0 forks source link

CBECC-Com: Design Day Weather File Error #66

Open joesinger12 opened 5 years ago

joesinger12 commented 5 years ago

11/5/18 User - I noticed that the DDY files that come with CBECC-COM software have negative values for the "Daily Dry-Bulb Temperature Range {C}" field in the SizingPeriod:DesignDay object, for 5 of the CEC climate zones. This field should be positive, but is negative for November 21 SummerDesignDay for the 5 climate zones attached (CZ04, 6, 8, 10, 15). For CZ09 (Burbank-Glendale), this field is also blank for the 6/21 and 7/21 SummerDesignDays. The negative values in these fields causes simulations to fail. Also, these DDY files do not match the DDY files available on the EnergyPlus website.

Why are these values negative? And why do they not match the DDY files on the EnergyPlus website?

Reported by: joesinger12

Original Ticket: cbecc-com/tickets/2887

joesinger12 commented 5 years ago

Original comment by: joesinger12

joesinger12 commented 5 years ago

Original comment by: joesinger12

joesinger12 commented 5 years ago

Original comment by: joesinger12

joesinger12 commented 5 years ago

Original comment by: joesinger12

joesinger12 commented 5 years ago

Sent issue to Joe Huang (creator of the original weather files) to check what the correct values are.

Original comment by: joesinger12

joesinger12 commented 5 years ago

Original comment by: joesinger12

joesinger12 commented 1 year ago

Original comment by: joesinger12