Open joesinger12 opened 5 years ago
User model where the cooling was defined as 1 btu/h and 0 design flow rate for a FPFC. This is causing CBECC to crash during translation. I removed the cooling coil and everything worked fine.
Option 2 to bypass the crash - the user needs to enter a cooling coil capacity for three of the FPFC defined in the model as highlighted below. These FPFC cooling coils currently have a capacity defined as 1 btu/hr. This should be changed to a minimum of 300 btu/hr.
Original comment by: joesinger12
Original comment by: joesinger12
Original comment by: joesinger12
Original comment by: joesinger12
Original comment by: joesinger12
CBECC-Com Application is crashing. Original model developed in EnergyPro
Reported by: joesinger12
Original Ticket: cbecc-com/tickets/2990