Closed GoogleCodeExporter closed 9 years ago
Roger may have guidance on the first question.
Regarding when an economizer is required: first, the economizer requirement is
a prescriptive requirement, so it is never mandatory for the proposed case. The
standard design (baseline) will have an integrated economizer for systems with
cooling capacity above 54 kBtu/h when the system provides outside air
ventilation as well as cooling.
Some systems that have no ducts (PTAC, Four-pipe fan coil, VRF) by definition
cannot have an airside economizer and therefore won't have an economizer in the
performance method (unless, in the case of VRF systems, their performance is
approximated by a packaged single zone or PVAV unit that delivers outside air
in the model. Table 4-17 does not apply to CBECC or the performance method,
since all tradeoffs are done in the software.
Assuming that CBECC will at some point have a VRF model that models the
performance of these systems, IF and WHEN that is available, the VRF model
would not include an economizer. The standard design likely would. The VRF
system would require a separate dedicated outside air system that provides the
necessary ventilation requirements for the zones served by the VRF system. This
system would likely use 100% outside air, so would not need an economizer.
I will see if I can document this more clearly in the ACM Reference Manual -
that airside economizers do not apply to some types of systems.
Original comment by JohnJArent
on 3 Dec 2014 at 11:02
CBECC-Com can model split system heat pumps, but cannot model VRF systems as
yet. There is an Exceptional Design compliance procedure that can be followed
which allows use of the VRF modeling capabilities in EnergyPlus. See
http://bees.archenergy.com/faq_software.html#excep for additional information.
The economizer requirement is a prescriptive requirement, so it is never
mandatory for the proposed case. The standard design (baseline) will have an
integrated economizer for systems with cooling capacity above 54 kBtu/h when
the system provides outside air ventilation as well as cooling.
Some systems that have no ducts (PTAC, Four-pipe fan coil, VRF) by definition
cannot have an airside economizer and therefore won't have an economizer in the
performance method (unless, in the case of VRF systems, their performance is
approximated by a packaged single zone or PVAV unit that delivers outside air
in the model). Table 4-17 does not apply to CBECC or the performance method,
since all tradeoffs are done in the software.
When VRF systems are included in CBECC-Com, the VRF model would not include an
economizer. The standard design will. The VRF system will likely require a
separate dedicated outside air system that provides the necessary ventilation
requirements for the zones served by the VRF system. This system would likely
use 100% outside air, so would not need an economizer.
Original comment by rhedr...@archenergy.com
on 3 Dec 2014 at 11:10
Original issue reported on code.google.com by
f.le...@gmail.com
on 2 Dec 2014 at 2:15