Closed GoogleCodeExporter closed 9 years ago
Addition input (JA comments from email):
JA: 'Condensing unit' equipment type does not apply to refrigeration units,
according to AHRI Standard 365
JA: EER requirement is only based on compressor + condenser fan input.
DR: This would then be applicable to EERAdj (EER adjusted to remove fan energy
in AHRI rating) for split systems with capacity >=135 kBtu/hr
KA: Supports not checking IEER because it’s not being directly used by the
software. Need confirmation from CEC.
DR: I agree. Will assume no check of IEER unless CEC indicates otherwise
Original comment by da...@360-analytics.com
on 25 Aug 2013 at 10:00
Closing issue. Rules to be committed in next day or two include CODECHECK for
EERAdj (applicable to SplitSystem only).
Just to note: using the default fan energy assumption @ AHRI conditions, I
found there should never be a condition where a split system meets the overall
minimum EER requirement, but not the condensing unit minimum EER requirement.
Therefore, this CODECHECK is a bit redundant...
As recommended by JA, no check of IEER requirement for any systems.
Original comment by da...@360-analytics.com
on 25 Sep 2013 at 6:26
Original issue reported on code.google.com by
da...@360-analytics.com
on 18 Aug 2013 at 7:40Attachments: