Closed GoogleCodeExporter closed 9 years ago
The original model you sent had a bunch of errors related to cfm/ton ratios
being out of range on 8 of the 15 VRV units. When I fixed those, I did still
get the errors related to the multiplier. These are really due to the
inability of version 2b to properly handle situations where PriAirCondgSysRef
and VentSysRef were not the same, i.e., with a DOAS. There is no workaround
for this that I am aware of. This bug was fixed in version 3.
Original comment by rhedr...@archenergy.com
on 3 Dec 2014 at 4:48
Original issue reported on code.google.com by
f.le...@gmail.com
on 24 Nov 2014 at 9:55Attachments: