The first problem you are having can be fixed by going to the Space data screen
and using the Thermal Zone Reference dropdown to associate the spaces and
thermal zones.
In your air system, you have not added any components. You will need to add
supply and return air segments, a cooling coil, heating coil, fan, outdoor air
control and terminal unit objects to your system. You will also need to
associate the terminal unit and thermal zone.