David, We'll use 90.1 2013 requirements for this. Table 6.5.1.4 of 90.1 2013
specifies DX cooling stage requirements for systems that control space
temperature by modulating air flow.
Systems with rated capacity >=65,000 btu/h and <240,000 btu/hr would be modeled
with 3 cooling stages.
Systems with rated capacity >=240,000 btu/h would be modeled with 4 cooling
stages
Does this work?
Original comment by supriya....@pnnl.gov
on 9 Oct 2014 at 6:35
[deleted comment]
We currently only support the E+ DX:SingleSpeed and DX:TwoSpeed E+ objects. I
suppose we could add another set of curves to try and approximate the 3 and 4
stage cooling systems, but we don't currently have those curves prepared.
Original comment by da...@360-analytics.com
on 9 Oct 2014 at 7:51
David,
We discussed this internally and 2 stage of control would work fine for DX
systems.
90.1 2013 section 6.5.1.3 on integrated economizer control specifies that units
that include an integrated air side economizer are required to have 2 stages of
cooling. All other units (without integrated economizer control) are required
to have 3 or 4 stages of cooling.
for App G we can stick to 2 stages of cooling for rated cap >75,000 Btu/h
according to 90.1 2013 and ignore the requirement for 3 or 4 stage cooling for
systems without economizer.
Does this work better?
Original comment by supriya....@pnnl.gov
on 9 Oct 2014 at 10:00
Yes, this works. Do you want this capacity threshold to apply all the Phase 1
baseline HVAC system types with DX coils (#5/6-Multi-zone, #3/4-Single-zone),
or just #5/6?
Original comment by da...@360-analytics.com
on 9 Oct 2014 at 10:33
Just 5/6.
Since 3/4 have CAV fans the capacity control requirements wouldn't apply to
those.
I'll go ahead and make the required revisions to the PRM
Original comment by supriya....@pnnl.gov
on 9 Oct 2014 at 10:50
Original comment by da...@360-analytics.com
on 14 Oct 2014 at 4:57