I suspect the second error message is the real issue here. EnergyPlus only
allows airflow per ton of cooling capacity of around 400 cfm/ton, with actual
limits that I think are about 350 cfm/ton on the low end and 450 or 500 cfm/ton
on the upper end. Check the airflow and cooling capacity of CoilCooling 28 and
make sure that the ratio is in that range.